When the operation mode is changed over, the value for t1, t2 and t3 are shifted as below:
Cooling/Soft dry
→
Heating: - 2°C
Heating
→
Cooling/Soft dry: + 2°C
•
When the indoor intake air temperature is lower than 16°C, heating operation is immediately started.
•
When the outdoor air temperature is more than 25°C, and the intake air temperature is over 16°C, cooling operation is
immediately started.
•
The operation mode is judged every 30 minutes.
•
When the operation mode (Heating, Cooling or Soft Dry) is decided, the internal setting temperature will shift as shown below:
32
S-G95KE CU-G95KE / CS-G125KE CU-G125KE