49
12.12.2.1 Demo Mode
The air conditioner starts the operation in the Demo mode as described below when 2 minutes have elapsed after the
protection control was started subsequent to the confirmation of communication error.
(At this time, a strong warning sound is emitted for 3 minutes if the test run memory is “incomplete”.)
Condition to stop the mode
The operation is stopped by turning off the air conditioner on the remote control or pressing the EMERGENCY
OPERATON switch during the Demo mode.
(“TIMER” LED flashes.)
Zone B
Airflow Unit Operation Mode (Normal Operation)
Transition time to Demo
Mode
180sec from
the demo starts
360 sec from
the demo starts
540 sec from
the demo starts
640 sec from
the demo starts
[POWER] LED
ON
OFF
[NANOE-G] LED
Follow the remote control settings
OFF
[+8/10°C HEAT] LED
Follow the remote control settings
OFF
[ECONAVI] LED
Follow the remote control settings
OFF
[TIMER] LED
Auto Demo mode is set during the model selection: Follow the remote control settings.
When in Product Demo mode: Always OFF (Timer is cancelled due to H11)
Front panel STM
Open
Stop position
Vertical louver STM
Ceiling airflow
Heating 5
Swing
Stop position
Horizontal louver STM
Area OFF or Auto Demo is set: Swing from the front side
Others: Area control under Heating, Range B, Airflow stable
Reset
Fan motor
Fan speed is set to Auto on the remote control: OFF
Fan speed is set to Manual on the remote control: Remote controller
setting tap
Stop position
Human activity sensor
Area ON: Repeat the scan detection and fixed detection.
Area OFF: Standby position (Default position)
Standby position
(Default position)
Sunlight sensor
LED brightness changes (Bright-Dim) when ECONAVI is ON. Confirmed time is for Demo only.
NANOE output
OFF
12.12.2.2 Infrared Sensor Abnormality
Abnormality detection:
Connector disconnection / Wire cut abnormality
o
Sensor judge Hi level continuously for 25 seconds
Circuit
abnormality
o
65 seconds after power ON, if infrared sensor judge Lo level continuously for 25 seconds
Error Code judgment
When abnormality happened, internal counter increase by 1 time.
Infrared sensor power OFF, retry after 5 seconds.
When the infrared sensor maintains normal condition for 120 seconds, the counter reset or AC reset.
When abnormality counter reached 4 times, H59 occurred – No TIMER indicator blinking.
When error code happened, the unit is able to operate without ECONAVI / AUTO COMFORT.
12.12.2.3 Infrared Sensor Check Mode
1 Conditions to start the mode
The infrared sensor check mode starts when all of the following conditions are met:
o
The infrared sensor error is not being detected.
o
Not in Demo mode.
o
Human activity sensor is not selected.
o
An error of Error Level 20 or higher is not present.
o
The signal for infrared sensor check is received. (Long-press the “AUTO COMFORT” button on the
remote control for 10 seconds)
2 Conditions to end the mode
The infrared sensor check mode ends when any of the following conditions is met:
o
A signal other than the signal for infrared sensor check is received; or the EMERGENCY button is
pressed
→
The signal received is followed.
o
5 minutes have elapsed since the signal for infrared sensor check was received
→
The mode is stopped.
o
The infrared sensor error is confirmed
→
The mode is stopped.
o
An error of Error Level 20 or higher has occurred
→
Follow the processing of each error.
Содержание CS-VE9NKE
Страница 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control...
Страница 13: ...13 5 Dimensions 5 1 Indoor Unit and Remote Control...
Страница 14: ...14 5 2 Outdoor Unit...
Страница 15: ...15 6 Refrigeration Cycle Diagram...
Страница 16: ...16 7 Block Diagram...
Страница 17: ...17 8 Wiring Connection Diagram 8 1 Indoor Unit...
Страница 18: ...18 8 2 Outdoor Unit...
Страница 19: ...19 9 Electronic Circuit Diagram 9 1 Indoor Unit...
Страница 20: ...20 9 2 Outdoor Unit...
Страница 21: ...21 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board...
Страница 22: ...22 10 1 2 Printed Circuit Board...
Страница 23: ...23 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board...
Страница 27: ...27...
Страница 68: ...68 15 4 Self diagnosis Method 15 4 1 H11 Indoor Outdoor Communication Error Troubleshooting...
Страница 69: ...69 15 4 2 H14 Indoor Unit Intake Air Temperature Sensor Error Troubleshooting...
Страница 71: ...71 15 4 8 H53 Heat Storage Tank Temperature Sensor Error Troubleshooting...
Страница 72: ...72 15 4 9 H16 Outdoor Unit CT Disconnection Error Troubleshooting...
Страница 73: ...73 15 4 10 H19 Indoor Unit Fan Motor Lock Error Troubleshooting...
Страница 74: ...74 15 4 11 H33 Connection Error of the Models with Different Voltage Power Supply Troubleshooting...
Страница 75: ...75 15 4 12 H38 Brand not Corresponding Troubleshooting...
Страница 76: ...76 15 4 13 H50 Ventilation Fan Motor Error Troubleshooting...
Страница 77: ...77 15 4 14 H51 Filter Cleaning Nozzle Lock Error Troubleshooting...
Страница 78: ...78 15 4 15 H59 Infrared Sensor Error Troubleshooting...
Страница 79: ...79 15 4 16 H67 NANOE Error Troubleshooting...
Страница 80: ...80 15 4 17 H70 Sunlight Sensor Error Troubleshooting...
Страница 81: ...81 15 4 18 H96 2 and 3 Way Valve Opening Failure Check Troubleshooting...
Страница 82: ...82 15 4 19 H97 Outdoor Unit Fan Motor Lock Error Troubleshooting...
Страница 83: ...83 15 4 20 H98 Indoor Unit Overpressure Protection Troubleshooting...
Страница 85: ...85 15 4 22 F11 Cooling Heating Switching Error Troubleshooting...
Страница 86: ...86 15 4 23 F16 Cooling Dry Switching Error Troubleshooting...
Страница 87: ...87 15 4 24 F19 Heat Storage Cycle Error Troubleshooting...
Страница 88: ...88 15 4 25 F90 PFC Protection Troubleshooting...
Страница 89: ...89 15 4 26 F91 Refrigeration Cycle Error Troubleshooting...
Страница 90: ...90 15 4 27 F93 Compressor Rotation Error Troubleshooting...
Страница 91: ...91 15 4 28 F95 Overpressure Protection in Case of Cooling Error Troubleshooting...
Страница 92: ...92 15 4 29 F96 Transistor Module Over temperature Protection Troubleshooting...
Страница 93: ...93 15 4 30 F97 Compressor Over temperature Protection Troubleshooting...
Страница 94: ...94 15 4 31 F98 Total Current Protection Control Troubleshooting...
Страница 95: ...95 15 4 32 F99 DC Peak Operation Error Troubleshooting...
Страница 127: ...127 Heating Characteristic Condition Room temperature 20 C DBT Piping length 5m Fh 37Hz...
Страница 131: ...131 Heating Characteristic Condition Room temperature 20 C DBT Piping length 5m Fh 49Hz...
Страница 134: ...134 18 Exploded View and Replacement Parts List 18 1 Indoor Unit...