106
AHU Kit – Installation Instructions –
11/2021
Control
7
4. Press the
SSEETT
button repeatedly to select the entry “PSL”.
TR-16e
SSEETT
repeatedly
5. Use the
and
buttons to change the value to either “0” (= factory setting) for „heating
mode“ or “1” for „cooling mode“.
TR-16e
SSEETT
6.
Confirm the complete parametrization by pressing and holding the
SSEETT
button for
approximatedly 3 seconds.
TR-16e
SSEETT
1 x for 3 sec.
9
Parametrization is now complete. The PV and SV displays have returned to showing the current
temperature and the set temperature values respectively.
Switching from 0–10 V to 2–10 V output signals
The voltage range for the output signals on terminals 6–7 is factory-set to 0–10 V.
Switching the voltage range from 0–10 V to 2–10 V is possible. However, Panasonic recommends
to keep the factory setting.
To switch from 0–10 V to 2–10 V output signals, perform the following steps:
1. Press and hold the
SSEETT
and
buttons jointly for approximately 5 seconds.
TR-16e
SSEETT
1 x 2 buttons for 5 sec.
The PV display shows “PAS”, while the current setting (“0”) in the SV display is blinking.
Note:
After 30 seconds of idleness, the display automatically returns from parametrization view
to normal view.
2. Use the
,
and
buttons to change the value to “–72” (minus 72).
TR-16e
SSEETT
3.
Confirm the new setting by pressing the
SSEETT
button.
TR-16e
SSEETT
1
x
briefly
The PV display now shows “nun”, while the SV display now shows “3”.
4. Press the
SSEETT
button repeatedly to select the entry “AO”.
TR-16e
SSEETT
repeatedly
5. Use the
and
buttons to change the value to either “1” for “output 2 ... 10V” or “2”
(= factory setting) for „output 0 ... 10V“.
TR-16e
SSEETT