11.1. Evacuation of Installation

Required tools:

hexagonal wrench, adjustable wrench,
torque wrenches, wrench to hold the
joints, gas leak detector, and charging
set.

 1. 

Connect a charging hose with a push pin to the Low
and High sides of a charging set and the service ports
of a 3-way valve.

  • 

Be sure to connect the end of the charging hose with the
push pin to the service port.

 2. 

Connect the centre hose of the charging set to a
vacuum pump.

 3. 

Turn on the power switch of the vacuum pump and
make sure that the needle in the gauge moves from 0
cmHg (0 MPa) to -76 cmHg (-0.1 MPa). Then evacuate
the air for approximately 10 minutes.

 4. 

Close the valve of both the Low and High sides of the
charging set and turn off the vacuum pump. Make sure
that the needle in the gauge does not move after
approximately 5 minutes.
BE SURE TO TAKE THIS PROCEDURE IN ORDER TO
AVOID REFRIGERANT GAS LEAKAGE.

 5. 

Disconnect the charging hose from the vacuum pump
and from the service port of the 3-way valve.

The air in the indoor unit and in the piping must be purged. If air
remains

in

the

refrigeration

pipings,

it

will

affect

the

compressor, reduce the cooling capacity, and could lead to a
malfunction.

 6. 

Tighten the service port caps of both the 3-way valves
at a torque of 18 N.m with a torque wrench.

 7. 

Remove the valve caps of the 3-way valves. Position
both of the valves to “open” using a hexagonal wrench
(4 mm).

 8. 

Mount the valve caps onto both of the 3-way valves.

  • 

Be sure to check for gas leakage.

Caution

If gauge needle does not move from 0 cmHg (0 MPa)
to -76 cmHg (-0.1 MPa) in step (3) above, take the
following measures:

If the leaks stop when the piping connections are
tightened further, continue working from step (3).

If the leaks do not stop when the connections are
retightened, repair the location of the leak.

When installing an air conditioner, be sure to evacuate the air inside the indoor unit and pipes in the following procedure.

Service port cap
Be sure, using a torque wrench to tighten the service port cap (after using the service port), so that it prevents the gas leakage from the
refrigeration cycle

Procedure:

52

CS-A28

BKP5/CU-A28BKP5

Содержание CS-A28BKP5

Страница 1: ...ditioning Corp Sdn Bhd 183914D All rights reserved Unauthorized copying and distribution is a violation of law CS A28BKP5 CU A28BKP5 11 3 way Valve 51 12 Servicing Information 58 13 Troubleshooting Guide 62 14 Technical Data 64 15 Exploded View 67 16 Replacement Parts List 68 17 Exploded View 69 18 Replacement Parts List 70 19 Electronic Parts List 71 20 Electronic Circuit Diagram 72 Room Air Cond...

Страница 2: ... Efficiency Airflow Circuit Compact Design Auto Restart after Power Failure Long Piping up to 30m Catechin Deodorizing Air Filter Deodorizing Control during operation Cold draught Control 1 Features 2 CS A28BKP5 CU A28BKP5 ...

Страница 3: ...ime Timer Setting Hours and minutes setting Clock Setting Current time setting Sleep Mode Operation OFF ON SLEEP Indoor Fan Speed Selection FAN SPEED h j k Low Speed l h j k Medium Speed lll h j k High Speed lllll AUTOFAN Automatic Fan Speed Airflow Direction Control 24 hour OFF ON Real Timer Setting ON TIMER OFF TIMER Timer Operation Selection SET CANCEL Timer Operation Set Cancel ON Timer and OF...

Страница 4: ...stops until the indoor heat exchanger temperature over 30 C The indoor fan operates at SLo and Lo when indoor heat exchanger temperature reaches 30 C 42 C Hot start is completed when indoor heat exchanger reaches 42 C Auto Operation Switch Used when the remote control cannot be used AUTO OFF ON Remote Control Signal Receiving Sound Control It can be controlled by pressing Auto Operation Switch for...

Страница 5: ...ed For Cooling or Soft Dry Operation Hi speed when outdoor temperature reaches to 31 C Lo speed when outdoor temperature reaches to 29 C For Heating Operation Hi speed when outdoor temperature reaches to 13 5 C Lo speed when outdoor temperature reaches to 15 5 C For Over heating Protection the Fan is switched ON or OFF depending on the piping temperature and the outdoor temperature Overload Protec...

