52
13.2 Soft Dry Operation
•
Soft Dry operation can be set using remote control.
•
Soft Dry operation is applied to dehumidify and to perform a gentle cooling to the room.
•
This operation starts when the intake air temperature sensor reaches the setting temperature on the remote
control.
•
When operation begins, Soft Dry will be switched “ON” for a maximum 10 minutes, then Soft Dry operation will be
turn “OFF” for a minimum 6 minutes. After that, the Soft Dry operation will be “ON” and “OFF” based on the
setting temperature as shown in figure below.
•
However after 3 minutes of compressor off, during Soft Dry “OFF” (within 6 minutes Soft Dry restart control), the
indoor unit will start to operate at normal Cooling mode if the intake temperature is higher than Cooling “ON”
point.
13.2.1 Soft Dry Operation Time Diagram (For CS-C9PK CU-C9PK and CS-C12PK
CU-C12PK)
Содержание CS-C12PKV
Страница 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Страница 13: ...13 5 Dimensions 5 1 Indoor Unit 5 1 1 CS C9PKV CS C12PKV ...
Страница 14: ...14 5 1 2 CS C18PKV CS C24PKV CS C28PKV ...
Страница 15: ...15 5 2 Outdoor Unit 5 2 1 CU C9PKV 5 2 2 CU C12PKV ...
Страница 16: ...16 5 2 3 CU C18PKV 5 2 4 CU C24PKV CU C28PKV ...
Страница 18: ...18 7 Block Diagram 7 1 1 CS C9PKV CU C9PKV CS C12PKV CU C12PKV ...
Страница 19: ...19 7 1 2 CS C18PKV CU C18PKV CS C24PKV CU C24PKV ...
Страница 20: ...20 7 1 3 CS C28PKV CU C28PKV ...
Страница 25: ...25 9 Electronic Circuit Diagram 9 1 CS C9PKV CU C9PKV CS C12PKV CU C12PKV ...
Страница 26: ...26 9 2 CS C18PKV CU C18PKV ...
Страница 27: ...27 9 3 CS C24PKV CU C24PKV ...
Страница 28: ...28 9 4 CS C28PKV CU C28PKV ...
Страница 29: ...29 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board 10 1 1 1 CS C9PKV CS C12PKV ...
Страница 31: ...31 10 1 4 Comparator Printed Circuit Board 10 1 5 Human Activity Sensor Printed Circuit Board ...
Страница 45: ...45 12 2 5 Wire Stripping And Connecting Requirement ...
Страница 51: ...51 13 1 2 Cooling Operation Time Diagram For CS C18PK CU C18PK CS C24PK CU C24PK and CS C28PK CU C28PK ...
Страница 53: ...53 13 2 2 Soft Dry Operation Time Diagram For CS C18PK CU C18PK CS C24PK CU C24PK and CS C28PK CU C28PK ...
Страница 81: ...81 Figure 3 Figure 4 17 1 1 3 To remove discharge grille Figure 5 ...
Страница 83: ...83 Figure 9 Figure 10 ...
Страница 87: ...87 Figure 20 Figure 21 ...
Страница 88: ...88 18 Technical Data 18 1 Thermostat Characteristics Cooling Soft Dry ...
Страница 114: ...114 Printed in Malaysia SZ0313 0 ...