75
Table 11 R410A flaring dimensions
Table 12 R22 flaring dimensions
Table 13 R410A flare and flare nut dimensions Unit: mm
Table 14 R22 flare and flare nut dimensions Unit: mm
2. Procedure and precautions for flare connection
a. Check to make sure there is no scratches, dust, etc., on the flare and union.
b. Align the flared surface with the axial center of the union.
c. Use a torque wrench, and tighten to the specified torque. The tightening torque for R410A is the same as the conventional
torque value for R22. Be careful, because if the torque is too weak, it may lead to a gas leak. If it is too strong, it may split
the flare nut or make it impossible to remove the flare nut.
Table 15 R410A tightening torque
11.3.3.
Storing and managing piping materials
1. Types of piping and their storage
The following is a general classification of the refrigerant pipe materials used for ACs.
Because the gas pressure of R410A is approximately 1.6 times as high as that of R22, copper pipes with the thickness shown
in Table 10, and with minimal impurities must be used. Care must also be taken during storage to ensure that pipes are not
crushed, deformed, or scratched, and that no dust, moisture or other substance enters the pipe interior. When storing
sheathed copper pipes or plain copper pipes, seal the openings by pinching or taping them securely.
2. Makings and management
a. Sheathed copper pipes and copper-element pipes
Nominal
diameter
Outside
diameter
(mm)
Wall thickness
(mm)
A (mm)
R410A flaring
tool, clutch type
Conventional flaring tool
Clutch type
Wing-nut type
1/4
6.35
0.8
0 - 0.5
1.0 - 1.5
1.5 - 2.0
3/8
9.52
0.8
0 - 0.5
1.0 - 1.5
1.5 - 2.0
1/2
12.70
0.8
0 - 0.5
1.0 - 1.5
2.0 - 2.5
5/8
15.88
1.0
0 - 0.5
1.0 - 1.5
2.0 - 2.5
Nominal
diameter
Outside
diameter
(mm)
Wall thickness
(mm)
A (mm)
R22 flaring
tool, clutch type
Conventional flaring tool
Clutch type
Wing-nut type
1/4
6.35
0.8
0 - 0.5
0.5 - 1.0
1.0 - 1.5
3/8
9.52
0.8
0 - 0.5
0.5 - 1.0
1.0 - 1.5
1/2
12.70
0.8
0 - 0.5
0.5 - 1.0
1.5 - 2.0
Nominal
diameter
Outside
diameter (mm)
Wall thickness
(mm)
A +0, -0.4
B
dimension
C
dimension
D
dimension
Flare nut
width
1/4
6.35
0.8
9.1
9.2
6.5
13
17
3/8
9.52
0.8
13.2
13.5
9.7
20
22
1/2
12.70
0.8
16.6
16.0
12.9
23
26
5/8
15.88
1.0
19.7
19.0
16.0
25
29
Nominal
diameter
Outside
diameter (mm)
Wall thickness
(mm)
A +0, -0.4
B
dimension
C
dimension
D
dimension
Flare nut
width
1/4
6.35
0.8
9.0
9.2
6.5
13
17
3/8
9.52
0.8
13.0
13.5
9.7
20
22
1/2
12.70
0.8
16.2
16.0
12.9
20
24
Nominal
diameter
Outside
diameter (mm)
Tightening torque
N.m (kgf.cm)
Torque wrench tightening torque
N.m (kgf.cm)
1/4
6.35
14 - 18 (140 - 180)
18 (180)
3/8
9.52
33 - 42 (330 -420)
42 (420)
1/2
12.70
55 (550)
55 (550)
5/8
15.88
65 (650)
65 (650)
Содержание CU-B14DBE5
Страница 11: ...11 4 Dimensions 4 1 CS F18DTE5 ...
Страница 12: ...12 4 2 CU J18DBE5 ...
Страница 13: ...13 5 Refrigeration Cycle 5 1 CS F18DTE5 CU J18DBE5 ...
Страница 14: ...14 6 Block Diagram 6 1 CS F18DTE5 6 2 CU J18DBE5 ...
Страница 15: ...15 7 Wiring Diagram 7 1 CS F18DTE5 ...
Страница 16: ...16 7 2 CU J18DBE5 ...
Страница 18: ...18 8 2 Remote Control Display ...
Страница 19: ...19 8 3 Remote Control Panel ...
Страница 95: ...95 13 3 Reaching distance CS F18DTE5 Cooling ...
Страница 96: ...96 13 4 Sound data ...
Страница 97: ...97 13 5 Sound measuring point 13 5 1 Indoor Unit 13 5 2 Outdoor Unit ...
Страница 100: ...100 14 Exploded View Indoor Unit 14 1 CS F18DTE5 ...
Страница 101: ...101 14 2 CS F18DTE5 ...
Страница 102: ...102 14 3 CS F18DTE5 ...
Страница 105: ...105 16 Exploded View Outdoor Unit 16 1 CU J18DBE5 ...
Страница 106: ...106 16 2 CU J18DBE5 ...
Страница 108: ...108 18 Print Pattern 18 1 Indoor Unit Printed Main ...
Страница 109: ...109 18 2 Indoor Unit Printed Indicator 18 2 1 Outdoor Unit Main PHAAM Printed in Malaysia SSBZ0603 00 ...