Страница 6: ...m Cooling 16 3 575 Heating 17 7 625 Outdoor Air m3 min cfm Cooling 59 0 2 083 Heating 59 2 2 090 Noise Level dB A Cooling 48 46 44 Cooling 63 55 Heating 48 44 Heating 63 55 Electrical Data Input kW Cooling 2 62 2 60 Heating 2 88 2 85 Running Current A Cooling 12 2 12 5 Heating 13 2 13 5 COP W W Cooling 3 0 3 0 Heating 2 9 2 9 Starting Current A 76 Piping Connection Port Flare piping inch inch G Ha...

Страница 7: ...er Description Evaporator Condenser Tube material Copper Copper Fin material Aluminium Aluminium Fin Type Louver Louver Row Stage Plate fin configuration forced draft 2 10 2 26 FPI 18 18 Size W H L mm 966 5 254 44 826 663 9 44 Refrigerant Control Device Capillary Tube Refrigeration Oil cm3 SONTEX 200 LT 1 242 Refrigerant R 22 g oz 1 800 63 5 Thermostat Electronic Control Electronic Control Protect...

Страница 8: ...4 Dimensions 8 CS A28BKP5 CU A28BKP5 CS A28BKP5 CU A28BKP5 ...

Страница 9: ...CS A28BKP5 CU A28BKP5 5 Refrigeration Cycle Diagram 9 CS A28BKP5 CU A28BKP5 Dimensions CS A28BKP5 CU A28BKP5 CS A28BKP5 CU A28BKP5 ...

Страница 10: ...6 Block Diagram 10 CS A28BKP5 CU A28BKP5 CS A28BKP5 CU A28BKP5 ...

Страница 11: ...7 Wiring Diagram 11 CS A28BKP5 CU A28BKP5 CS A28BKP5 CU A28BKP5 ...

Страница 12: ... 10 C Recovery 3 minutes waiting of Time Delay Safety Control is valid for Cooling Operation 8 Operation Details 8 1 Cooling Mode Operation When the compressor is stopped by Power Switch Remote Control or there is a power failure it restarts after 3 minutes when the Power Switch Remote Control is turned ON or the power supply is resumed When the setting temperature is reached during cooling operat...

Страница 13: ...an Speed Mode Cooling Operation Time Diagram When Automatic Fan Speed is selected at Remote Control during cooling operation Fan speed rotates in the range of Hi to Me Deodorizing Control 13 CS A28BKP5 CU A28BKP5 ...

Страница 14: ...rates with Lo speed Once room temperature reaches below Soft Dry OFF temperature Indoor Fan Compressor and Outdoor Fan Stop for 6 minutes Once the compressor stops it will not start for 3 minutes during Cooling operation Same as Anti Freezing Control for Cooling Mode operation For Soft Dry region 6 minutes waiting is valid during compressor stops When Automatic Fan Speed is selected at Remote Cont...

Страница 15: ...Soft Dry Operation Time Diagram 15 CS A28BKP5 CU A28BKP5 ...

Страница 16: ...inutes The compressor will start automatically if it has stopped for 30 minutes even if the room temperature is below the compressor OFF temperature If the temperature of the Outdoor Heat Exchanger less than 3 C Outdoor Fan is ON The Outdoor Fan stop when Outdoor Heat Exchanger temperature is Tb or more according to Outdoor Air Temperature region as table below During starting of Heating mode and ...

Страница 17: ...de Heating Operating Time Diagram When Automatic Fan Speed is selected at Remote Control during heating operation Fan speed rotates in the range of Hi SLo according to the heat exchanger temperature 17 CS A28BKP5 CU A28BKP5 ...

Страница 18: ... is in operation deice will start There is no detection during Outdoor Fan stops Overload Deicing During heating operation if the outdoor Fan OFF duration due to overload control is accumulated up to 60 minutes and after compressor starts for 1 minute deicing starts Deicing ends when a 12 minutes after deicing operation starts b The outdoor piping temperature rises to about 12 C After deicing oper...

Страница 19: ...temperature does not reach to set temperature Compressor keeps running eventhough after 1 hour from automatic operation mode started For 2nd judgement onwards indoor fan will operate for 20 seconds to sense the intake air temperature for determining operation mode Standard for Determining Operation Mode 2nd Judgement onwards Present Judgement Next Mode Mode Cooling Soft Dry Heating O O Cooling 23 ...

