Specifications
30
3.3 FP-FNS Block Communication Specifications
PROFIBUS, DeviceNet, CANopen
Item
PROFIBUS
DeviceNet
CANopen
Baud rate
Automatic baud rate
detection
9.6kbaud to 12Mbaud
Automatic baud rate
detection
125kbps to 500kbps
Automatic baud rate
detection
10kbps to 1Mbps
Isolation
Galvanically isolated bus
electronics
Galvanically isolated bus
electronics
Galvanically isolated bus
electronics
Connection types
DP-V0: process data is
accessed from the
PROFIBUS network as
cyclical I/O data
Cyclic connections
COS (Change of State)
Bit strobe connections
Polled connections
Explicit connections
PDO (Process Data Object)
Exchange via:
Cyclic Synchronous
Acyclic Synchronous
COS
Timer-driven
connections
Maximum inputs/outputs
76 words altogether for
inputs and outputs (in units
of 1, 2 or 4 words)
E.g. for cyclic connections:
128 words in each direction
128 words (for TPDOs and
RPDOs)
Additional features
Diagnostic support
UCMM capable
CIP Parameter Object
Diagnostic support
Diagnostic support
Interface
DB9F (9-pin Sub-D female) 5-pin terminal block
9-pin Sub-D male
(AFPN-AB6218)
PROFINET IO, BACnet/IP, BACnet MS/TP
Item
PROFINET IO
BACnet/IP
BACnet MS/TP
Baud rate
100Mbit/s
Full duplex
100Mbit/s
10Mbit/s
Full duplex
Half duplex
9600kbits/s
19200kbits/s
38400kbits/s
76800kbits/s
Isolation
Galvanically isolated bus
electronics
Galvanically isolated bus
electronics
Galvanically isolated bus
electronics
Connection types
PROFINET IO
conformance class B
Cyclic data exchange
via PROFINET IO
Real Time (RT)
communication, 2ms
cycle time
Change Of Value (COV)
notification
Alarm/ Event
functionality
Change Of Value (COV)
notification
Alarm/ Event
functionality
Maximum inputs/
outputs
128 words of Real Time I/O
data in each direction
256-byte write process data 256-byte write process data
Additional features
Diagnostic support
Diagnostic support
Diagnostic support
Interface
Integrated 2-port switch: 2 x
RJ45 socket
Integrated 2-port switch: 2 x
RJ45 socket
5-pin terminal block
Содержание FPSIGMA
Страница 1: ...programmable controller FPS FP2 Fieldbus Slave Units Technical Manual ...
Страница 7: ......
Страница 8: ...Chapter 1 Features and Restrictions ...
Страница 11: ......
Страница 12: ...Chapter 2 Parts and Functions ...
Страница 14: ...FP2 FNS Unit 13 2 2 FP2 FNS Unit ...
Страница 25: ......
Страница 26: ...Chapter 3 Specifications ...
Страница 32: ...Chapter 4 Installation and Wiring ...
Страница 48: ...Chapter 5 Programming Examples for FPWIN Pro ...
Страница 84: ...Chapter 6 Outline Dimensions ...
Страница 85: ...Outline Dimensions 84 6 1 Outline Dimensions of FP2 FNS Unit ...
Страница 86: ...Outline Dimensions of FPΣ FNS Unit 85 6 2 Outline Dimensions of FPΣ FNS Unit ...
Страница 87: ...Outline Dimensions 86 6 3 Dimensions of the FP FNS Blocks ...