Panasonic CS/CU-HU12ZKY Series Скачать руководство пользователя страница 6

6

Prevent water leakage by ensuring drainage 

pipe is:

 -Connected properly,

 -Kept clear of gutters and containers, or

 -Not immersed in water

After a long period of use or use with any 

combustible equipment, aerate the room 

regularly.
After a long period of use, make sure the 

installation rack does not deteriorate to 

prevent the unit from falling down.

Remote control

Do not use rechargeable (Ni-Cd) batteries. It 

may damage the remote control.
To prevent malfunction or damage of the 

remote control:

• Remove the batteries if the unit is not going 

to be used for a long period of time.

• New batteries of the same type must be 

inserted following the polarity stated.

Power supply

Do not disconnect the plug by pulling the cord 

to prevent electric shock.

Precaution for using R32 refrigerant

The basic installation work procedures are the same as 

conventional refrigerant (R410A, R22) models.

1. Installation (Space)

• Must ensure the installation of pipe-work 

shall be kept to a minimum. Avoid use 

dented pipe and do not allow acute bending.

• Must ensure that pipe-work shall be 

protected from physical damage.

• Must comply with national gas regulations, 

state municipal rules and legislation. Notify 

relevant authorities in accordance with all 

applicable regulations.

• Must ensure mechanical connections be 

accessible for maintenance purposes.

• In cases that require mechanical ventilation, 

ventilation openings shall be kept clear of 

obstruction.

• When disposal of the product, do follow 

to the precautions in #12 and comply with 

national regulations.

Always contact to local municipal offi ces for 

proper handling.

Safety precautions

2. Servicing

2-1. Service personnel

• Any qualifi ed person who is involved with 

working on or breaking into a refrigerant 

circuit should hold a current valid certifi cate 

from an industry-accredited assessment 

authority, which authorizes their competence 

to handle refrigerants safely in accordance 

with an industry recognised assessment 

specifi cation.

• Servicing shall only be performed 

as recommended by the equipment 

manufacturer.

Maintenance and repair requiring the 

assistance of other skilled personnel shall 

be carried out under the supervision of the 

person competent in the use of fl ammable 

refrigerants.

• Servicing shall be performed only as 

recommended by the manufacturer.

2-2. Work

• Prior to beginning work on systems 

containing fl ammable refrigerants, safety 

checks are necessary to ensure that the risk 

of ignition is minimised.

For repair to the refrigerating system, the 

precautions in #2-2 to #2-8 must be followed 

before conducting work on the system.

• Work shall be undertaken under a controlled 

procedure so as to minimize the risk of a 

fl ammable gas or vapour being present while 

the work is being performed.

• All maintenance staff and others working 

in the local area shall be instructed and 

supervised on the nature of work being 

carried out.

• Avoid working in confi ned spaces.

• Wear appropriate protective equipment, 

including respiratory protection, as 

conditions warrant.

• Ensure that the conditions within the area 

have been made safe by limit of use of any 

fl ammable material. Keep all sources of 

ignition and hot metal surfaces away.

2-3. Checking for presence of refrigerant

• The area shall be checked with an 

appropriate refrigerant detector prior to and 

during work, to ensure the technician is 

aware of potentially fl ammable atmospheres.

• Ensure that the leak detection equipment 

being used is suitable for use with fl ammable 

refrigerants, i.e. non sparking, adequately 

sealed or intrinsically safe.

• In case of leakage/spillage happened, 

immediately ventilate area and stay upwind 

and away from spill/release.

• In case of leakage/spillage happened, do 

notify persons down wind of the leaking/spill, 

isolate immediate hazard area and keep 

unauthorized personnel out.

Содержание CS/CU-HU12ZKY Series

Страница 1: ...fore installation the installer should Read the Installation Operating Instructions then request the customer keep them for future reference Remove the remote control packed with the indoor unit Air c...

Страница 2: ...INVERTER leverages ECONAVI sensor data and varies compressor rotation speed This helps to optimize cooling operation and reduces wasteful cooling nanoe G nanoeX Purifies the air down to the smallest p...

Страница 3: ...FAN DRY 2 1 3 7m Accessories Remote control AAA or R03 batteries X 2 Remote control holder Screws for remote control holder X 2 Ag Clean PM 0 1 Filter Safety precautions 4 9 How to use 10 11 To learn...

Страница 4: ...pecialist to clean the internal parts repair install remove and reinstall the unit Improper installation and handling will cause leakage electric shock or fire Confirm with authorised dealer or specia...

Страница 5: ...the same as conventional refrigerant R410A R22 models Since the working pressure is higher than that of refrigerant R22 models some of the piping and installation and service tools are special Especi...

Страница 6: ...accredited assessment authority which authorizes their competence to handle refrigerants safely in accordance with an industry recognised assessment specification Servicing shall only be performed as...

Страница 7: ...where they are unlikely to be exposed to any substance which may corrode refrigerant containing components unless the components are constructed of materials which are inherently resistant to being co...

