![Panasonic U-4LE1R8 Скачать руководство пользователя страница 54](http://html1.mh-extra.com/html/panasonic/u-4le1r8/u-4le1r8_service-manual_4153774054.webp)
Mini VRF SYSTEM
Trouble Diagnosis
3
3-14
3. Mini VRF System Alarm Codes
E05 Error in Indoor Unit Transmitting Signal to the Outdoor Unit
Error Detection Method
Error Diagnosis
It is judged an error when a unit itself cannot receive a signal that it has sent.
Indoor unit control PC board error
The setting of the terminal resistor select switch on the outdoor unit main PC board is set incorrectly.
•
•
For information on the procedures for replacing the indoor unit’s control PC board, refer to the manual that is packaged with
the indoor unit service board.
•
1.
2.
Is the terminal resistor select switch on the outdoor main PC board
set to OPEN?
Is the indoor/outdoor operation line opened or shorted?
1-3
1-4
Replace the indoor unit control PC board.
1-5
Is the indoor/outdoor operation line connected to more than one
outdoor unit? (Network wired?)
1-1
Is the SHORT on the terminal resistor select switch on the outdoor
main PC board set to one unit, and the others are OPEN?
1-2
Make the SHORT
setting
1-4
Yes
No
1-2
1-3
Yes
No
1-4
Set the SHORT to
one unit only
Yes
No
1 Indoor
unit
control
PC board
Correct the wiring
1-5
Yes
No
(for single-phase outdoor unit PC board)
(for 3-phase outdoor unit PC board)
TERMINAL
TERMINAL
SM830209-00̲Mini̲VRF SYS.indb 14
SM830209-00̲Mini̲VRF SYS.indb 14
2012/01/11 18:24:43
2012/01/11 18:24:43