AHU Kit – Installation Instructions –
11/2021
Electrical Wiring
5
As an alternative to using PAW-T10 terminals 1 and 2, it is also possible to use for example con
-
tacts 1 to 4 in Section C of the main control board (“COM” and “DI1” to “DI3”). For correct use of
5.3 Terminal board layout, p. 66
The wiring system shown in the diagram provides the following control functions:
● During the first 3 minutes after unit has been switched to “ON” (either by BMS or by
local remote controller), the delay timer relay will keep the PAW-T10 contacts closed
and operation is permitted.
● After the AHU fan has been started and while the air volume flow is sufficient, the air
flow switch will keep the PAW-T10 contacts closed so that operation continues.
●
Once the set delay time has elapsed, the timer contact will be opened, but the
PAW-T10 contacts will stay closed due to the air flow switch relay.
● When the air volume flow drops below the lower limit, the air flow switch will open
the PAW-T10 contacts and the outdoor unit will stop operation. At the same time the
remote controller in the AHU unit will be locked to prevent unintentional operation.
● The minimum air volume flow should be set on the air flow switch according to the
required minimum air volume flow of each AHU Kit model.
Electric circuit example including a timer and air flow switch
Air flow switch
SET
AL1
OUT
ATU
PV
SV
ºC
ºC
PACi or ECOi/ECO G outdoor unit
AHU Kit
0–10
V capacity control
External control
system
Air Handling Unit (AHU)
Timer
L
N
16
15
14
PAW-T10
L
N
30
56b
31
t
56b1
1
2
3
4
Main terminal board:
Terminals D4 and D5
PAW-T10: Terminals I (1) and I (2)