20

General Installation Manual

WIRING GENERAL

•  All wiring should be done in 

accordance with applicable 

electrical codes.

•  Wiring methods should be in 

accordance with the NEC in USA or 

CEC in Canada.

•  All wiring should be done by a 

qualified, licensed professional.

•  Wiring should be protected to help 

ensure personal safety and to 

prevent its damage.

•  Please connect each cable after 

confirming the polarity of it is 

correct.

•  Connectors between modules must 

be inserted until they click.

•  When connecting the connectors, 

please make sure that foreign 

matter such as water, sand and so 

on do not get inside the connector. 

Also, please keep in mind that 

if you leave the connector in a 

nonconnected state for a long 

period of time, contamination of 

foreign matter is likely to occur.

•  If an extreme load is applied to 

the cable, the cables may come 

off the junction box body or the 

connectors.

•  Please connect so that a strong 

load is not applied to the cable.

•  Do not disconnect terminals while 

modules generate electricity and 

connect electrical load to avoid the 

hazard of electrical shock.

•  Cable conduits should be used 

in locations where the wiring is 

inaccessible to children or small 

animals.

•  Please contact your Panasonic 

Authorized Representative 

with questions regarding other 

electrical connections if needed. 

 

 

 

 

 

 

MODULE WIRING

•  All modules connected in series 

should be of the same model 

number and/or type.

•  The maximum number of modules 

in a string can be calculated by 

dividing the maximum system 

voltage of the module by its 

VOC accounting for the lowest 

ambient temperature at site, e.g.: 

for a 1000V system, if the lowest 

ambient temperature is 15°C, the 

module has a VOC of 44.3 V and a 

temperature coefficient of VOC of 

-0.24%/°C, the maximum modules 

per string is 22 (ΔT°C = 25° - 15° = 

10°; 10° x 0.24 = 2.4%; 44.3 + 2.4% 

= 45.4; 1000 V / 45.4 = 22.0, so a 

total of 22 modules or 976 V).

•  Qualified system designers can 

make exact calculations that 

account for specific project 

requirements and site conditions.

•  If modules will be used in an 

“offgrid” system, a compatible 

MPPT (Maximum Power Point 

Tracking) charge controller is 

required. Especially charge battery 

can not be used without MPPT.

•  These modules contain factory 

installed bypass diodes. If these 

modules are incorrectly connected 

to each other, the bypass diodes, 

cable, or junction box may be 

damaged.

•  Do not connect modules in parallel 

without using connection devices 

that connect to appropriate FUSE 

for each series string or each 

module. 

 

 

 

 

 

 

 

 

 

 

 

ARRAY WIRING

•  The term “array” is used to 

describe the assembly of several 

modules on a support structure 

with associated wiring.

•  When installing a PV array, the 

system design must be completed 

with reference to the module 

electrical specifications for proper 

selection of inverters, fuses, 

breakers, charging controllers, 

batteries and other storage 

devices. In particular, as the 

temperature characteristic of 

the PV module, the voltage value 

rises on the low temperature side. 

Consider the lowest temperature 

in the area where the system is 

installed and select the equipment 

so that it does not exceed the rated 

voltage of the equipment.

•  Use copper wire which is insulated 

to withstand the maximum possible 

system open circuit voltage. For 

applications where wire conduits 

are used, follow the applicable 

codes for outdoor installation 

of wires in conduits. Minimum 

diameter of wire conduit is 4 

mm2. The temperature rating 

of conductor is -40ºF(-40ºC) to 

194ºF(90ºC).

•  In order to avoid submerging 

cables and connectors in the water, 

cables must be fixed either to the 

module frame using cable fixing 

holes or to the mounting structure. 

Also, if the cable is not secured, a 

force may be applied to the cable 

from the outside, and the module 

may be damaged.

•  Do not insert PV cable between 

back side and mounting structure 

rail. When snow weight is applied 

to the module, load may be applied 

to the cable.

•  Verify that all fittings are properly 

installed to protect cables against 

damage and prevent moisture 

intrusion.

•  Check your local codes for 

requirements

Содержание EverVolt EVPV HK Series

Страница 1: ...General Installation Manual EVPVXXX SERIES WHITE BACKSHEET EVPVXXXK SERIES BLACK BACKSHEET EVPVXXXH SERIES WHITE BACKSHEET EVPVXXXPK SERIES BLACK BACKSHEET EVPVXXXHK SERIES BLACK BACKSHEET ...

