32
AHU Kit – Installation Instructions –
11/2021
Product description
3
System lineup – ECO G systems
Capacity
Outdoor unit
AHU Kit
HP
kW
5
16
all ECO G outdoor units
PAW-160MAH2(L/M)
1
10
28
all ECO G 2-way outdoor units
PAW-280MAH2(L/M)
2
20
56
all ECO G 2-way outdoor units
PAW-560MAH2(L/M)
3
1
PAW-160MAH2(L/M):
● Like any other standard indoor unit, PAW-160MAH2(L/M) can be installed in combination with all ECO G
outdoor units.
● Mixed installation with standard indoor units is possible. However, in this case one additional RAP valve
(CZ-P160RVK2) must be installed in the unit connection pipe, unless the complete system is exclusively
used in cooling only operation or in a 3-way system with heat recovery box.
2
PAW-280MAH2(L/M):
● Like any other indoor unit of similar capacity, PAW-280MAH2(L/M) can be installed in combination with
all ECO G 2-way outdoor units only.
● Mixed installation with standard indoor units is possible. However, in this case two additional RAP
valves (2 x CZ-P160RVK2) must be installed in the unit connection pipe, unless the complete system is
exclusively used in cooling only operation. For further restrictions in mixed installations, please refer to
the system descriptions in the corresponding ECOG technical data books.
● Connection to ECO G 3-way systems is not allowed.
3 PAW-560MAH2(L/M):
● Like any other indoor unit of similar capacity, PAW-560MAH2(L/M) can be installed in combination with
all ECO G 2-way outdoor units only.
● Mixed Installation with standard indoor units is not possible.
● Connection to ECO G 3-way systems is not allowed.
System lineup – PACi systems
Capacity
(kW)
Refrigerant
Outdoor unit
1
AHU Kit
PACi Standard
PACi Elite
Single-phase
units
Three-phase
units
Single-phase
units
Three-phase
units
3.6
R410A
–
–
U-36PE2E5A
–
PAW-280PAH2(L/M)
2
or
PAW-280PAH3M(-1)
2
R32
–
–
U-36PZH2E5
–
5.0
R410A
–
–
U-50PE2E5A
–
R32
–
–
U-50PZH2E5
–
6.0
R410A
U-60PEY2E5
–
U-60PE2E5A
–
R32
U-60PZ2E5
–
U-60PZH2E5
–
7.1
R410A
U-71PEY2E5
–
U-71PE1E5A
U-71PE1E8A
R32
U-71PZ2E5
–
U-71PZH2E5
U-71PZH2E8
10.0
R410A
U-100PEY1E5
U-100PEY1E8
U-100PE1E5A
U-100PE1E8A
R32
U-100PZ2E5
U-100PZ2E8
U-100PZH2E5
U-100PZH2E8
12.5
R410A
U-125PEY1E5
U-125PEY1E8
U-125PE1E5A
U-125PE1E8A
R32
U-125PZ2E5
U-125PZ2E8
U-125PZH2E5
U-125PZH2E8
14.0
R410A
–
U-140PEY1E8
U-140PE1E5A
U-140PE1E8A
R32
U-140PZ2E5
U-140PZ2E8
U-140PZH2E5
U-140PZH2E8
20.0
R410A
–
–
–
U-200PE2E8A
R32
–
–
–
U-200PZH2E8
25.0
R410A
–
–
–
U-250PE2E8A
R32
–
–
–
U-250PZH2E8
1
With PACi systems, only 1-to-1 installations are allowed (e.g. 1 x PACi outdoor unit + 1 x PAW-280PAH2(L/M)). Combi
-
nations with more than 1 outdoor unit or more than 1 AHU Kit are not possible.
2
Mixed installation with standard indoor units is not allowed.
22.07.2021, cH
On page 43 you have confirmed that combinations
of PZ2/PZH2 outdoor units with PAH3M are “offi-
cially compatible and allowed”.
In this case, however, we should also mention
these combinations in this table, correct?
If you confirm, then I have two more questions, just
have to make sure:
- R410A models are NOT compatible with PAH3M,
right?
- All restrictions mentioned in the footnote apply
also to combinations with PAH3M, right?
27.07.2021, JW
It is possible also to combine PAH3M with R32 and
also R410A PACi in this list. Footnotes are then
valid as well
02.08.2021, cH
PAH3M model added in AHU Kit column
06.08.2021, JW: OK