Setting a sterilisation cycle requires an immersion heater controlled by the Panasonic unit, uses 
energy and carries the risk of scalds. Discuss this with the end user.

 

 

Sterilisation is to prevent the growth of legionella.

 

Legionella grows at between 20C and 45C but dies above 45C 

Scald time is minutes for water at 50C but seconds at 60C

 

 

To optimise protection against scalds then choose NO sterilisation cycle, set the tank temperature to 50C and 
lower the Tank Reheat Temperature (* above) to minus 5C.

 

 

To optimise legionella protection then Choose a weekly sterilisation cycle. Discuss the day and time with the 

customer. Choose 60C and 10 minutes. You can set the tank temperature at 45-48C with sterilisation cycle 
set to on. Check the immersion heater physically and ensure the thermostat on it is set to maximum.

 

 

Installer Setup

Service Setup 

After setting up Operation Setup scroll back to the Installer Setup menu and choose Service 
Setup which will give you the options of setting the Pump Maximum Speed, Pump Down Op- 

eration, Dry Concrete Function and Service Contact. Use Pump Maximum Speed to measure 
the water flow rate and check it is sufficient (2.9 l/min per KW), note the flow rate down and 
then set your contact details in Service Contact 

 
 

 

 

 

Function Setup Settings 

 

Enter your 

details

 

 

All that is required now is to go back to the Main Menu choose the Function Setup and check 
the following settings 

 

Room Heater

Set to On 

Tank Heater

Set to On

 

Sterilisation

Set to either ON or OFF according to the notes above in the previous section

 

 

You are now ready to Test the System 

Set this as 
minus 8C *

 

See notes 

Below in red

 

 

Discuss with 
end user

 

Содержание Secon H Series

Страница 1: ... H J Series Typical Installation and setup Monobloc System Revision 1 4 January 10 2022 ...

Страница 2: ...uding for an optional sterilisa tion cycle using the 3 way valve and if needed the Booster Heater which is the name Panasonic use for the immersion heater There is an electric heater inside the monobloc unit Panasonic refer to this as the Backup Heater The 3 way valve is a diverting not a mixing valve When unpowered it provides flow to the buffer tank When powered it cuts off flow to the buffer ta...

Страница 3: ...reeze is used then this should be food safe and pre mixed before intro duction and of the correct strength for the system Most applications will require this The water quality should be tested against Panasonics requirements Part of the startup process involves checking the water flow rate In order for the unit to op erate at all then an absolute minimum low rates must be observed aswell as the re...

Страница 4: ... A 30A 4mm 30mA 2P type AC WH MDC16H6E5 30A 4mm 30mA 2P type A 30A 4mm 30mA 2P type AC WH MDC16J6E5 30A 6mm 30mA 2P type A 30A 4mm 30mA 2P type AC WH MXC09H3E5 30A 6mm 30mA 2P type A 30A 1 5mm 30mA 2P type AC WH MXC09J3E5 30A 6mm 30mA 2P type A 30A 1 5mm 30mA 2P type AC WH MXC12H6E5 30A 6mm 30mA 2P type A 30A 4mm 30mA 2P type AC WH MXC12J6E5 30A 6mm 30mA 2P type A 30A 4mm 30mA 2P type AC All Cable...

Страница 5: ... as shown on the first page Connections are made onto the main control PCB in the monobloc unit 3 Port Diverting Valve Motor Open for Tank Mode Zone Valve Please Note If you use an immersion Booster Heater with the hot water cylinder then the two ter minals OLP Booster Heater should be shorted or connected to an overload NC contact Be sure to run the Panasonic Controller cable separately to other ...

Страница 6: ... expansion vessel is large enough The Panasonic unit contains an expansion tank large enough for 150 litres for single fan and 200 litres for twin fan models For lar ger water volumes or more than 7m height difference then an extra tank is required Check all fuses and circuit breakers Controller Setup on Start Up Once you are in installer mode set the pump to run in Air Purge In the Pump maximum s...

Страница 7: ...pical installation from Installer Setup mode First In the Installer Setup menu choose System Setup Then scroll through each setting and set the values as below Set this as NO Set this as Room Thermostat External Usually don t change this For low power set at 3KW Set this as YES Set this as YES Set this as EXTERNAL Set this as NO ...

Страница 8: ...E info seconrenewables com T 0191 516 6554 W www seconrenewables com Set this as NO Set this as NO Set this as NO Set this as NO Set this as GLYCOL only if anti freeze is used Set this as MANUAL ...

Страница 9: ...Compensation Curve with set tings as below in red For test purposes set this at 55C 45C minus 5C and 15C respectively When testing is finished we recommend changing this to For underfloor heating 35C 30C minus 5C and 15C respectively For modern radiators 45C 35C minus 5C and 15C respectively For old fashioned radiators 52C 40C minus 5C and 15C respectively Set this as 35C during testing then drop ...

Страница 10: ...C with sterilisation cycle set to on Check the immersion heater physically and ensure the thermostat on it is set to maximum Installer Setup Service Setup After setting up Operation Setup scroll back to the Installer Setup menu and choose Service Setup which will give you the options of setting the Pump Maximum Speed Pump Down Op eration Dry Concrete Function and Service Contact Use Pump Maximum S...

Страница 11: ... check that the pump operates and check the flow rate You can adjust the speed if required Checking water flow rate on the go Press hold LEFT RIGHT UP Press the UP LEFT and RIGHT but tons together for 5 seconds while the unit is running then scroll down to address 12 This shows the cur rent water flow rate in l min PRESS HOLD Address Data 10 0 11 0 12 34 5 SCROLL DOWN TO ADDRESS 12 Important Water...

Страница 12: ...ld Be patient Check that the 3 way valve has not operated and the water flow is to the buffer and not hot water cylinder If the water is cold then the unit may operate using the electric heater before initiating actual heat pump operation But gradually the central displayed temperature water flow temperature will increase If you want to test more quickly then switch the local switch for the second...

Страница 13: ...ing a sterilisation cycle Press the centre button to confirm and set the unit to operate Selecting Tank Only mode Now the system should operate in tank mode Note the operation sign next to the Tank icon Now right arrow to set the tank temperature The unit will operate but once again it may take some time to start to heat the water from cold Be patient Check that the 3 way valve has operated and th...

Страница 14: ...lay a fault code which they should report to you So you should now turn the heat pump off on the controller so the green light is off then go back into the Menu of the controller and do the following Go into Installer setup Now select System Setup and then Heat mode Select Water temperature for Heating On This should be set at Compensation Curve Go into the settings for the compensation curve and ...

Страница 15: ...E info seconrenewables com T 0191 516 6554 W www seconrenewables com ...

Страница 16: ...These are a set of functions that can be easily accessed using the quick menu key The user should generally not need to use these but they can be useful in the event of problems or to prevent unauthorised access to the controller For more details consult the User Manual ...

Страница 17: ...yet www seconrenewables com We have a huge range of heat pumps and accessory items Secon Renewables Unit 87 Business Innovation Centre Wearfield Sunderland SR5 2TH W www seconrenewables com E info seconrenewables com T 0191 516 6554 ...