Страница 2: ... Specifications 3 Standards Fire Class of Product Junction Box Terminals and Connectors Bypass Diode Installation 8 General Operating Conditions Unpacking and Handling Cable Management Module Installation Use of Rails and Clamps Mounting with Continous Rails Parallel to Long Side of the Module Mounting with Short Rails Mounting Methods Mounting Holes Wiring 20 General Module Wiring Array Wiring Dr...

Страница 3: ... in parallel producing higher current and as modules are connected in series producing higher voltages The shock hazard increases as modules rated for maximum system voltage in excess of 50 V Wear suitable clothing gloves and guards to prevent from direct contact with 30 VDC or greater Work only in dry conditions with dry modules and dry tools Children and unauthorized persons should not be allowe...

Страница 4: ... of modules should be multiplied by a factor of 1 25 to determine ampacity An additional factor of 1 25 may be required for sizing conductors fuses disconnects etc Please refer to section 690 8 of the National Electric Code NEC for guidelines The Voc must be factored according to the lowest recorded ambient temperature recorded for the location where the modules will be installed Please refer to s...

Страница 5: ... 24 0 01 47 2 1200 0 81 0 02 20 5 0 5 0 43 0 008 11 0 2 0 26 0 008 6 6 0 2 35 5 901 71 7 0 1 1821 2 5 18 1 460 43 3 1100 38 4 0 1 975 2 5 26 4 0 12 671 3 Figure 3 Module Dimension for EVPVxxxPK Series GR GR GR GR 0 43 0 1 11 0 2 0 26 0 1 6 6 0 2 0 8 0 02 20 5 0 5 GR 25 1 638 1 2 30 0 9 22 5 1 1 28 69 10 0 1 1755 2 5 33 27 845 17 91 455 39 33 999 43 3 1100 0 22 0 01 5 5 0 2 47 1200 40 94 0 1 1040 2...

Страница 6: ...48 6V 44 3V 44 1V 43 9V 44 1V 43 9V Short Circuit Current Isc 10 35A 10 25A 10 19A 10 61A 10 55A 10 49A 10 55A 10 49A Cell Type Silicon hetero junction Maximum System Voltage 1000V 1000V 1000V 1000V 1000V 1000V 1000V 1000V Factory Installed Bypass Diodes 3 3 3 3 3 3 3 3 Maximum series fuse A 25 25 25 25 25 25 25 25 Length inches mm 71 7 1821 67 75 1721 Width inches mm 40 0 1016 Frame Depth Inches ...

Страница 7: ... 40 6V 40 3V 49 0V 48 8V 48 6V Short Circuit Current Isc 11 38A 11 26A 11 13A 10 35A 10 28A 10 22A Cell Type PERC Silicon hetero junction Maximum System Voltage 1000V 1000V 1000V 1000V 1000V 1000V Factory Installed Bypass Diodes 3 3 3 3 3 3 Maximum series fuse A 25 25 25 25 25 25 Length inches mm 69 1 1755 71 7 1821 Width inches mm 40 94 1040 40 0 1016 Frame Depth Inches mm 1 2 30 1 2 30 Weight po...

Страница 8: ...s dedicated to one polarity with the polarity symbols engraved onto the body of the junction box see Figure 1 Each terminal is provided with factory installed lead cables and a latching connector for series and string connections Always use these connectors and do not detach them from cables The PV module comes pre wired Each module has two 12 AWG type PV wire stranded sunlight resistant output ca...

Страница 9: ...he cables follow the instructions below To prevent stress on the junction box casing ensure the cable exits the junction box in a straight line before any bend in the cable The cables must have a minimum bending radius of 1 2 in 30 mm to avoid damage to the insulation refer Figure 6 Ensure cables do not hang loose where they may be damaged through friction or stress e g caused by mechanical abrasi...

Страница 10: ...sture shall not be employed alone or in combinations that could result in deterioration or corrosion USE OF RAILS AND CLAMPS Installing the EverVolt modules with clamps and rails has been found to comply with UL 61730 requirements for downward pressure e g snow of up to 7000 Pa 4666 Pa design load and upward pressure e g wind of up to 4000 Pa 2666 Pa design load according to the following instruct...

