15
8 Operation Details
8.1
.
Cooling Mode Operation
When selecting the Cooling Mode Operation, the unit will operate according to the setting by the Remote Controller or
the control panel on the indoor unit and the operation is as the following.
Time Delay Safety Control
3 min.----If the compressor stops, it will not restart within 3 minutes.(Protection of compressor).
7 Minutes Time Save Control
7 min.----The unit will automatically operate in 7 minutes even if the room temperature is not reached.
(Prevention of raising the humidity)
Evaporator
Temperature
(
)
10
2
Restart
4 minutes
Compressor ceases
Time
Anti-Freezing Control
If temperature of evaporator is lower than 2
continuously
for 4 minutes, the compressor will cease to prevent the
evaporator from freezing. Fan speed setting will not be
changed.
When temperature of evaporator reaches 10
,compressor
will restart.
During Cooling Mode Operation, the Time Delay Safety
Control is available.
Indoor Fan
STOP
Slow
Slow
STOP
STOP
Slow
Slow
STOP
ON
Compressor
ON
1 Fan speed will be at
Hi
till the compressor ceases (set temperature reached).
2 Fan speed will be at
Me
when the compressor restarts.
40
30
40
30
20
160
1
2
Automatic Fan Speed Mode
During Cooling Mode Operation, use remote controller to select Automatic Fan Speed.
Deodorization control.
Fan speed will be at the point between "High speed" and "Medium speed".
CS-PC9DKV / CU-PC9DKV / CS-PC12DKV / CU-PC12DKV