14. Protection
Control
14.1 Restart Control (Time Delay Safety Control)
•
When the thermo-off temperature (temperature which compressor stops to operate) is reach during:-
o
Cooling operation – the compressor stops for 3 minutes (minimum) before resume operation.
o
Soft Dry operation – the compressor stops for 6 minutes (minimum) before resume operation.
•
If the operation is stopped by the remote control, the compressor will not turn on within 3 minutes from the
moment operation stop, although the unit is turn on again within the period.
•
This phenomenon is to balance the pressure inside the refrigerant cycle.
14.2 7 Minutes Time Save Control
•
The compressor will start automatically if it has stopped for 7 minutes and the intake air temperature falls
between the compressor ON temperature (A) and compressor OFF temperature (B) during the period.
•
This phenomenon is to reduce the built up humidity inside a room.
14.3 60 Seconds Forced Operation
•
Once the air conditioner is turned on, the compressor will not stop within 60 seconds in a normal operation
although the intake air temperature has reached the thermo-off temperature. However, forced stop by pressing
the OFF/ON operation button at the remote control is permitted.
•
The reason for the compressor to force operate at the minimum 60 seconds is to allow the refrigerant oil run in a
full cycle and return back to the outdoor unit.
14.4 Starting Current Control
•
When the compressor, outdoor fan motor and indoor fan motor are simultaneously started, the indoor fan motor
will start to operate at 1.6 seconds later.
•
The reason of the difference is to reduce the starting current flow.
Содержание CS-C12PKV
Страница 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Страница 13: ...13 5 Dimensions 5 1 Indoor Unit 5 1 1 CS C9PKV CS C12PKV ...
Страница 14: ...14 5 1 2 CS C18PKV CS C24PKV CS C28PKV ...
Страница 15: ...15 5 2 Outdoor Unit 5 2 1 CU C9PKV 5 2 2 CU C12PKV ...
Страница 16: ...16 5 2 3 CU C18PKV 5 2 4 CU C24PKV CU C28PKV ...
Страница 18: ...18 7 Block Diagram 7 1 1 CS C9PKV CU C9PKV CS C12PKV CU C12PKV ...
Страница 19: ...19 7 1 2 CS C18PKV CU C18PKV CS C24PKV CU C24PKV ...
Страница 20: ...20 7 1 3 CS C28PKV CU C28PKV ...
Страница 25: ...25 9 Electronic Circuit Diagram 9 1 CS C9PKV CU C9PKV CS C12PKV CU C12PKV ...
Страница 26: ...26 9 2 CS C18PKV CU C18PKV ...
Страница 27: ...27 9 3 CS C24PKV CU C24PKV ...
Страница 28: ...28 9 4 CS C28PKV CU C28PKV ...
Страница 29: ...29 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board 10 1 1 1 CS C9PKV CS C12PKV ...
Страница 31: ...31 10 1 4 Comparator Printed Circuit Board 10 1 5 Human Activity Sensor Printed Circuit Board ...
Страница 45: ...45 12 2 5 Wire Stripping And Connecting Requirement ...
Страница 51: ...51 13 1 2 Cooling Operation Time Diagram For CS C18PK CU C18PK CS C24PK CU C24PK and CS C28PK CU C28PK ...
Страница 53: ...53 13 2 2 Soft Dry Operation Time Diagram For CS C18PK CU C18PK CS C24PK CU C24PK and CS C28PK CU C28PK ...
Страница 81: ...81 Figure 3 Figure 4 17 1 1 3 To remove discharge grille Figure 5 ...
Страница 83: ...83 Figure 9 Figure 10 ...
Страница 87: ...87 Figure 20 Figure 21 ...
Страница 88: ...88 18 Technical Data 18 1 Thermostat Characteristics Cooling Soft Dry ...
Страница 114: ...114 Printed in Malaysia SZ0313 0 ...