15.4.16. H99 (Indoor Freeze Prevention Protection: Cooling or Soft Dry)
Error code will not display (no TIMER LED blinking) but store in EEPROM
Malfunction Decision Conditions
Freeze prevention control takes place (when indoor pipe temperature is lower than 2
°
C)
Malfunction Caused
• Clogged air filter of the indoor unit
• Dust accumulation on the indoor unit heat exchanger
• Air short circuit
• Detection error due to faulty indoor pipe temperature sensor
• Detection error due to faulty indoor unit PCB
Troubleshooting
Содержание CS-NE9LKE
Страница 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control...
Страница 13: ...13 5 Dimensions 5 1 Indoor Unit...
Страница 14: ...14 5 2 Outdoor Unit...
Страница 15: ...15 6 Refrigeration Cycle Diagram...
Страница 16: ...16 7 Block Diagram...
Страница 17: ...17 8 Wiring Connection Diagram 8 1 Indoor Unit...
Страница 18: ...18 8 2 Outdoor Unit...
Страница 19: ...19 9 Electronic Circuit Diagram 9 1 Indoor Unit...
Страница 20: ...20 9 2 Outdoor Unit...
Страница 21: ...21 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board...
Страница 22: ...22 10 1 2 Power Printed Circuit Board 10 1 3 Indicator Printed Circuit Board...
Страница 23: ...23 10 1 4 Receiver Printed Circuit Board 10 1 5 High Voltage Power Supply Printed Circuit Board...
Страница 24: ...24 10 2 Outdoor Unit...
Страница 80: ...80 16 1 3 To remove discharge grille...
Страница 81: ...81 16 1 4 To remove control board 16 1 5 To remove cross flow fan and indoor fan motor...
Страница 82: ...82...
Страница 84: ...84 17 Technical Data 17 1 Operation Characteristics 17 1 1 CU NE9LKE...
Страница 85: ...85...
Страница 86: ...86...
Страница 87: ...87...
Страница 88: ...88 17 1 2 CU NE12LKE...
Страница 89: ...89...
Страница 90: ...90...
Страница 91: ...91...