13.5 Cooling overload control (Cool)
This control detect outdoor pipe temperature and perform the compressor frequency restriction during cooling
operation.
13.6 Heating overload control (Heat)
This control detect indoor pipe temperature and perform the compressor frequency restriction during heating
operation.
This control detect outdoor ambient temperature and perform the fan speed adjustment during heating operation.
13.7 Extreme Low Temperature Compressor low pressure protection control
(Heat)
This control is to prevent low pressure drops too low during extremely low outdoor ambient temperature to
improve the compressor reliability.
During heating operation, when outdoor ambient temperature is in Zone 1, this control will be activated.
Compressor frequency restriction will be based on outdoor piping temperature.
Comp stop
Comp freq
restricted
60°C
57°C
Comp freq
free
64°C
OD Pipe
temp
Comp stop
Comp freq
restricted
53°C
Comp freq
free
60°C
ID Pipe
temp
48°C
Comp freq
maintain
RPM controlled
12°C
10°C
RPM free
OD temp
Zone 0
-5°C
-3°C
Zone 1
OD temp
Comp freq
free
Comp freq
restricted
Comp freq
stop
-25°C
-23°C
-28°C
-26°C
OD pipe