11.1. Evacuation of Installation
Required tools:
hexagonal wrench, adjustable wrench,
torque wrenches, wrench to hold the
joints, gas leak detector, and charging
set.
1.
Connect a charging hose with a push pin to the Low
and High sides of a charging set and the service ports
of a 3-way valve.
•
Be sure to connect the end of the charging hose with the
push pin to the service port.
2.
Connect the centre hose of the charging set to a
vacuum pump.
3.
Turn on the power switch of the vacuum pump and
make sure that the needle in the gauge moves from 0
cmHg (0 MPa) to -76 cmHg (-0.1 MPa). Then evacuate
the air for approximately 10 minutes.
4.
Close the valve of both the Low and High sides of the
charging set and turn off the vacuum pump. Make sure
that the needle in the gauge does not move after
approximately 5 minutes.
BE SURE TO TAKE THIS PROCEDURE IN ORDER TO
AVOID REFRIGERANT GAS LEAKAGE.
5.
Disconnect the charging hose from the vacuum pump
and from the service port of the 3-way valve.
The air in the indoor unit and in the piping must be purged. If air
remains
in
the
refrigeration
pipings,
it
will
affect
the
compressor, reduce the cooling capacity, and could lead to a
malfunction.
6.
Tighten the service port caps of both the 3-way valves
at a torque of 18 N.m with a torque wrench.
7.
Remove the valve caps of the 3-way valves. Position
both of the valves to “open” using a hexagonal wrench
(4 mm).
8.
Mount the valve caps onto both of the 3-way valves.
•
Be sure to check for gas leakage.
Caution
If gauge needle does not move from 0 cmHg (0 MPa)
to -76 cmHg (-0.1 MPa) in step (3) above, take the
following measures:
If the leaks stop when the piping connections are
tightened further, continue working from step (3).
If the leaks do not stop when the connections are
retightened, repair the location of the leak.
When installing an air conditioner, be sure to evacuate the air inside the indoor unit and pipes in the following procedure.
Service port cap
Be sure, using a torque wrench to tighten the service port cap (after using the service port), so that it prevents the gas leakage from the
refrigeration cycle
Procedure:
52
CS-A28
BKP5/CU-A28BKP5
Содержание CS-A28BKP5
Страница 8: ...4 Dimensions 8 CS A28BKP5 CU A28BKP5 CS A28BKP5 CU A28BKP5 ...
Страница 10: ...6 Block Diagram 10 CS A28BKP5 CU A28BKP5 CS A28BKP5 CU A28BKP5 ...
Страница 11: ...7 Wiring Diagram 11 CS A28BKP5 CU A28BKP5 CS A28BKP5 CU A28BKP5 ...
Страница 15: ...Soft Dry Operation Time Diagram 15 CS A28BKP5 CU A28BKP5 ...
Страница 46: ... This can be used for left rear piping and left bottom piping also 46 CS A28BKP5 CU A28BKP5 ...
Страница 64: ...14 Technical Data 64 CS A28BKP5 CS A28BKP5 CU A28BKP5 ...
Страница 65: ...65 CS A28BKP5 CU A28BKP5 CS A28BKP5 CU A28BKP5 ...
Страница 66: ...66 CS A28BKP5 CU A28BKP5 CS A28BKP5 CU A28BKP5 ...
Страница 67: ...15 Exploded View 67 CS A28BKP5 CS A28BKP5 CU A28BKP5 ...
Страница 69: ...17 ExplodedView 69 CU A28BKP5 CS A28BKP5 CU A28BKP5 ...
Страница 72: ...20 Electronic Circuit Diagram CS A28BKP5 CU A28BKP5 SCHEMATIC DIAGRAM 1 3 72 CS A28BKP5 CU A28BKP5 ...
Страница 73: ...SCHEMATIC DIAGRAM 2 3 73 CS A28BKP5 CU A28BKP5 ...
Страница 74: ...SCHEMATIC DIAGRAM 3 3 74 CS A28BKP5 CU A28BKP5 ...
Страница 75: ...75 CS A28BKP5 CU A28BKP5 ...
Страница 77: ...20 1 REMOTE CONTROL 77 Printed in Taiwan CS A28BKP5 CU A28BKP5 ...