Страница 20: ...ority 8 5 Sleep Mode Auto Operation 8 6 Auto Restart Control If there is a power failure operation will be automatically restarted when the power is resumed It will start with previous operation mode and airflow direction Time Delay Safety Control is valid Auto Restart Control is not available when Timer or Sleep Mode is set This control can be omitted by cutting the jumper wire J2 Refer Circuit D...

Страница 21: ...utton at the desired louver position When the remote control is used to stop the operation the discharge vent is closed with airflow direction louver The left and right airflow direction louvers can be adjusted manually 8 8 Airflow Direction Control 8 9 Delay ON Timer Control When the Delayed ON Timer is set by using the remote control the unit will start operate slightly before the set time so th...

Страница 22: ...wing symbols Installation precautions Before operating please read the following Safety Precautions carefully This room air conditioner must be earthed Improper grounding could cause electric shock Do not install the unit in a place where there may be explosive gas leaks Gas leaks near the unit could cause fires Ensure that drainage piping is connected properly Otherwise water will leak out This s...

Страница 23: ...o not operate the unit with wet hands It could cause an electric shock If there is a smell of burning stop the air conditioner and disconnect the power supply The heat generated could cause electric shock or fire Please con sult an authorized dealer or serv ice centre Do not damage or use an unspecified power cord It will cause electrical shock or fire Do not insert finger sticks or other objects ...

Страница 24: ...old the plug when disconnect ing the plug from the wall outlet Do not use for other pur poses Do not use for preservation pur poses It will affect food quality animals or plants Do not wash the unit with water It could cause an electric shock When cleaning the unit re move the plug This is to prevent injury due to the rotating fan in the unit Ventilate the room regularly If not ventilated regularl...

Страница 25: ...ke Vents Air Outlet Vents Drain Hose Piping Ground Terminal Inside Cover Front Panel Air Intake Vent Air Outlet Vent Panel Opener Horizontal Airflow Direction Louver Manually adjusted Vertical Airflow Direction Louver Signal Receptor Power Sleep Timer Red Orange Orange 25 CS A28BKP5 CU A28BKP5 ...

Страница 26: ...Setting Button Sleep Mode Operation Button Operation Display Door Airflow Direction Manual Control Button Signal Transmitter Operation Mode Selection Button Airflow Direction Auto Control Button OFF Timer Button ON Timer Button Set Button Cancellation Button Time Button q OFF TIMER ON TIMER CANCEL SET TIME Door OFF ON Button Airflow Volume Selection Button O F F O N S L E E P P M M O D E T E M P F...

Страница 27: ...up the front panel Air filter Connect the power supply cord to an independent power supply 1 Air purifying filter Be careful not to hurt your hands by metal parts Note Use under the following conditions Unit in C DBT Dry Bulb Temperature WBT Wet Bulb Temperature Maximum Temperature Minimum Temperature Cooling Indoor Outdoor DBT WBT DBT WBT 32 23 43 26 16 11 16 11 Heating Indoor Outdoor DBT WBT DBT...

Страница 28: ...atteries because such batteries differ from standard dry cell batteries in shape dimensions and performance Be sure to replace the batteries with two new batteries of the same type Do not dispose of empty batteries in household waste Take them to special local collection sites Make sure that the signal path is not obstructed The maximum dis tance at which signals can be received is about 10 m 12 1...

Страница 29: ...Mode is set Auto Restart Control How to Operate For Heating 20 C 24 C For Cooling 26 C 28 C For Soft Dry 1 C 02 C lower than room temperature OFF ON AUTO FAN SLEEP MODE TEMP FANSPEED MANUAL SWING AIRSWING AUTO m Cooling Operation until room tem perature reaches the setting temper ature When room temperature reaches the setting tempera ture operation will switch to Soft Dry Setting Temperature Supe...

Страница 30: ...er than standard OFF ON I FAN SPEED MODE i TEMP MANUAL SWING Press to select operation mode The display changes in the order each time the button is pressed Press to start the operation Operation indication lamp RED will light up Press once more to stop the operation Press to select airflow volume The display changes in the order Automatic Low Medium High Press to select room temperature Heating C...

Страница 31: ...en two air conditioners units have been installed in one room Please consult your dealer RESET points Setting the Timer B A switch If there is a power failure OFF TIMER SET To reset the Timer Example If the OFF Timer has been set Even if there is a power failure the setting time is still stored in the memory because the re mote control is a battery operated type q OFF ON SLEEP PM OFF TIMER TIME ON...

