5-17
When Connected to a PLC (FX Series) Made by Mitsubishi Electric Corporation
For GT01, GT11 and GT21
Code No.
Content
Cause and solution
ERFF
Time up error
There is no response
from the PLC.
1) PLC connection cable is disconnected. Check the wiring of
the connection cable and check for disconnection.
2) It is a temporary error caused by noise, etc. Turn on the
power supplies for PLC or GT again.
ER10
Data error
A data error occurred
during communication
Check for errors in the communication conditions settings.
ER12
Overrun error
The GT cannot receive
data.
PLC runaway might be the problem.
ER61
PLC error
A NAK error has been
returned from the PLC.
Verify the PLC settings.
For GT02, GT02L, GT03-E, GT05, GT12, GT32, GT32-R and GT32-E
Code No.
Content
Cause and solution
ERFFFE
NAK error
A NAK error has been
returned from the PLC.
Verify the PLC settings.
When Connected to a PLC Made by Omron Corporation
For GT01, GT11 and GT21
Code No.
Content
Cause and solution
ER00
Time up error
There is no response
from the PLC.
1) PLC connection cable is disconnected. Check the wiring of
the connection cable and check for disconnection.
2) It is a temporary error caused by noise, etc. Turn on the
power supplies for PLC or GT again.
ER01
Cannot be executed
due to operation mode.
(The PLC received the
command that cannot
be executed in the
operation mode.)
Change the mode of the PLC from the operation mode to the
monitor mode.
ER10
Data error
A data error occurred
during communication
Check for errors in the communication conditions settings.
ER12
Overrun error
The GT cannot receive
data.
PLC runaway might be the problem.
ER15
Numerical data error
Designated read/write
area is wrong.
Verify whether or not the reference device used with the basic
communication area and each part is a readable and writable
area.
Error codes other than these are based on Omron PLC error codes.
Be sure to used the PLC in monitor mode. Otherwise, communication will not work properly.
Содержание GT01
Страница 25: ...Chapter 1 Features and Functions ...
Страница 40: ...1 16 ...
Страница 41: ...Chapter 2 Names and Functions of Parts ...
Страница 42: ...2 2 2 1 Part Names 2 1 1 GT01 GT11 GT21 GT01 GT01R GT11 GT21 ...
Страница 44: ...2 4 2 1 2 GT02 GT02L GT02M2 GT02G2 GT02M0 GT02M1 GT02G0 GT02G1 GT02L ...
Страница 48: ...2 8 2 1 4 GT05 GT12 GT32 GT32 R GT32 E GT05 GT12 GT32 Standard High function ...
Страница 49: ...2 9 GT32 R GT32 E ...
Страница 62: ...2 22 ...
Страница 63: ...Chapter 3 Installation and Wiring ...
Страница 86: ...3 24 ...
Страница 87: ...Chapter 4 Connecting with PLC ...
Страница 108: ...4 22 Connecting to the 2 channel type RS485 Note Check the usable GT models for 1 N communication ...
Страница 122: ...4 36 ...
Страница 123: ...Chapter 5 Troubleshooting ...
Страница 141: ...Chapter 6 Specifications ...
Страница 187: ...Chapter 7 Dimensions and Other Documentation ...
Страница 188: ...7 2 7 1 Dimensions 7 1 1 GT01 GT01R Installation dimensions Panel cutout dimensions ...
Страница 189: ...7 3 7 1 2 GT02 Installation dimensions Panel cutout dimensions ...
Страница 190: ...7 4 7 1 3 GT02L Installation dimensions Panel cutout dimensions ...
Страница 191: ...7 5 7 1 4 GT03M E Installation dimensions Panel cutout dimensions ...
Страница 193: ...7 7 7 1 6 GT05 Installation dimensions Panel cutout dimensions ...
Страница 194: ...7 8 7 1 7 GT11 Installation dimensions Panel cutout dimensions ...
Страница 195: ...7 9 7 1 8 GT12 Installation dimensions Panel cutout dimensions ...
Страница 196: ...7 10 7 1 9 GT21 Installation dimensions Panel cutout dimensions ...
Страница 197: ...7 11 7 1 10 GT32 GT32M Back view GT32T0 GT32T1 Installation dimensions Panel cutout dimensions ...
Страница 198: ...7 12 7 1 11 GT32 R GT32 E Installation dimensions Panel cutout dimensions ...
Страница 199: ...7 13 7 2 Cable Specifications 7 2 1 AIGT8142 7 2 2 AIGT8152 7 2 3 AIGT8160 AIGT8162 AIGT8165 AIGT8192 ...
Страница 200: ...7 14 7 2 4 AIGT8175 7 2 5 AIP81842 ...
Страница 202: ...7 16 7 4 ASCII Code Table ...
Страница 205: ......