39
12.4.1 Vertical
Airflow
Vertical Airflow Direction Louver
Airflow direction: Auto
Sensor
Airflow
direction:
Manual
Normal Powerful
Long
Normal
AUTO
According to each mode
Discharge
temperature
is high.
35°
Discharge
temperature
is medium.
2.2 ~ 3.6kW : 57°
4.0 ~ 5.6kW : 51°
6.3 ~ 7.1kW : 48°
Horizontal airflow
direction
When “Front, Spot or
Wide” is set:
40°
When “Slightly Right or
Slightly Left” is set:
40°
When “Right or Left” is
set:
68° (upper louver)
60° (lower louver)
3.6kW or below: 60°
(Slightly upward when there is no airflow
towards feet.)
When the furniture position has been set on the
remote control, the airflow direction is set
upward according to the setting.
4.0kW and above: Human detecting direction
When the furniture position has been set on the
remote control, the airflow direction is set
upward according to the setting.
When the human detection sensor detects an
obstacle automatically, the airflow direction is
set upward according to the detection.
HEAT
Discharge
temperature
is low.
1-4: Preset
angle (10-50°)
5: Preset
angle 60°
(57° when
there is no
airflow
towards feet.)
10°
Unstable:
10-40°
(Swing)
Initial airflow:
30°
Airflow unstable: Human detecting direction
3.6kW or below:
When the furniture position has been set on the
remote control, the airflow direction is set
upward according to the setting.
4.0kW and above:
When the furniture position has been set on the
remote control, the airflow direction is set
upward according to the setting.
When the human detection sensor detects an
obstacle automatically, the airflow direction is
set upward according to the detection.
COOL
1: Ceiling
airflow
2-5: Preset
angle (10-50°)
Stable: 10-35°
(Swing)
Other than
initial airflow:
10°
Horizontal airflow
direction
When “Front, Spot or
Wide” is set:
20°
When “Slightly Right or
Slightly Left” is set:
30°
When “Right or Left” is
set:
66° (upper louver)
60° (lower louver)
Airflow stable: Ceiling airflow
Drying unstable: Human detecting direction
3.6kW or below:
When the furniture position has been set on the
remote control, the airflow direction is set
upward according to the setting.
4.0kW and above:
When the furniture position has been set on the
remote control, the airflow direction is set
upward according to the setting.
When the human detection sensor detects an
obstacle automatically, the airflow direction is
set upward according to the detection.
COOL DRY
Mild Dry Cooling
(For the models of
6.3kW and above
only)
1: Ceiling
airflow
2-5: Preset
angle (10-40°)
Ceiling airflow
(No powerful setting for Mild
Dry Cooling)
Drying stable: Ceiling airflow
Initial
airflow: 30°
DRY
Same as the
manual
setting in
COOL mode.
Ceiling airflow Other than
initial airflow:
Ceiling
airflow
No setting is available.
Louver direction can be
set when the “Auto
Comfort” is set.
At this time, the angle is
the same as the Cool
Long mode if the mode
set is other than the
HEAT mode.
Ceiling airflow
Содержание CS-VE9NKE
Страница 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control...
Страница 13: ...13 5 Dimensions 5 1 Indoor Unit and Remote Control...
Страница 14: ...14 5 2 Outdoor Unit...
Страница 15: ...15 6 Refrigeration Cycle Diagram...
Страница 16: ...16 7 Block Diagram...
Страница 17: ...17 8 Wiring Connection Diagram 8 1 Indoor Unit...
Страница 18: ...18 8 2 Outdoor Unit...
Страница 19: ...19 9 Electronic Circuit Diagram 9 1 Indoor Unit...
Страница 20: ...20 9 2 Outdoor Unit...
Страница 21: ...21 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board...
Страница 22: ...22 10 1 2 Printed Circuit Board...
Страница 23: ...23 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board...
Страница 27: ...27...
Страница 68: ...68 15 4 Self diagnosis Method 15 4 1 H11 Indoor Outdoor Communication Error Troubleshooting...
Страница 69: ...69 15 4 2 H14 Indoor Unit Intake Air Temperature Sensor Error Troubleshooting...
Страница 71: ...71 15 4 8 H53 Heat Storage Tank Temperature Sensor Error Troubleshooting...
Страница 72: ...72 15 4 9 H16 Outdoor Unit CT Disconnection Error Troubleshooting...
Страница 73: ...73 15 4 10 H19 Indoor Unit Fan Motor Lock Error Troubleshooting...
Страница 74: ...74 15 4 11 H33 Connection Error of the Models with Different Voltage Power Supply Troubleshooting...
Страница 75: ...75 15 4 12 H38 Brand not Corresponding Troubleshooting...
Страница 76: ...76 15 4 13 H50 Ventilation Fan Motor Error Troubleshooting...
Страница 77: ...77 15 4 14 H51 Filter Cleaning Nozzle Lock Error Troubleshooting...
Страница 78: ...78 15 4 15 H59 Infrared Sensor Error Troubleshooting...
Страница 79: ...79 15 4 16 H67 NANOE Error Troubleshooting...
Страница 80: ...80 15 4 17 H70 Sunlight Sensor Error Troubleshooting...
Страница 81: ...81 15 4 18 H96 2 and 3 Way Valve Opening Failure Check Troubleshooting...
Страница 82: ...82 15 4 19 H97 Outdoor Unit Fan Motor Lock Error Troubleshooting...
Страница 83: ...83 15 4 20 H98 Indoor Unit Overpressure Protection Troubleshooting...
Страница 85: ...85 15 4 22 F11 Cooling Heating Switching Error Troubleshooting...
Страница 86: ...86 15 4 23 F16 Cooling Dry Switching Error Troubleshooting...
Страница 87: ...87 15 4 24 F19 Heat Storage Cycle Error Troubleshooting...
Страница 88: ...88 15 4 25 F90 PFC Protection Troubleshooting...
Страница 89: ...89 15 4 26 F91 Refrigeration Cycle Error Troubleshooting...
Страница 90: ...90 15 4 27 F93 Compressor Rotation Error Troubleshooting...
Страница 91: ...91 15 4 28 F95 Overpressure Protection in Case of Cooling Error Troubleshooting...
Страница 92: ...92 15 4 29 F96 Transistor Module Over temperature Protection Troubleshooting...
Страница 93: ...93 15 4 30 F97 Compressor Over temperature Protection Troubleshooting...
Страница 94: ...94 15 4 31 F98 Total Current Protection Control Troubleshooting...
Страница 95: ...95 15 4 32 F99 DC Peak Operation Error Troubleshooting...
Страница 127: ...127 Heating Characteristic Condition Room temperature 20 C DBT Piping length 5m Fh 37Hz...
Страница 131: ...131 Heating Characteristic Condition Room temperature 20 C DBT Piping length 5m Fh 49Hz...
Страница 134: ...134 18 Exploded View and Replacement Parts List 18 1 Indoor Unit...