45
13.2. Protection Control For Cooling & Soft Dry Operation
13.2.1. Outdoor Air Temperature Control
• The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the diagram below.
• This control will begin 1 minute after the compressor starts.
• Compressor frequency will adjust base on outdoor air temperature.
13.2.2. Cooling Overload Control
• Detects the Outdoor pipe temperature and carry out below restriction/limitation (Limit the compressor Operation frequency)
• The compressor stop if outdoor pipe temperature exceeds 63
°
C.
• If the compressor stops 4 times in 20 minutes, Timer LED blinking (F95 indicated: outdoor high pressure rise protection)
13.2.3. Freeze Prevention Control 1
1. When indoor heat exchanger temperature is lower than 0
°
C continuously for 6 minutes, compressor will stop operating.
2. Compressor will resume its operation 3 minutes after the indoor heat exchanger is higher than 5
°
C.
3. At the same time, indoor fan speed will be higher than during its normal operation.
4. If indoor heat exchanger temperature is higher than 5
°
C for 5 minutes, the fan speed will return to its normal operation.
13.2.4. Freeze Prevention Control 2
1. Control start conditions
• During Cooling operation and soft dry operation
- During thermo OFF condition, indoor intake temperature is less than 10
°
C or
- Compressor stops for freeze prevention control
• Either one of the conditions above occurs 5 times in 60 minutes.
2. Control contents
• Operation stops
• Timer LED blinks and “H99” indicated
13.2.5. Dew Prevention Control 1
• To prevent dew formation at indoor unit discharge area.
• This control will be activated if:
- Outdoor air temperature and Indoor pipe temperature judgment by microcontroller is fulfilled.
- When Cooling or Dry mode is operated more than 20 minutes or more.
• This control stopped if:
- Compressor stopped.
- Remote control setting changed (fan speed / temperature).
- Outdoor air temperature and indoor intake temperature changed.
• Fan speed, angle of louver (vertical airflow angle) will be adjusted accordingly in this control.
- Fan speed will be increased slowly if the unit is in quiet mode but no change in normal cooling mode.
Содержание CS-NE9LKE
Страница 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control...
Страница 13: ...13 5 Dimensions 5 1 Indoor Unit...
Страница 14: ...14 5 2 Outdoor Unit...
Страница 15: ...15 6 Refrigeration Cycle Diagram...
Страница 16: ...16 7 Block Diagram...
Страница 17: ...17 8 Wiring Connection Diagram 8 1 Indoor Unit...
Страница 18: ...18 8 2 Outdoor Unit...
Страница 19: ...19 9 Electronic Circuit Diagram 9 1 Indoor Unit...
Страница 20: ...20 9 2 Outdoor Unit...
Страница 21: ...21 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board...
Страница 22: ...22 10 1 2 Power Printed Circuit Board 10 1 3 Indicator Printed Circuit Board...
Страница 23: ...23 10 1 4 Receiver Printed Circuit Board 10 1 5 High Voltage Power Supply Printed Circuit Board...
Страница 24: ...24 10 2 Outdoor Unit...
Страница 80: ...80 16 1 3 To remove discharge grille...
Страница 81: ...81 16 1 4 To remove control board 16 1 5 To remove cross flow fan and indoor fan motor...
Страница 82: ...82...
Страница 84: ...84 17 Technical Data 17 1 Operation Characteristics 17 1 1 CU NE9LKE...
Страница 85: ...85...
Страница 86: ...86...
Страница 87: ...87...
Страница 88: ...88 17 1 2 CU NE12LKE...
Страница 89: ...89...
Страница 90: ...90...
Страница 91: ...91...