13 Servicing Mode
13.1. Auto Switch Operation
The below operations will be performed by pressing the “AUTO” switch.
1. AUTO OPERATION MODE
The Auto operation will be activated immediately once the Auto Switch is pressed.
2. TEST RUN OPERATION (FOR PUMP DOWN/SERVICING PURPOSE)
The Test Run operation will be activated if the Auto Switch is pressed continuously for more than 5 sec. A “beep” sound will
occur at the fifth sec., in order to identify the starting of Test Run operation.
3. REMOTE CONTROLLER RECEIVING SOUND ON/OFF
The ON/OFF of remote controller receiving sound can be change over by pressing the following step:
a. Release the Auto Switch after Test Run operation is activated.
b. Then, within 20 sec., after a., press Auto Switch for more than 5 sec.
A “beep” “beep” sound will occur at the fifth sec., then release the Auto Switch.
c. Within 20 sec. after b., press Auto Switch again. Everytime Auto Switch is pressed (within 20 sec. interval), remote
controller receiving sound status will be reversed between ON and OFF.
Long “beep” sound indicates that remote controller receiving sound is OFF.
Short “beep” sound indicates that remote controller receiving sound is ON.
4.
a. When the switch is pressed between 0 to 5 seconds, Auto Mode operation starts to function.
b. When the switch is pressed between 5 to 8 seconds, the unit is forced to operate in Cooling Mode.
c. When the switch is pressed between 8 to 11 seconds, the unit will enter forced Heating Mode standby. Press timer
decrement button for 5S for the unit to operate in Heating Mode.
d. When the switch is pressed between 11 to 16 seconds and together with the signal from remote control (timer decrement
button for 5S), the unit can be changed to different controlling setting (4 type of transmission codes).
e. When the switch is pressed between 16 to 21 seconds, either “H14” error detection selection mode or the remote control
signal receiving sound can be cancelled or turned on.
13.2. Selecting The Wireless Remote Control Transmission Code
When there are more than one indoor units installed in the same room, it is possible to set different remote control receiving signal
by modifying the jumpers inside Remote Control.
Содержание CS-E15EKEA
Страница 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 CS E15EKEA 4 1 2 CS E18EKEA CS E21EKEA ...
Страница 13: ...13 4 2 Outdoor Unit 4 3 Remote Control ...
Страница 14: ...14 5 Dimensions 5 1 Indoor Unit Remote Control 5 1 1 CS E15EKEA ...
Страница 15: ...15 5 1 2 CS E18EKEA CS E21EKEA ...
Страница 16: ...16 5 2 Outdoor Unit ...
Страница 18: ...18 7 Block Diagram ...
Страница 19: ...19 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Страница 20: ...20 8 2 Outdoor Unit ...
Страница 21: ...21 9 Printed Circuit Board 9 1 Indoor Unit 9 1 1 Main Printed Circuit Board ...
Страница 22: ...22 ...
Страница 23: ...23 9 1 2 Power Printed Circuit Board ...
Страница 24: ...24 ...
Страница 25: ...25 9 2 Outdoor Unit ...
Страница 26: ...26 ...
Страница 29: ...29 3 For the embedded piping This can be used for left rear piping left bottom piping also ...
Страница 35: ...35 3 For the embedded piping This can be used for left rear piping left bottom piping also ...
Страница 55: ...55 ...
Страница 56: ...56 15 2 Indoor Cross Flow Fan and Fan Motor ...
Страница 57: ...57 ...
Страница 60: ...60 ...
Страница 62: ...62 ...
Страница 64: ...64 ...
Страница 66: ...66 ...
Страница 68: ...68 ...
Страница 70: ...70 ...
Страница 72: ...72 ...
Страница 74: ...74 ...
Страница 76: ...76 ...
Страница 78: ...78 ...
Страница 80: ...80 ...
Страница 82: ...82 ...