12 Operation and Control
12.1. Basic Function
Inverter control, which equipped with a microcomputer in determining the most suitable operating mode as time passes,
automatically adjusts output power for maximum comfort always. In order to achieve the suitable operating mode, the
microcomputer maintains the set temperature by measuring the temperature of the environment and performing temperature
shifting. The compressor at outdoor unit is operating following the frequency instructed by the microcomputer at indoor unit that
judging the condition according to internal setting temperature and intake air temperature.
12.1.1.
Internal Setting Temperature
Once the operation starts, remote control setting temperature will be taken as base value for temperature shifting processes.
These shifting processes are depending on the air conditioner settings and the operation environment. The final shifted value
will be used as internal setting temperature and it is updated continuously whenever the electrical power is supplied to the unit.
12.1.2.
Cooling Operation
12.1.2.1. Thermostat control
• Compressor is OFF when Intake Air Temperature - Internal Setting Temperate < -1.5
q
C.
• Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature > Compressor OFF
point.
12.1.3.
Soft Dry Operation
12.1.3.1. Thermostat control
• Compressor is OFF when Intake Air Temperature - Internal Setting Temperate < -2.0
q
C.
• Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature > Compressor OFF
point.
12.1.4.
Heating Operation
12.1.4.1. Thermostat control
• Compressor is OFF when Intake Air Temperature - Internal Setting Temperate > +2.0
q
C.
• Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature < Compressor OFF
point.
Содержание CS-E18JKEW
Страница 9: ...9 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Страница 10: ...10 5 Dimensions 5 1 Indoor Unit Remote Control ...
Страница 11: ...11 5 2 Outdoor Unit 5 2 1 CU RE18JKE ...
Страница 12: ...12 5 2 2 CU RE24JKE ...
Страница 13: ...13 6 Refrigeration Cycle Diagram ...
Страница 14: ...14 7 Block Diagram 7 1 CS RE18JKE CU RE18JKE ...
Страница 15: ...15 7 2 CS RE24JKE CU RE24JKE ...
Страница 16: ...16 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Страница 17: ...17 8 2 Outdoor Unit 8 2 1 CU RE18JKE ...
Страница 18: ...18 8 2 2 CU RE24JKE ...
Страница 19: ...19 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Страница 20: ...20 9 2 Outdoor Unit 9 2 1 CU RE18JKE ...
Страница 21: ...21 9 2 2 CU RE24JKE ...
Страница 22: ...22 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Страница 23: ...23 10 1 2 Power Printed Circuit Board 10 1 3 Indicator Printed Circuit Board ...
Страница 24: ...24 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board 10 2 1 1 CU RE18JKE ...
Страница 25: ...25 10 2 2 Main Printed Circuit Board 10 2 2 1 CU RE24JKE ...
Страница 26: ...26 10 2 3 Power Printed Circuit Board 10 2 3 1 CU RE24JKE ...
Страница 29: ...29 1 For the right rear piping 2 For the right and right bottom piping 3 For the embedded piping ...
Страница 76: ...76 16 1 3 To remove power electronic controller ...
Страница 77: ...77 16 1 4 To remove discharge grille 16 1 5 To remove control board ...
Страница 78: ...78 16 1 6 To remove cross flow fan and indoor fan motor ...
Страница 79: ...79 ...
Страница 90: ...90 18 Exploded View and Replacement Parts List 18 1 Indoor Unit ...