60
13.8 Powerful Operation
•
To achieve the setting temperature quickly.
•
When powerful operation is set, the setting temperature will be automatically decreased 3°C internally against
the present setting temperature (Lower temperature limit: 16°C).
•
This operation automatically running under Shi fan speed (Cooling), Lo- Fan Speed (Soft Dry) is applicable for
C9PK and C12PK only.
•
Vertical Airflow Direction:
o
In “Manual” setting, the vane will automatically shift down 10° lower than previous setting.
o
In “Auto” setting, the vane will automatically swing up and down. However the lower limit will be shifted 10°
downward.
•
Powerful operation stops when:
o
Powerful/Quiet button is pressed again
o
Powerful operation has operate for 15 minutes.
o
Stopped by OFF/ON operation button.
o
Timer OFF activates
o
Operation mode is changed
13.9 Quiet Operation
(For Cooling Operation or cooling region of Soft Dry Operation)
•
To provide quiet cooling operation condition.
•
Once the Quiet Operation is set at the remote control, the Quiet LED brightness will be dimmed. The sound level
will reduce around 2dB(A) for Lo fan speed or 3dB(A) for Hi/Me fan speed against the present operation sound
level.
•
Dew formation become severe at Quite Lo Cool, therefore Quiet Lo cool operated only for 1 hour 30 minutes
(1 hour QLo, 30 minutes QLo + 80rpm)(for C9PK and C12PK) and Quiet Lo cool operated only 1 hour
30 minutes (1 hour QLo, 30 minutes QLo + 50 rpm) (for C18PK, C24PK and C28PK).
•
Manual Airflow Direction:
o
RPM control during Lo cool
(For C9PK and C12PK)
(For C18PK, C24PK and C28PK)
Содержание CS-C12PKV
Страница 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Страница 13: ...13 5 Dimensions 5 1 Indoor Unit 5 1 1 CS C9PKV CS C12PKV ...
Страница 14: ...14 5 1 2 CS C18PKV CS C24PKV CS C28PKV ...
Страница 15: ...15 5 2 Outdoor Unit 5 2 1 CU C9PKV 5 2 2 CU C12PKV ...
Страница 16: ...16 5 2 3 CU C18PKV 5 2 4 CU C24PKV CU C28PKV ...
Страница 18: ...18 7 Block Diagram 7 1 1 CS C9PKV CU C9PKV CS C12PKV CU C12PKV ...
Страница 19: ...19 7 1 2 CS C18PKV CU C18PKV CS C24PKV CU C24PKV ...
Страница 20: ...20 7 1 3 CS C28PKV CU C28PKV ...
Страница 25: ...25 9 Electronic Circuit Diagram 9 1 CS C9PKV CU C9PKV CS C12PKV CU C12PKV ...
Страница 26: ...26 9 2 CS C18PKV CU C18PKV ...
Страница 27: ...27 9 3 CS C24PKV CU C24PKV ...
Страница 28: ...28 9 4 CS C28PKV CU C28PKV ...
Страница 29: ...29 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board 10 1 1 1 CS C9PKV CS C12PKV ...
Страница 31: ...31 10 1 4 Comparator Printed Circuit Board 10 1 5 Human Activity Sensor Printed Circuit Board ...
Страница 45: ...45 12 2 5 Wire Stripping And Connecting Requirement ...
Страница 51: ...51 13 1 2 Cooling Operation Time Diagram For CS C18PK CU C18PK CS C24PK CU C24PK and CS C28PK CU C28PK ...
Страница 53: ...53 13 2 2 Soft Dry Operation Time Diagram For CS C18PK CU C18PK CS C24PK CU C24PK and CS C28PK CU C28PK ...
Страница 81: ...81 Figure 3 Figure 4 17 1 1 3 To remove discharge grille Figure 5 ...
Страница 83: ...83 Figure 9 Figure 10 ...
Страница 87: ...87 Figure 20 Figure 21 ...
Страница 88: ...88 18 Technical Data 18 1 Thermostat Characteristics Cooling Soft Dry ...
Страница 114: ...114 Printed in Malaysia SZ0313 0 ...