5-16
For GT02, GT02L, GT03-E, GT05, GT12, GT32, GT32-R and GT32-E
Code No.
Content
Cause and solution
ER0021
Data error
A data error
occurred during
communication.
1) There is an error in the communication condition settings. Check
the PLC and GT baud rate and transfer format.
2) There is a temporary error due to noise, etc. Re-supply power to
the PLC and GT.
ER0022
Overrun error
The PLC isn
’t
receiving data.
The CPU unit
’s reception buffer is overflowing.
There could be an error in the PLC.
Re-supply power to the PLC and GT.
ER0040
BCC error
A data error
occurred during
communication.
1) There is a temporary error due to noise, etc.
Re-supply power to the PLC and GT.
2) There is an error in the CPU unit. Re-supply power to the PLC
and GT.
ER0041
Format error
The PLC has been
sent a command
that doesn
’t match
the protocol.
1) There is a temporary error due to noise, etc.
Re-supply power to the PLC and GT.
2) There is an error in the CPU unit. Re-supply power to the PLC
and GT.
ER0042
NOT support error
The GT has sent a
non-supported
command to the
PLC.
1) There is a temporary error due to noise, etc.
Re-supply power to the PLC and GT.
2) There is an error in the CPU unit. Re-supply power to the PLC
and GT.
ER0053
BUSY error
The PLC is
currently
processing another
command.
A large amount of data is being communicated with another
RS232C port on the PLC.
Wait until the error is gone.
ER0060
Parameter error
The specified parameter does not exist, or it cannot be used.
ER0061
Data run error
There is an error in
the register or
relay number.
A register or relay number which doesn
’t exist in the PLC was
specified during screen creation using GTWIN.
Correct the output device being used with the part, or the transfer
of clock data to an external device.
Содержание GT01
Страница 25: ...Chapter 1 Features and Functions ...
Страница 40: ...1 16 ...
Страница 41: ...Chapter 2 Names and Functions of Parts ...
Страница 42: ...2 2 2 1 Part Names 2 1 1 GT01 GT11 GT21 GT01 GT01R GT11 GT21 ...
Страница 44: ...2 4 2 1 2 GT02 GT02L GT02M2 GT02G2 GT02M0 GT02M1 GT02G0 GT02G1 GT02L ...
Страница 48: ...2 8 2 1 4 GT05 GT12 GT32 GT32 R GT32 E GT05 GT12 GT32 Standard High function ...
Страница 49: ...2 9 GT32 R GT32 E ...
Страница 62: ...2 22 ...
Страница 63: ...Chapter 3 Installation and Wiring ...
Страница 86: ...3 24 ...
Страница 87: ...Chapter 4 Connecting with PLC ...
Страница 108: ...4 22 Connecting to the 2 channel type RS485 Note Check the usable GT models for 1 N communication ...
Страница 122: ...4 36 ...
Страница 123: ...Chapter 5 Troubleshooting ...
Страница 141: ...Chapter 6 Specifications ...
Страница 187: ...Chapter 7 Dimensions and Other Documentation ...
Страница 188: ...7 2 7 1 Dimensions 7 1 1 GT01 GT01R Installation dimensions Panel cutout dimensions ...
Страница 189: ...7 3 7 1 2 GT02 Installation dimensions Panel cutout dimensions ...
Страница 190: ...7 4 7 1 3 GT02L Installation dimensions Panel cutout dimensions ...
Страница 191: ...7 5 7 1 4 GT03M E Installation dimensions Panel cutout dimensions ...
Страница 193: ...7 7 7 1 6 GT05 Installation dimensions Panel cutout dimensions ...
Страница 194: ...7 8 7 1 7 GT11 Installation dimensions Panel cutout dimensions ...
Страница 195: ...7 9 7 1 8 GT12 Installation dimensions Panel cutout dimensions ...
Страница 196: ...7 10 7 1 9 GT21 Installation dimensions Panel cutout dimensions ...
Страница 197: ...7 11 7 1 10 GT32 GT32M Back view GT32T0 GT32T1 Installation dimensions Panel cutout dimensions ...
Страница 198: ...7 12 7 1 11 GT32 R GT32 E Installation dimensions Panel cutout dimensions ...
Страница 199: ...7 13 7 2 Cable Specifications 7 2 1 AIGT8142 7 2 2 AIGT8152 7 2 3 AIGT8160 AIGT8162 AIGT8165 AIGT8192 ...
Страница 200: ...7 14 7 2 4 AIGT8175 7 2 5 AIP81842 ...
Страница 202: ...7 16 7 4 ASCII Code Table ...
Страница 205: ......