14.4. Error Codes Table
Note:
“O” - Frequency measured and fan speed fixed.
The memory data of error code is erased when the power supply is cut off, or press the Auto Switch until “beep” sound heard
following by pressing the “CHECK” button at Remote Control.
Although operation forced to stop when abnormality detected, emergency operation is possible for certain errors (refer to Error
Codes Table) by using Remote Control or Auto Switch at indoor unit. However, the Remote Control signal receiving sound is
changed from one “beep” to four “beep” sounds.
Abnormality / Protection control
Abnormality
Judgement
Emergency
operation
Primary location to verify
Diagnosis
display
H00
No abnormality detected
—
Normal operation
—
H11
Indoor / outdoor abnormal
communication
> 1 min after starting
operation
Indoor fan operation
only
• Internal / external cable connections
• Indoor / Outdoor PCB
H14
Indoor intake air temperature sensor
abnormality
Continue for 5 sec.
—
• Intake air temperature sensor
(defective or disconnected)
H15
Outdoor compressor temperature sensor
abnormality
Continue for 5 sec.
—
• Compressor temperature sensor
(defective or disconnected)
H16
Outdoor Current Transformer open
circuit
—
—
• Outdoor PCB
• IPM (Power transistor) module
H19
Indoor fan motor merchanism lock
—
—
• Indoor PCB
• Fan motor
H23
Indoor heat exchanger temperature
sensor abnormality
Continue for 5 sec.
O
(Cooling only)
• Heat exchanger temperature sensor
(defective or disconnected)
H24
Indoor heat exchanger temperature
sensor 2 abnormality
Continue for 5 sec.
—
• Heat exchanger temperature sensor 2
(defective or disconnected)
H26
Ion abnormality
—
—
• Indoor PCB
• Ionizer
H27
Outdoor air temperature sensor
abnormality
Continue for 5 sec.
O
• Outdoor temperature sensor
(defective or disconnected)
H28
Outdoor heat exchanger temperature
sensor abnormality
Continue for 5 sec.
O
• Outdoor heat exchanger temperature
sensor (defective or disconnected)
H30
Discharge temperature sensor
abnormality
Continue for 5 sec.
—
• Discharge temperature sensor
H33
Indoor/Outdoor wrong connection
—
—
• Indoor/Outdoor supply voltage
H38
Indoor/Outdoor mismatch (brand code)
—
—
—
H97
Outdoor Fan Motor lock abnormality
2 times occurance
within 30 minutes
—
• Outdoor PCB
• Outdoor Fan Motor
H98
Indoor high pressure protection
—
—
• Air filter dirty
• Air circulation short circuit
H99
Indoor heat exchanger anti-freezing pro-
tection
—
—
• Insufficient refrigerant
• Air filter dirty
F11
Cooling / Heating cycle changeover
abnormality
4 times occurance
within 30 minutes
—
• 4-way valve
• V-coil
F90
PFC control
4 times occurance
within 10 minutes
—
• Voltage at PFC
F91
Refrigeration cycle abnormality
2 times occurance
within 20 minutes
—
• No refrigerant
(3-way valve is closed)
F93
Outdoor compressor abnormal revolution
4 times occurance
within 20 minutes
—
• Outdoor compressor
F95
Cool high pressure protection
4 times occurance
within 20 minutes
—
• Outdoor refrigerant circuit
F96
IPM (power transistor) overheating
protection
—
—
• Excess refrigerant
• Improper heat radiation
• IPM (Power transistor)
F97
Outdoor compressor overheating
protection
4 times occurance
within 10 minutes
—
• Insufficient refrigerant
• Compressor
F98
Total running current protection
3 times occurance
within 20 minutes
—
• Excess refrigerant
• Improper heat radiation
F99
Outdoor Direct Current (DC) peak
detection
7 times occurance
continuously
—
• Outdoor PCB
• IPM (Power transistor)
• Compressor
Содержание CS-E15EKEA
Страница 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 CS E15EKEA 4 1 2 CS E18EKEA CS E21EKEA ...
Страница 13: ...13 4 2 Outdoor Unit 4 3 Remote Control ...
Страница 14: ...14 5 Dimensions 5 1 Indoor Unit Remote Control 5 1 1 CS E15EKEA ...
Страница 15: ...15 5 1 2 CS E18EKEA CS E21EKEA ...
Страница 16: ...16 5 2 Outdoor Unit ...
Страница 18: ...18 7 Block Diagram ...
Страница 19: ...19 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Страница 20: ...20 8 2 Outdoor Unit ...
Страница 21: ...21 9 Printed Circuit Board 9 1 Indoor Unit 9 1 1 Main Printed Circuit Board ...
Страница 22: ...22 ...
Страница 23: ...23 9 1 2 Power Printed Circuit Board ...
Страница 24: ...24 ...
Страница 25: ...25 9 2 Outdoor Unit ...
Страница 26: ...26 ...
Страница 29: ...29 3 For the embedded piping This can be used for left rear piping left bottom piping also ...
Страница 35: ...35 3 For the embedded piping This can be used for left rear piping left bottom piping also ...
Страница 55: ...55 ...
Страница 56: ...56 15 2 Indoor Cross Flow Fan and Fan Motor ...
Страница 57: ...57 ...
Страница 60: ...60 ...
Страница 62: ...62 ...
Страница 64: ...64 ...
Страница 66: ...66 ...
Страница 68: ...68 ...
Страница 70: ...70 ...
Страница 72: ...72 ...
Страница 74: ...74 ...
Страница 76: ...76 ...
Страница 78: ...78 ...
Страница 80: ...80 ...
Страница 82: ...82 ...