Страница 32: ...ase 10 minutes each step to decrease 10 minutes each step TIME OFF TIMER q SET 0N TIMER SET OFF TIMER CANCEL SET 0N TIMER Cooling and Soft Dry 15 minutes before Heating and Automatic 30 minutes before TIME to advance the time to reverse the time q To set the current time Set hours and minutes To set the Timer OFF Timer Set hours and minutes The OFF TIMER will blink ON Timer Set hours and minutes T...

Страница 33: ...l switch off SLEEP SLEEP OFF ON SLEEP PM MODE TEMP FANSPEED MANUAL SWING AIRSWING AUTO C 1 1 3 0 c 27 h j k 0 1 hour 1 hour TEMP SETTING TEMPERATURE TIME Approx 0 5 C increase Approx 0 5 C increase SETTING TEMPERATURE TEMP 0 1 hour 1 hour TIME Approx 2 C decrease Approx 3 C decrease Heating Operation for Sleep Mode move ment will start to avoid overheating Information Cooling or Soft Dry Operation...

Страница 34: ...l Signal receiving sound can be omitted as desired To switch OFF the signal receiving sound press Auto Operation Button for 10 seconds or more At the same time Automatic Operation starts To switch ON press Auto Operation Button once more for 10 seconds or more Press Auto Operation Button The operation indication lamp will blink for 20 seconds and then light up If the button is pressed once more th...

Страница 35: ...the Timer Use Timer when sleeping or going out to save electricity cost Clean the air filter regularly Blockage in the air filter reduces the airflow and lowers the cooling or heating Clean at least once every 2 weeks Otherwise about 6 of electricity cost will be wasted Do not block the air outlet vents at outdoor unit Otherwise it will lower the cooling or heating performance 1 C higher 2 C lower...

Страница 36: ...ers horizontal for Cool ing Operation and downwards for Heating Operation Operation result will be better Keep blinds or curtains closed Do not let sun shine enter the room directly About 5 of electricity cost can be saved Use insulating material for better performance Use insulating material during construction or renovations It will save electricity cost Cooling H e a t i n g 36 CS A28BKP5 CU A2...

Страница 37: ...g forward Purchase replacement filters from your air con ditioner dealer if the air filters become damage Air Filter No CWD4209540 right Cleaning the air conditioner and air filters Better Care and Maintenance Do not use water or volatile liquids Do not make air conditioner wet as there is the danger that it could cause electric shocks Be sure not to apply water when cleaning or at any other time ...

Страница 38: ...ernal mechanisms Operate the air condi tioner for 2 to 3 hours Type of operation Cooling Temperature setting 30 C When not using the air conditioner for a long period Pre season inspection The earlier the better Replacement of air purifying filters Note Solar Refreshing Deodorizing Filter Used to remove unpleasant odour and deodorize the air in the room Reusable Vacuum place under direct sunlight ...

Страница 39: ...will cause an undesired cooling effect In order to prevent this the airflow will not begin until it is sufficiently warm The operation lamp will blink until the airflow begins This may be a damp smell exuded by the walls carpet furniture or clothing in the room Condensation occurs when the airflow from the air conditioner cools the room air This is to remove the smell exuded by the surroundings Th...

Страница 40: ... immediately Abnormal noise is heard during operation Water or foreign material gets into the remote con trol by mistake Water leaks from the indoor unit If the following conditions occur immediately turn the power plug or turn off the power breaker Switches or buttons do not operate properly The circuit breaker switch es off frequently Power supply cord and plug become unusually warm Has the circ...

Страница 41: ...rown Live If the colours of the wires in the main lead of this appliance do not correspond with the coloured markings indentifying the terminals in your plug proceed as follows The green and yellow wire must be connected to the terminal in the plug which is marked with letter E or by the earth symbol or coloured green or green and yellow The blue wire must be connected to the terminal which is mar...

Страница 42: ... according to this installation instruction strictly If installation is defective it will cause water leakage electrical shock or fire 3 Use the attached accessories parts and specified parts for installation Otherwise it will cause the set to fall water leakage fire or electrical shock 4 Install at a strong and firm location which is able to withstand the set s weight If the strength is not enoug...

