Outdoor Unit
5
Panasonic
Anti-reverse Protection
To protect the compressor from reverse
rotation when power off suddenly.
Overload Protector
The 2-step Overload Protector is to protect
the compressor when
1)Temperature of compressor reaches 153
(YW9DKE) or
2)High temperature or current enters into the
compressor
146
(YW12DKE)
60-seconds Test Operation Control
Once the compressor is activated, it does not
stop for 60 seconds. It stops immediately with
remote control ON/OFF button.
Anti-freezing operation for outdoor unit
(during Heating Mode Operation only)
Temperature of the condenser is tested
by TRS.
Deicing Control
4-way Valve Control
If the unit is stopped during Heating
Operation,the 4-way valve will remain in
heating mode operation for 5 minutes.
CS-YW9DKE / CU-YW9DKE / CS-YW12DKE / CU-YW12DKE
Overload Protection Control
When the temperature of evaporator
reaches 51
,outdoor fan stops,and will
restart when the temperature of evaporator
declines to 49
.
When the temperature of evaporator
reaches 65
,compressor will stop.