41
1. When one of the following conditions is satisfied, quiet operation stops:
a. Powerful button is pressed.
b. Stop by OFF/ON switch.
c. Timer “off” activates.
d. Quiet button is pressed again.
2. When quiet operation is stopped, operation is shifted to normal operation with previous setting.
3. When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.
4. When operation mode is changed, quiet operation is shifted to quiet operation of the new mode.
5. During quiet operation, if timer “on” activates, quiet operation maintains.
6. After off, when on back, quiet operation is not memorised.
C. Control contents
1. Fan speed is changed from normal setting to quiet setting of respective fan speed.
This is to reduce sound of Hi, Me, Lo for 3dB.
2. Fan speed for quiet operation is -100 rpm from setting fan speed.
11.3.1.
Quiet operation under Soft Dry operation (Dry area at Soft Dry Mode)
Automatic Fan Speed (Soft dry operation)
Manual Fan Speed (Soft dry operation)
11.3.2.
Quiet operation (Heating)
A. Purpose
To provide quiet heating operation compare to normal operation.
B. Control condition
a. Quiet operation start condition
• When “quiet” button at remote control is pressed.
Quiet LED illuminates.
b. Quiet operation stop condition
1. When one of the following conditions is satisfied, quiet operation stops:
a. Powerful button is pressed.
b. Stop by OFF/ON switch.
c. Timer “off” activates.
d. Quiet button is pressed again.
2. When quiet operation is stopped, operation is shifted to normal operation with previous setting.
3. When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.
4. When operation mode is changed, quiet operation is shifted to quiet operation of the new mode, except fan only mode.
5. During quiet operation, if timer “on” activates, quiet operation maintains.
6. After off, when on back, quiet operation is not memorised.
Содержание CS-E15EKEA
Страница 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 CS E15EKEA 4 1 2 CS E18EKEA CS E21EKEA ...
Страница 13: ...13 4 2 Outdoor Unit 4 3 Remote Control ...
Страница 14: ...14 5 Dimensions 5 1 Indoor Unit Remote Control 5 1 1 CS E15EKEA ...
Страница 15: ...15 5 1 2 CS E18EKEA CS E21EKEA ...
Страница 16: ...16 5 2 Outdoor Unit ...
Страница 18: ...18 7 Block Diagram ...
Страница 19: ...19 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Страница 20: ...20 8 2 Outdoor Unit ...
Страница 21: ...21 9 Printed Circuit Board 9 1 Indoor Unit 9 1 1 Main Printed Circuit Board ...
Страница 22: ...22 ...
Страница 23: ...23 9 1 2 Power Printed Circuit Board ...
Страница 24: ...24 ...
Страница 25: ...25 9 2 Outdoor Unit ...
Страница 26: ...26 ...
Страница 29: ...29 3 For the embedded piping This can be used for left rear piping left bottom piping also ...
Страница 35: ...35 3 For the embedded piping This can be used for left rear piping left bottom piping also ...
Страница 55: ...55 ...
Страница 56: ...56 15 2 Indoor Cross Flow Fan and Fan Motor ...
Страница 57: ...57 ...
Страница 60: ...60 ...
Страница 62: ...62 ...
Страница 64: ...64 ...
Страница 66: ...66 ...
Страница 68: ...68 ...
Страница 70: ...70 ...
Страница 72: ...72 ...
Страница 74: ...74 ...
Страница 76: ...76 ...
Страница 78: ...78 ...
Страница 80: ...80 ...
Страница 82: ...82 ...