CN6
OLP Booster Heater
Either link across or connect to immersion overload
Zone 1 Room Sensor
CN5
Monobloc Main Control PCB
Outdoor Air Sensor
Tank Hot Water Sensor
Tank Sensor
CN4
External Control 1
Remote Controller
CN3
Boiler Contact
Panasonic Controller
Extra Pump
2 Way Valve 3 Way Valve
C O N C O N
Booster Heater
Heat Cool N L
L
N
E
Earth
CN1
CN2
Immersion Heater 3KW
—
220V
Earth
Heating Control
Wireless Programmable Controller
Base Station
N
PUMP
Heating
Circulation
Pump
Thermostat
Base
Station
L
N
COM
NO
E
Open N E
Open N E
Control Wiring
This shows a basic heating and domestic hot water system as shown on the first page.
Connections are made onto the main control PCB in the monobloc unit.
3 Port Diverting Valve
Motor Open for Tank Mode
Zone Valve
Please Note
•
If you use an immersion (Booster) Heater with the hot water cylinder then the two ter-
minals OLP Booster Heater should be shorted or connected to an overload NC contact
•
Be sure to run the Panasonic Controller cable separately to other cables
•
We recommend taking the immersion heater and the heating pump wiring through local
fused switches mounted next to each (Pump
—
5A and Heater 16A)
•
Ensure the thermostat in the immersion heater is set to maximum
The tank hot water sensor is a Panasonic specific part and not a generic item.
Please confirm all details with the Panasonic installation manuals.
All electrical wiring must be carried out by a competent electrician in accordance with local
and national regulations.