43
13.2.5.
Freeze Prevention Control 1
1. When indoor heat exchanger temperature is lower than 0
q
C continuously for six minutes, compressor will stop operating.
2. Compressor will resume its operation three minutes after the indoor heat exchanger is higher than 13
q
C.
3. At the same time, indoor fan speed will be higher than during its normal operation.
4. If indoor heat exchanger temperature is higher than 13
q
C for five minutes, the fan speed will return to its normal operation.
13.2.6.
Freeze Prevention Control 2
1. Control start conditions
• During Cooling operation and soft dry operation.
- During thermo OFF condition, indoor intake temperature is less than 10°C or
- Compressor stops for freeze prevention control
• Either one of the conditions above occurs 5 times in 60 minutes.
2. Control contents
• Operation stops.
• Timer LED blinks and “H99” indicated.
Содержание CS-E18JKEW
Страница 9: ...9 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Страница 10: ...10 5 Dimensions 5 1 Indoor Unit Remote Control ...
Страница 11: ...11 5 2 Outdoor Unit 5 2 1 CU RE18JKE ...
Страница 12: ...12 5 2 2 CU RE24JKE ...
Страница 13: ...13 6 Refrigeration Cycle Diagram ...
Страница 14: ...14 7 Block Diagram 7 1 CS RE18JKE CU RE18JKE ...
Страница 15: ...15 7 2 CS RE24JKE CU RE24JKE ...
Страница 16: ...16 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Страница 17: ...17 8 2 Outdoor Unit 8 2 1 CU RE18JKE ...
Страница 18: ...18 8 2 2 CU RE24JKE ...
Страница 19: ...19 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Страница 20: ...20 9 2 Outdoor Unit 9 2 1 CU RE18JKE ...
Страница 21: ...21 9 2 2 CU RE24JKE ...
Страница 22: ...22 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Страница 23: ...23 10 1 2 Power Printed Circuit Board 10 1 3 Indicator Printed Circuit Board ...
Страница 24: ...24 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board 10 2 1 1 CU RE18JKE ...
Страница 25: ...25 10 2 2 Main Printed Circuit Board 10 2 2 1 CU RE24JKE ...
Страница 26: ...26 10 2 3 Power Printed Circuit Board 10 2 3 1 CU RE24JKE ...
Страница 29: ...29 1 For the right rear piping 2 For the right and right bottom piping 3 For the embedded piping ...
Страница 76: ...76 16 1 3 To remove power electronic controller ...
Страница 77: ...77 16 1 4 To remove discharge grille 16 1 5 To remove control board ...
Страница 78: ...78 16 1 6 To remove cross flow fan and indoor fan motor ...
Страница 79: ...79 ...
Страница 90: ...90 18 Exploded View and Replacement Parts List 18 1 Indoor Unit ...