Страница 11: ...800 Pa 1200 Pa 1200 Pa 6200 Pa 4000 Pa 4133 Pa 2666 Pa 7000 Pa 4000 Pa 4666 Pa 2666 Pa X 22 2 23 8 in 565 605 mm 1200 Pa 1200 Pa 800 Pa 800 Pa 3000 Pa 2400 Pa 2400 Pa 1600 Pa 5400 Pa 2400 Pa 3600 Pa 1600 Pa X 23 8 27 4 in 605 695 mm 2400 Pa 2400 Pa 1600 Pa 1600 Pa 2400 Pa 2400 Pa 1600 Pa 1600 Pa 2400 Pa 2400 Pa 1600 Pa 1600 Pa X 0 4 in 0 100 mm X 1200 Pa 1200 Pa 800 Pa 800 Pa 1600 Pa 1600 Pa 1066 ...

Страница 12: ...Pa 2400 Pa 3600 Pa 1600 Pa X 0 4 in 0 100 mm X 1200 Pa 1200 Pa 800 Pa 800 Pa 1600 Pa 1600 Pa 1066 Pa 1066 Pa X 4 9 8 in 100 250 mm X 800 Pa 800 Pa 533 Pa 533 Pa 2400 Pa 2400 Pa 1600 Pa 1600 Pa X Once a module is secured in each of the 4 zones Figure 8 additional clamps i e 5 may be freely located on panel frame without affecting the warranty Loads marked with a were not certified as part of UL 617...

Страница 13: ... Pa 1600 Pa 1600 Pa 2400 Pa 2400 Pa 1600 Pa 1600 Pa X 0 4 in 0 100 mm X 1200 Pa 1200 Pa 800 Pa 800 Pa 1600 Pa 1600 Pa 1066 Pa 1066 Pa X 4 9 8 in 100 250 mm X 800 Pa 800 Pa 533 Pa 533 Pa 2400 Pa 2400 Pa 1600 Pa 1600 Pa X Rail length under module 4 7 9 in Min 1 in 4 7 9 in 0 8 2 in 0 208 mm X 1200 Pa 1200 Pa 800 Pa 800 Pa 1600 Pa 1600 Pa 1066 Pa 1066 Pa X 8 2 13 4 in 208 340 mm 1200 Pa 1200 Pa 800 P...

Страница 14: ... 40 60 mm 2 4 in 60 mm 0 8 in 20 mm Test Load Design Load Test Load Design Load Test Load Design Load Test Load Design Load Rail position 0 10 0 in 0 255 mm X 1200 Pa 1200 Pa 800 Pa 800 Pa 2400 Pa 2400 Pa 1600 Pa 1600 Pa X 10 0 14 8 in 255 375 mm 1800 Pa 1800 Pa 1200 Pa 1200 Pa 4200 Pa 2400 Pa 2800 Pa 1600 Pa 5400 Pa 2400 Pa 3600 Pa 1600 Pa X 14 8 19 9 in 375 505 mm 1800 Pa 1800 Pa 1200 Pa 1200 Pa...

Страница 15: ...600 Pa 5400 Pa 2400 Pa 3600 Pa 1600 Pa X 0 7 9 in 0 200 mm X 1200 Pa 1200 Pa 800 Pa 800 Pa 1600 Pa 1600 Pa 1066 Pa 1066 Pa X 7 9 11 8 in 200 300 mm X 800 Pa 800 Pa 533 Pa 533 Pa 2400 Pa 2400 Pa 1600 Pa 1600 Pa X Once a module is secured in each of the 4 zones Figure 8 additional clamps i e 5 may be freely located on panel frame without affecting the warranty Loads marked with a were not certified ...

Страница 16: ...a 1200 Pa 800 Pa 800 Pa 3000 Pa 3000 Pa 2000 Pa 2000 Pa 4200 Pa 4000 Pa 2800 Pa 2666 Pa X 15 9 24 0 in 505 610 mm 1200 Pa 1200 Pa 800 Pa 800 Pa 2400 Pa 2400 Pa 1600 Pa 1600 Pa 3600 Pa 2400 Pa 2400 Pa 1600 Pa X 24 0 27 5 in 610 700 mm 1800 Pa 1800 Pa 1200 Pa 1200 Pa 2400 Pa 2400 Pa 1600 Pa 1600 Pa 2400 Pa 2400 Pa 1600 Pa 1600 Pa X 0 7 9 in 0 200 mm X 1200 Pa 1200 Pa 800 Pa 800 Pa 1600 Pa 1600 Pa 10...