Страница 8: ...nd during the brazing process 8 Removal and evacuation When breaking into the refrigerant circuit to make repairs or for any other purpose conventional procedures shall be used However it is important...

Страница 9: ...hat it has been de commissioned and emptied of refrigerant The label shall be dated and signed Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant 12 Rec...

Страница 10: ...ling operation Vertical flaps will not work in AUTO air swing in HU and AU18 4F Model FAN To operate Air Con in Fan Only mode Indoor unit temp display will show set temp for AUTO COOL DRY mode and roo...

Страница 11: ...ally after 1 hour JETSTREAM To set the timer To turn ON and OFF the unit at a preset time To enjoy freshness and cleaner environment This is a combination operation together with nanoeX and nanoe G na...

Страница 12: ...ow activity to maximise energy saving Mode Human Low activity COOL Set temperature ECONAVI take advantage of the human nature that human being takes time to feel the temperature rise during low activi...

Страница 13: ...native to remove moisture left in the internal parts thoroughly to prevent mould growth Turn off the power supply and unplug Remove the remote control batteries nanoe G Generator For better efficiency...

Страница 14: ...and some alpha numeric codes appear on IDU display Unit s Wi Fi connection with the router is activated Wi Fi LED stays ON during unit turn OFF Check unit s Wi Fi connection with router Wi Fi LED coun...

Страница 15: ...Note 15 English Troubleshooting...

Страница 16: ...e condenser is not obstructed There should not be any animal or plant which could be affected by hot air discharged Keep the spaces indicated by arrows from wall ceiling fence or other obstacles Do no...

Страница 17: ...and secure with vinyl tape Vinyl tape Insulation of piping connections Remote control holder Remote control holder xing screws Remote control Attaching the remote control holder to the wall 50 mm or m...

Страница 18: ...uld be about from this line 1 Mount the installation plate on the wall with 5 screws or more at least 5 screws If mounting the unit on the concrete wall consider using anchor bolts Always mount the in...

Страница 19: ...left piping Right Rear piping Cover for piping How to keep the cover In case of the cover is cut keep the cover at the rear of chassis as shown in the illustration for future reinstallation Left right...

Страница 20: ...n cable Gas side piping Liquid side piping Drain hose Insert the connection cable This can be used for left rear piping and bottom piping also How to pull the piping and drain hose out in case of the...

Страница 21: ...roprene sheathed 4 x 1 0 mm2 1 5 1 8HP 4 x 1 5 mm2 2 0HP or 4 x 2 5mm2 2 5HP exible cord type designation IS 694 or 60245 IEC 57 or heavier cord Bind all the indoor and outdoor connection cable with t...

Страница 22: ...n this area must follow to national wiring rules Do not joint wires Wire stripping No loose strand when inserted 10 1 mm Conductor fully inserted ACCEPT Conductor over inserted PROHIBITED Conductor no...

Страница 23: ...ated in the table Torque wrench Spanner or Wrench Decide piping length and then cut by using pipe cutter Remove burrs from cut edge Make are after inserting the are nut locate at valve onto the copper...

Страница 24: ...r unit and outdoor unit shall be approved polychloroprene sheathed 4 x 1 0 mm2 1 5 1 8HP 4 x 1 5 mm2 2 0HP or 4 x 2 5mm2 2 5HP exible cord type designation IS 694 or 60245 IEC 57 or heavier cord Do no...

Страница 25: ...wn in the illustration 3 Then remove the 2 1 5HP or 4 2 0 2 5HP mounting screws 4 Pull the lower section of the front grille towards you to remove the front grille The below operations will be perform...

Страница 26: ...insulating material with a new one Heat insulating material is required for both liquid side and gas side piping Most Important Process Purpose To make the oil refrigerant mix together They are in se...

Страница 27: ...n inside a building or dwelling or room must be made by brazing orwelding Joint connection of indoor unit by aring method can only be made at outdoor or at outside of a buidling or dwelling or room Fl...

Страница 28: ...b 17 C for Half Load 50 For Full Load QUIET CLEAN Open the Front Panel by lifting Intake Grille Follow the below Instructions 4 Air Swing Horizontal Airflow Set vane position to be AUTO 5 Fan speed M...

Страница 29: ...r Unit Control button while holding the indoor unit button Step b Within 5 second press once the Remote Step c After hearing a beep sound from the Indoor Unit immediately release the Auto OFF ON butto...

Страница 30: ...ranty for 3 years from the date of purchase Product ROOM AIR CONDITIONER Panasonic Life Solutions India Pvt Ltd Model No ODU SI No IDU SI No Customer Name Address Tel No Date of Purchase Invoice No De...

Страница 31: ...re eg Rat lizard insect ants etc inside the Product unit f Use of harmful chemicals Improper heat load Usage of unit in an abnormally corrosive alkaline acidic atmosphere g Any change or defect result...

Страница 32: ...m in corporate sustainability panasonic india i recycle program html S No 1 All electrical and electronic products are required to be handed over only to the Authorized recycler 2 The product should b...

Отзывы: