44
12 Protection Control
12.1. Protection Control For All Operations
12.1.1.
Time Delay Safety Control
1. The compressor will not start for three minutes after stop of operation.
2. This control is not applicable if the power supply is cut off and on again or after 4-way valve deices condition.
12.1.2.
30 Seconds Forced Operation
1. Once the compressor starts operation, it will not stop its operation for 30 seconds.
2. However, it can be stopped using remote control or Auto Switch at indoor unit.
12.1.3.
Total Running Current Control
1. When the outdoor unit total running current (AC) exceeds X value, the frequency instructed for compressor operation will be
decreased.
2. If the running current does not exceed X value for five seconds, the frequency instructed will be increased.
3. However, if total outdoor unit running current exceeds Y value, compressor will be stopped immediately for three minutes.
4. The first 30 minutes of cooling operation, (A) will be applied.
12.1.4.
IPM (Power transistor) Prevention Control
A. Overheating Prevention Control
1. When the IPM temperature rises to 110
°
C, compressor operation will stop immediately.
2. Compressor operation restarts after three minutes the temperature decreases to 95
°
C.
B. DC Peak Current Control
1. When electric current to IPM exceeds set value of 25.0 ± 4.0 A, the compressor will stop operate. Then, operation will restart
after three minutes.
2. If the set value is exceeded again more than 30 seconds after the compressor starts, the operation will restart after two
minute.
3. If the set value is exceeded again within 30 seconds after the compressor starts, the operation will restart after one minute. If
this condition repeats continuously for seven times, all indoor and outdoor relays will be cut off.
E21EK
E18EK
E18EK
Operation Mode
X (A)
Y (A)
X (A)
Y (A)
X (A)
Y (A)
Cooling/Soft Dry (A)
11.0
15.0
8.8
15.0
7.2
15.0
Cooling/Soft Dry (B)
9.6
15.0
7.7
15.0
6.3
15.0
Heating
11.5
17.0
10.8
17.0
8.6
17.0
Содержание CS-E15EKEA
Страница 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 CS E15EKEA 4 1 2 CS E18EKEA CS E21EKEA ...
Страница 13: ...13 4 2 Outdoor Unit 4 3 Remote Control ...
Страница 14: ...14 5 Dimensions 5 1 Indoor Unit Remote Control 5 1 1 CS E15EKEA ...
Страница 15: ...15 5 1 2 CS E18EKEA CS E21EKEA ...
Страница 16: ...16 5 2 Outdoor Unit ...
Страница 18: ...18 7 Block Diagram ...
Страница 19: ...19 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Страница 20: ...20 8 2 Outdoor Unit ...
Страница 21: ...21 9 Printed Circuit Board 9 1 Indoor Unit 9 1 1 Main Printed Circuit Board ...
Страница 22: ...22 ...
Страница 23: ...23 9 1 2 Power Printed Circuit Board ...
Страница 24: ...24 ...
Страница 25: ...25 9 2 Outdoor Unit ...
Страница 26: ...26 ...
Страница 29: ...29 3 For the embedded piping This can be used for left rear piping left bottom piping also ...
Страница 35: ...35 3 For the embedded piping This can be used for left rear piping left bottom piping also ...
Страница 55: ...55 ...
Страница 56: ...56 15 2 Indoor Cross Flow Fan and Fan Motor ...
Страница 57: ...57 ...
Страница 60: ...60 ...
Страница 62: ...62 ...
Страница 64: ...64 ...
Страница 66: ...66 ...
Страница 68: ...68 ...
Страница 70: ...70 ...
Страница 72: ...72 ...
Страница 74: ...74 ...
Страница 76: ...76 ...
Страница 78: ...78 ...
Страница 80: ...80 ...
Страница 82: ...82 ...