13.15.1.7 Setting Position Judgment
•
According to installation position when there is only one activity area detected, the horizontal airflow direction
louver position is fixed according to chart below:
Horizontal airflow direction louver position
Target area
Left installation
Center installation
Right installation
A
3 2 2
B
1 1 1
C
5 5 4
•
Louver position refer to horizontal airflow direction control.
•
When 2 activity areas have been detected, according to Human Activity Level, the timing of horizontal airflow
direction louver steps at the targeted activity areas is judged.
Operation mode
Activity level difference
Louver stop time
1 level
Higher Activity level
≈
60 seconds
Lower Activity level
≈
30 seconds
Cooling
2 levels
Higher Activity level
≈
60 seconds
Lower Activity level
≈
8 seconds
•
When 3 activity areas have been detected, according to Human Activity Level the timing of horizontal airflow
louver steps at the targeted activity areas is judged.
Operation mode
Activity level
Louver stop time
Cooling
Hi
Me
Lo
≈
45 seconds
≈
30 seconds
≈
20 seconds
•
When 3 activity areas have same activity level, the horizontal airflow direction louver will swing left and right.
13.15.1.8 Setting Temperature and Fan Speed Shift
•
Cooling Dual Sensor
* During low activity, fan speed 1 tap up for first 15 minutes or until set temperature is reached.
** During human absence, maximum fan speed for COOL/DRY mode is medium fan.
Содержание CS-C12PKV
Страница 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Страница 13: ...13 5 Dimensions 5 1 Indoor Unit 5 1 1 CS C9PKV CS C12PKV ...
Страница 14: ...14 5 1 2 CS C18PKV CS C24PKV CS C28PKV ...
Страница 15: ...15 5 2 Outdoor Unit 5 2 1 CU C9PKV 5 2 2 CU C12PKV ...
Страница 16: ...16 5 2 3 CU C18PKV 5 2 4 CU C24PKV CU C28PKV ...
Страница 18: ...18 7 Block Diagram 7 1 1 CS C9PKV CU C9PKV CS C12PKV CU C12PKV ...
Страница 19: ...19 7 1 2 CS C18PKV CU C18PKV CS C24PKV CU C24PKV ...
Страница 20: ...20 7 1 3 CS C28PKV CU C28PKV ...
Страница 25: ...25 9 Electronic Circuit Diagram 9 1 CS C9PKV CU C9PKV CS C12PKV CU C12PKV ...
Страница 26: ...26 9 2 CS C18PKV CU C18PKV ...
Страница 27: ...27 9 3 CS C24PKV CU C24PKV ...
Страница 28: ...28 9 4 CS C28PKV CU C28PKV ...
Страница 29: ...29 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board 10 1 1 1 CS C9PKV CS C12PKV ...
Страница 31: ...31 10 1 4 Comparator Printed Circuit Board 10 1 5 Human Activity Sensor Printed Circuit Board ...
Страница 45: ...45 12 2 5 Wire Stripping And Connecting Requirement ...
Страница 51: ...51 13 1 2 Cooling Operation Time Diagram For CS C18PK CU C18PK CS C24PK CU C24PK and CS C28PK CU C28PK ...
Страница 53: ...53 13 2 2 Soft Dry Operation Time Diagram For CS C18PK CU C18PK CS C24PK CU C24PK and CS C28PK CU C28PK ...
Страница 81: ...81 Figure 3 Figure 4 17 1 1 3 To remove discharge grille Figure 5 ...
Страница 83: ...83 Figure 9 Figure 10 ...
Страница 87: ...87 Figure 20 Figure 21 ...
Страница 88: ...88 18 Technical Data 18 1 Thermostat Characteristics Cooling Soft Dry ...
Страница 114: ...114 Printed in Malaysia SZ0313 0 ...