Страница 43: ...e power disconnection in case of emergency In some countries permanent connection of this room air conditioner to the power supply is prohibited 1 Power supply connection to the receptacle using a power plug Use an approved 20A power plug with earth pin for the connection to the receptacle 2 Power supply connection to a circuit breaker for the permanent connection Use an approved circuit breaker a...

Страница 44: ...heat radiation from the condenser is not obstructed There should not be any animal or plant which could be affected by hot discharged air Keep the spaces indicated by arrows from wall ceiling fence or other obstacles Do not place any obstacles which may cause a short circuit of the discharged air If piping length is over 10 m additional refrigerant should be added as shown in the table Piping leng...

Страница 45: ...and using a level gauge 2 Drill the piping plate hole with ø70 mm hole core drill Line according to the arrows marked on the lower left and right side of the installation plate The meeting point of the extended line is the centre of the hole Drill the piping hole at either the right or the left and the hole should be slightly slant to the outdoor side 10 2 3 TO DRILL A HOLE IN THE WALL AND INSTALL...

Страница 46: ... This can be used for left rear piping and left bottom piping also 46 CS A28BKP5 CU A28BKP5 ...

Страница 47: ...it and outdoor unit shall be approved polychorprene sheathed 5 2 5 mm2 flexible cord 245 IEC 57 type designation H05 RN F or heavier cord Secure the cable onto the control board with the holder clamper INSTALLATION OF AIR PURIFYING FILTERS 1 Open the front panel 2 Remove the air filters 3 Hold the catechin filters by their tabs and install as shown in the illustration at below 47 CS A28BKP5 CU A28...

Страница 48: ...l box sub of the indoor unit 10 3 OUTDOOR UNIT 10 3 1 SELECT THE BEST LOCATION Refer to Select the best location section 10 3 2 INSTALL THE OUTDOOR UNIT After selecting the best location start installation according to Indoor Outdoor Unit Installation Diagram 1 Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut ø10 mm 2 When installing at roof please consider strong wind a...

Страница 49: ...4 Close the valve of both the Low and High sides of the charging set and turn off the vacuum pump Make sure that the needle in the gauge does not move after approximately five minutes Note BE SURE TO TAKE THIS PROCEDURE IN ORDER TO AVOID REFRIGERANT GAS LEAKAGE 5 Disconnect the charging hose from the vacuum pump and from the service port of the 3 way valve 6 Tighten the service port caps of the 3 ...

Страница 50: ...drain water freezes and the fan will not rotate EVALUATION OF THE PERFORMANCE 1 Operate the unit at cooling operation mode for fifteen minutes or more 2 Measure the temperature of the intake and discharge air 3 Ensure the difference between the intake temperature and the discharge is more than 8 C CHECK ITEMS Is there any gas leakage at flare nut connections Has the heat insulation been carried ou...

Страница 51: ...n Closed Closed Open Open Transferring Clockwise With cap Counter Clockwise Connected manifold gauge Evacuation Open Open Open Open Servicing Counter Clockwise Connected manifold Counter Clockwise Connected manifold gauge gauge Gas charging Open Open Open Open Servicing Counter Clockwise Connected manifold Counter Clockwise Connected manifold gauge gauge Pressure check Open Open Open Open Servicin...

Страница 52: ...of the 3 way valve The air in the indoor unit and in the piping must be purged If air remains in the refrigeration pipings it will affect the compressor reduce the cooling capacity and could lead to a malfunction 6 Tighten the service port caps of both the 3 way valves at a torque of 18 N m with a torque wrench 7 Remove the valve caps of the 3 way valves Position both of the valves to open using a...

Страница 53: ...e close position 6 Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 0 kg cm2 G 0 MPa If the unit cannot be operated at the cool condition weather is rather cool press the Pump Down Switch on the Indoor unit So that the unit can be operated 7 Immediately set the gas side 3 way valve to the close position Do this quickly so that the gauge ends up indicating 1 to ...

Страница 54: ...cuum pump 6 Charge the pipes and indoor unit with gas refrigerant from liquid High side 3 way valve service port and then discharge the refrigerant until gas Low side gauge needle indicates 3 kg cm2 0 3 MPa If air remain in the indoor unit and refrigeration pipes it will affect the compressor reduce to cooling capacity and could lead to a malfunction BE SURE TO USE REFRIGERANT RECLAIMING EQUIPMENT...

