2.
Protection Control For Cooling & Soft Dry
Fan Speed
Shift
Hi
2 rank down
Me+
3 rank up
Me
unchange
Me
-
unchange
Lo
2 rank up
a. Anti-Freezing Control
•
When the temperature of the indoor heat exchanger becomes low, the compressor operating frequency is reduced and
stopped when the temperature falls to lower than 2°C continuously for 6 minutes. This is to prevent freezing of indoor heat
exchanger. When the temperature rises to 10°C or above, the compressor restarts with 3 minutes. The compressor
operating frequency will resume to normal when the temperature reaches 14°C.
•
Indoor fan speed will increase when the temperature falls and it will resume to original speed when the temperature
increases to 14°C for 5 minutes continuously.
Note: The above phenomenon occurs when the fan is running at Me+ or below.
b. Anti-Dew Formation Control
•
When the following conditions occurs for 20 minutes continuously, anti-dew formation is controlled:
1. Indoor intake air temperature is 24°C or above.
2. Outdoor air temperature is less than 30°C.
3. Remote control setting temperature is less than 25°C.
•
During anti-dew formation control, compressor operates at 36 Hz (CS-G95KE) or 44 Hz (CS-G125KE) and airflow direction
vane move slightly (as shown in Airflow Direction Control). Indoor fan speed will shift as below:
•
This control is cancelled immediately when either condition 1-3 as written above is changed, or remote control setting
temperature or fan speed is changed.
45
CS-G95KE CU-G95KE / CS-G125KE CU-G125KE
Содержание CS-G125KE CU-G125KE
Страница 12: ...4 Dimensions 12 S G95KE CU G95KE CS G125KE CU G125KE ...
Страница 13: ...13 CS G95KE CU G95KE CS G125KE CU G125KE ...
Страница 14: ...5 Refrigeration Cycle Diagram 14 S G95KE CU G95KE CS G125KE CU G125KE ...
Страница 15: ...6 Block Diagram 15 CS G95KE CU G95KE CS G125KE CU G125KE ...
Страница 24: ... ii When indoor fan speed is lower than Medium 24 S G95KE CU G95KE CS G125KE CU G125KE ...
Страница 94: ...12 Technical Data 94 S G95KE CU G95KE CS G125KE CU G125KE ...
Страница 95: ...95 CS G95KE CU G95KE CS G125KE CU G125KE ...
Страница 109: ...109 CS G95KE CU G95KE CS G125KE CU G125KE ...
Страница 112: ...18 1 PRINT PATTERN INDOOR UNIT PRINTED CIRCUIT BOARD 112 S G95KE CU G95KE CS G125KE CU G125KE ...
Страница 113: ...18 2 PRINT PATTERN OUTDOOR UNIT PRINTED CIRCUIT BOARDBOTTOM VIEW 113 CS G95KE CU G95KE CS G125KE CU G125KE ...
Страница 114: ...114 S G95KE CU G95KE CS G125KE CU G125KE MACC Printed in Malaysia ...