57
AHU Kit – Installation Instructions –
11/2021
Installation
There are three different methods to achieve this aim.
Method A: Cutting JP001 to ignore capacity
One possibility is to cut jumper JP001 on the outdoor unit main PCB.
Important
Method A is only applicable to the following combinations of PACi outdoor units and AHU Kits:
●
PACi PEY/PE outdoor units (R410A) and PAH2/PAH3 AHU Kit models
●
PACi PZ2/PZH2 outdoor units (R32) and PAH2/PAH3 AHU Kit models
To cut jumper JP001 on the PACi outdoor unit main PCB, complete the following steps:
1. On the PACi outdoor unit PCB, cut the wire of jumper JP001 at two positions, and take the cut
jumper leads off. Depending on the PACi outdoor unit model, it can be found on the main PCB
at one of the following positions:
JP001
JP001
JP001
Standard –
R410A
U-60PEY2E5
U-71PEY2E5
Standard –
R32
U-60PZ2E5
U-71PZ2E5
Elite –
R410A
U-36PE2E5A
U-50PE2E5A
U-60PE2E5A
Elite –
R32
U-36PZH2E5
U-50PZH2E5
U-60PZH2E5
Standard –
R410A
U-100PEY1E5
U-125PEY1E5
U-100PEY1E8
U-125PEY1E8
U-140PEY1E8
Elite –
R410A
U-71PE1E5A
U-100PE1E5A
U-125PE1E5A
U-140PE1E5A
U-71PE1E8A
U-100PE1E8A
U-125PE1E8A
U-140PE1E8A
Standard –
R32
U-100PZ2E8
U-125PZ2E8
U-140PZ2E8
Elite –
R410A
U-200PE2E8A
U-250PE2E8A
Elite –
R32
U-200PZH2E8
U-250PZH2E8
JP001
JP001
JP001
Standard –
R32
U-100PZ2E5
U-125PZ2E5
U-140PZ2E5
Elite –
R32
U-71PZH2E5
U-100PZH2E5
U-125PZH2E5
U-140PZH2E5
Elite –
R32
U-71PZH2E8
U-100PZH2E8
U-125PZH2E8
U-140PZH2E8
25.06.2021, JW
This method is not possible for PACi NX OU combi-
nations
03.08.2021, cH: Text adjusted
06.08.2021, JW: OK
01.09.2021, cH
„... to ignore capacity“ added in Method A as per ii_
AHUkit21_EN_v3_2021.08.11pa.pdf.
i
Содержание PAW-280PAH3M-1
Страница 2: ...Notes ...
Страница 113: ...Notes ...