Programming Example, FP-FNS Block BACnetIP
75
Input
Data Type
Function
iWatchdogTime_ms
INT
Watchdog timeout value for the unit in ms.
Valid values from 1 to 32767. 0: default of
700ms.
ModuleConfig
DUT BACnetIP_DeviceInit
Data unit type to configure the module.
Outputs
Output
Data Type
Function
sName
STRING[16]
Name of installed FP-FNS block
sBusType
STRING[20]
Network type of installed FP-FNS block
bOnline
BOOL
Flag for online status
bError
BOOL
Error flag
wErrorCode
WORD
Error code if error flag is set
List of error codes for FP-FNS block BACnet
Error code
Indication
16#0000
No error
16#0005
FP-FNS block is not installed correctly
16#0007
FP-FNS block has incorrect provider ID
16#0008
Wrong FP-FNS block installed
16#000A
Exception state entered; application watchdog timeout; unit needs resetting
16#0056
Process data area is too large (max. 256 bytes)
16#0057
pMultistateValues and pMultistateValuesVarName variable: different number of elements
16#0058
pBinarValues and pBinaryValuesVarName variable: different number of elements
16#0059
pAnalogrValues and pAnalogValuesVarName variable: different number of elements
16#005A
pAnalogrValuesConfig and pAnalogrValuesIDNumber: different number of elements
16#005B
pBinarValues and pBinaryValuesIDNumber variable: different number of elements
16#005C
pMultistateValues and pMultistateValuesIDNumber: different number of elements
16#0060
Stringsize pMultistateValuesStateText > 32
16#0061
Stringsize pMultistateValuesVarName > 32
16#0062
Stringsize pBinaryValuesVarName > 32
16#0063
Stringsize pAnalogValuesVarName > 32
16#0064
AnalogValuesIDNumber > 2039
16#0065
AnalogValuesIDNumber < 0
16#0066
BinaryValuesIDNumber > 2039
16#0067
BinaryValuesIDNumber < 0
16#0068
MultiStateValueValuesIDNumber > 2039
16#0069
MultiStateValueValuesIDNumber < 0
16#0070
AnalogValueConfig: array not allowed
16#0071
AnalogValueConfig: not a valid datatype
Содержание FPSIGMA
Страница 1: ...programmable controller FPS FP2 Fieldbus Slave Units Technical Manual ...
Страница 7: ......
Страница 8: ...Chapter 1 Features and Restrictions ...
Страница 11: ......
Страница 12: ...Chapter 2 Parts and Functions ...
Страница 14: ...FP2 FNS Unit 13 2 2 FP2 FNS Unit ...
Страница 25: ......
Страница 26: ...Chapter 3 Specifications ...
Страница 32: ...Chapter 4 Installation and Wiring ...
Страница 48: ...Chapter 5 Programming Examples for FPWIN Pro ...
Страница 84: ...Chapter 6 Outline Dimensions ...
Страница 85: ...Outline Dimensions 84 6 1 Outline Dimensions of FP2 FNS Unit ...
Страница 86: ...Outline Dimensions of FPΣ FNS Unit 85 6 2 Outline Dimensions of FPΣ FNS Unit ...
Страница 87: ...Outline Dimensions 86 6 3 Dimensions of the FP FNS Blocks ...