Страница 17: ...0 60 mm 2 4 in 60 mm 0 8 in 20 mm Test Load Design Load Test Load Design Load Test Load Design Load Test Load Design Load Rail position 0 8 9 in 0 225 mm X 1200 Pa 1200 Pa 800 Pa 800 Pa 2400 Pa 2400 Pa 1600 Pa 1600 Pa X 8 9 14 1 225 357 mm 1800 Pa 1800 Pa 1200 Pa 1200 Pa 4200 Pa 2400 Pa 2800 Pa 1600 Pa 5400 Pa 2400 Pa 3600 Pa 1600 Pa X 14 1 22 9 in 357 582 mm 1800 Pa 1800 Pa 1200 Pa 1200 Pa 6200 P...

Страница 18: ... 1600 Pa 5400 Pa 2400 Pa 3600 Pa 1600 Pa X 0 4 in 0 100 mm X 1200 Pa 1200 Pa 800 Pa 800 Pa 1600 Pa 1600 Pa 1066 Pa 1066 Pa X 4 9 8 in 100 250 mm X 800 Pa 800 Pa 533 Pa 533 Pa 2400 Pa 2400 Pa 1600 Pa 1600 Pa X Once a module is secured in each of the 4 zones Figure 8 additional clamps i e 5 may be freely located on panel frame without affecting the warranty Loads marked with a were not certified as ...

Страница 19: ...00 Pa 800 Pa 3000 Pa 3000 Pa 2000 Pa 2000 Pa 4200 Pa 4000 Pa 2800 Pa 2666 Pa X 22 9 24 5 in 582 622 mm 1200 Pa 1200 Pa 800 Pa 800 Pa 2400 Pa 2400 Pa 1600 Pa 1600 Pa 3600 Pa 2400 Pa 2400 Pa 1600 Pa X 24 5 28 0 in 622 712 mm 1800 Pa 1800 Pa 1200 Pa 1200 Pa 2400 Pa 2400 Pa 1600 Pa 1600 Pa 2400 Pa 2400 Pa 1600 Pa 1600 Pa X 0 4 in 0 100 mm X 1200 Pa 1200 Pa 800 Pa 800 Pa 1600 Pa 1600 Pa 1066 Pa 1066 Pa...

Страница 20: ...s in the frame must be used Figure 21 Additional electrical bonding to Ground is required for the support structure Refer to the fixing device manufacturer s installation instructions for preload or torque values Do not contact a tip of a mounting bolt to back sheet of the module when fixing the module to the mounting structure rail EverVolt modules must be secured with a torque between 8 8 18 4 f...

Страница 21: ...lations that account for specific project requirements and site conditions If modules will be used in an offgrid system a compatible MPPT Maximum Power Point Tracking charge controller is required Especially charge battery can not be used without MPPT These modules contain factory installed bypass diodes If these modules are incorrectly connected to each other the bypass diodes cable or junction b...

Страница 22: ...lated E34440 Grounding cable size should be between 4 14 AWG 2 1 mm 21 2 mm Attach grounds to the grounding holes in the module frames Fix lug to the frame using a star washer and lock nut ensuring a conductive connection Follow the grounding device manufacturer s installation instructions to ensure a safe and conductive connection including any supplementary hardware e g star washer and tighten a...

Страница 23: ...ector may be deteriorated or damaged SYSTEM INSPECTION The system should be inspected regularly to ensure that Fasteners are secure tight and free from corrosion Electrical connections are secure tight clean and free of corrosion The mechanical integrity of the cables is intact Bonding points to ground are tight secure and free from corrosion which could break the continuity between the modules an...

Страница 24: ...neral Installation Manual REVISION HISTORY Edition Revision Date Revised Item Revised Content A 10 13 2020 NEW B 12 1 2021 Addition of EVPVxxxH and EVPVxxxPK Series C 11 15 2022 Addition of EVPVxxxHK Series ...

Страница 25: ...ing an MLPE device to a solar module it must be secured to the module frame Follow MLPE manufacturer instructions to ensure optimum mounting of MLPE device and prevent any slippage during operation MLPE devices may also be attached to the mounting construction In such cases refer to the instructions provided by the manufacturer Wherever possible the installation of the MLPE device should not cover...

Страница 26: ...ny of America Two Riverfront Plaza Newark NJ 07102 panasonicsolar us panasonic com na panasonic com us solar All Rights Reserved 2022 COPYRIGHT Panasonic Corporation Specifications are subject to change without notice RS22026BRO R5 ...

Отзывы: