<Timing chart (Normal)>
ON
ON
OFF
OFF
300ms or less
300ms or less
50ms or less
(Note 1)
External device
monitor input
Control output
(OSSD 1 / 2)
Light received
Light blocked
Light received
state
<Timing chart (Error 1)>
ON
ON
OFF
OFF
300ms or less
(Note)
External device
monitor input
Control output
(OSSD 1 / 2)
Light received
Light blocked
Light received
state
Lockout state
<Timing chart (Error 2)>
ON
ON
OFF
OFF
300ms or less
60ms or less
External device
monitor input
Control output
(OSSD 1 / 2)
Light received
Light blocked
Light received
state
Lockout state
Note: The response time depends on the number of beam channels.
Response time (OFF response)
Main sensor
Sub sensor
Number of units in
series connection
1 unit
1 unit
2 units
3 units
4 units
Number of beam channels
4 to 48
6ms
10ms
10ms
12ms
12ms
49 to 96
8ms
10ms
10ms
12ms
12ms
97 to 127
10ms
12ms
12ms
14ms
14ms
128 to 144
−
12ms
12ms
14ms
14ms
145 to 192
−
14ms
14ms
16ms
16ms
193 to 256
−
16ms
16ms
18ms
18ms
Содержание SF4D-*-01 Series
Страница 2: ... Panasonic Industrial Devices SUNX Co Ltd 2020 2 MEMO ...
Страница 6: ... Panasonic Industrial Devices SUNX Co Ltd 2020 6 MEMO ...
Страница 120: ...Functions Panasonic Industrial Devices SUNX Co Ltd 2020 120 MEMO ...
Страница 134: ...Troubleshooting Panasonic Industrial Devices SUNX Co Ltd 2020 134 MEMO ...
Страница 168: ... Panasonic Industrial Devices SUNX Co Ltd 2020 168 MEMO ...