121
16.2.8.3 Process 2 (Removing Brazing Point)
1 Removing butyl tape from piping prior to removing the brazing point.
Caution
Protection from the brazing flame should be considered during replacing the parts.
Firstly disconnect the pipe which entering to heat charger, discharging from heat charger, compressor
suction and the discharging pipes.
16.2.8.4 Separate Compressor from Heat Charger.
1 Take out blocks of compressor and heat charger from the base pan.
2 Cut off 2 bands (top and bottom) which holding compressor and heat charger, and lift the bracket to remove.
3 Remove the heat transferring sheet from the compressor once separate the heat charger from compressor.
4 Remove the sensor on heat charger by peeling off polyethylene sheet. Keep the sensor for re-use after the
brazing work.
Содержание CS-VE9NKE
Страница 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control...
Страница 13: ...13 5 Dimensions 5 1 Indoor Unit and Remote Control...
Страница 14: ...14 5 2 Outdoor Unit...
Страница 15: ...15 6 Refrigeration Cycle Diagram...
Страница 16: ...16 7 Block Diagram...
Страница 17: ...17 8 Wiring Connection Diagram 8 1 Indoor Unit...
Страница 18: ...18 8 2 Outdoor Unit...
Страница 19: ...19 9 Electronic Circuit Diagram 9 1 Indoor Unit...
Страница 20: ...20 9 2 Outdoor Unit...
Страница 21: ...21 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board...
Страница 22: ...22 10 1 2 Printed Circuit Board...
Страница 23: ...23 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board...
Страница 27: ...27...
Страница 68: ...68 15 4 Self diagnosis Method 15 4 1 H11 Indoor Outdoor Communication Error Troubleshooting...
Страница 69: ...69 15 4 2 H14 Indoor Unit Intake Air Temperature Sensor Error Troubleshooting...
Страница 71: ...71 15 4 8 H53 Heat Storage Tank Temperature Sensor Error Troubleshooting...
Страница 72: ...72 15 4 9 H16 Outdoor Unit CT Disconnection Error Troubleshooting...
Страница 73: ...73 15 4 10 H19 Indoor Unit Fan Motor Lock Error Troubleshooting...
Страница 74: ...74 15 4 11 H33 Connection Error of the Models with Different Voltage Power Supply Troubleshooting...
Страница 75: ...75 15 4 12 H38 Brand not Corresponding Troubleshooting...
Страница 76: ...76 15 4 13 H50 Ventilation Fan Motor Error Troubleshooting...
Страница 77: ...77 15 4 14 H51 Filter Cleaning Nozzle Lock Error Troubleshooting...
Страница 78: ...78 15 4 15 H59 Infrared Sensor Error Troubleshooting...
Страница 79: ...79 15 4 16 H67 NANOE Error Troubleshooting...
Страница 80: ...80 15 4 17 H70 Sunlight Sensor Error Troubleshooting...
Страница 81: ...81 15 4 18 H96 2 and 3 Way Valve Opening Failure Check Troubleshooting...
Страница 82: ...82 15 4 19 H97 Outdoor Unit Fan Motor Lock Error Troubleshooting...
Страница 83: ...83 15 4 20 H98 Indoor Unit Overpressure Protection Troubleshooting...
Страница 85: ...85 15 4 22 F11 Cooling Heating Switching Error Troubleshooting...
Страница 86: ...86 15 4 23 F16 Cooling Dry Switching Error Troubleshooting...
Страница 87: ...87 15 4 24 F19 Heat Storage Cycle Error Troubleshooting...
Страница 88: ...88 15 4 25 F90 PFC Protection Troubleshooting...
Страница 89: ...89 15 4 26 F91 Refrigeration Cycle Error Troubleshooting...
Страница 90: ...90 15 4 27 F93 Compressor Rotation Error Troubleshooting...
Страница 91: ...91 15 4 28 F95 Overpressure Protection in Case of Cooling Error Troubleshooting...
Страница 92: ...92 15 4 29 F96 Transistor Module Over temperature Protection Troubleshooting...
Страница 93: ...93 15 4 30 F97 Compressor Over temperature Protection Troubleshooting...
Страница 94: ...94 15 4 31 F98 Total Current Protection Control Troubleshooting...
Страница 95: ...95 15 4 32 F99 DC Peak Operation Error Troubleshooting...
Страница 127: ...127 Heating Characteristic Condition Room temperature 20 C DBT Piping length 5m Fh 37Hz...
Страница 131: ...131 Heating Characteristic Condition Room temperature 20 C DBT Piping length 5m Fh 49Hz...
Страница 134: ...134 18 Exploded View and Replacement Parts List 18 1 Indoor Unit...