Страница 55: ...1 kg cm2 G 3 Connect the charge set s centre hose to refrigerant reclaiming equipment 4 Open the valve Low side on the charge set and loosen the hose connected with the Refrigerant Reclaiming Equipment to purge the air from the hose 5 Turn on refrigerant reclaiming equipment to collect the refrigerant until the needle indicates 0 no refrigerant is remaining 11 4 Balance refrigerant of the 3 way va...

Страница 56: ... for approximately 1 hour vacuum of 4 mmHg or less 3 Close the valve Low side and High side on the charge set turn off the vacuum pump and confirm that the gauge needle does not move approximately 5 minutes after the vacuum pump is turned off 4 Disconnect the charge hose from the vacuum pump 11 5 Evacuation No refrigerant in the refrigeration cycle Procedure 56 CS A28BKP5 CU A28BKP5 ...

Страница 57: ...ure to open only the High side valve on the charge set to charge the system from the liquid side high presure pipe If the system cannot be charged with the specified amount of refrigerant operate the compressor until the specified amount can be charged and then close the valve at the bottom of the charge cylinder 4 Immediately disconnect the charge hose from both the 3 way valve service ports 5 Mo...

Страница 58: ...nnector CN STM of stepping motor from the electronic controller Release the earth wire YELLOW GREEN from the control board terminal and sensors from its holders Refer 2 Remove the Control Board As shown in remove the 5 screws Pull the control board forward slightly Caution Remove of Discharge Grille before removing the control board is necessary to avoid damaging other parts Fig 1 Fig 2 Fig 3 12 S...

Страница 59: ...rille in a down and forward direction 4 Remove the Indoor Fan Motor Loosen the Fan Mounting Screw at the junction with Cross Flow Fan Loosen the screw at the left side of the evaporator Pull off the Bearing at the left of the Cross Flow Fan Fig 4 Fig 5 Fig 6 Fig 7 59 CS A28BKP5 CU A28BKP5 ...

Страница 60: ...porator 2 Pull the left side of the evaporator forward slightly and remove the cross Flow Fan B Disassembly of the parts Outdoor Unit Inspection points for the Outdoor Electronic Controller 1 The Electronic Controller Can be seen by removing the cabinet Top plate and Front plate as shown in the Fig 8 Fig 9 Fig 10 60 CS A28BKP5 CU A28BKP5 ...

Страница 61: ...de When two indoor units are installed in the same room in order to prevent operating errors caused by using two remote controls set up the remote control B A switch SW1 The unit is set to A when it is shipped By adding a jumper wire to the remote control side and CUTTING J RA J RB to the indoor printed circuit board it is possible to select from 4 types of transmission codes including one at time...

Страница 62: ...de insufficient insulation problem with the power source malfunction of a compressor and a fan The normal outlet air temperature and pressure of the refrigeration cycle depends on various conditions the standard values for them are shown in the table to the right 13 Troubleshooting Guide 13 1 Refrigeration cycle system 62 CS A28BKP5 CU A28BKP5 ...

Страница 63: ...on of a compressor and 4 way valve Nature of fault Symptom Electric current during operation becomes approximately 20 lower than the normal value Insufficient compressing of a compressor The discharge tube of the compressor becomes abnormally hot normally 70 to 90 C The difference between high pressure and low pressure becomes almost zero Electric current reaches a high level abnormally and the va...

Страница 64: ...14 Technical Data 64 CS A28BKP5 CS A28BKP5 CU A28BKP5 ...

Страница 65: ...65 CS A28BKP5 CU A28BKP5 CS A28BKP5 CU A28BKP5 ...

Страница 66: ...66 CS A28BKP5 CU A28BKP5 CS A28BKP5 CU A28BKP5 ...

Страница 67: ...15 Exploded View 67 CS A28BKP5 CS A28BKP5 CU A28BKP5 ...

Страница 68: ... CWC3919 420A 24 TERMINAL BOARD ASS Y 1 CWC4706 600 25 1 27 TERMINAL BOARD COMPLETE 1 CWC4706 620 28 SENSOR COMPLETE 1 CWC3900 230 29 CONTROL BOARD TOP COVER 1 CWC4945 590 30 HOLDER P S CORD 1 CWC4627 040 31 CAP BUTTON 1 CWC5060 120 32 REMOTE CONTROL COMPLETE ASS Y 1 CWA75C556 33 FRONT GRILLE COMPLETE 1 CWC5053 360 34 DECORATING PLATE COMPLETE 1 CWC5027 410 35 DOOR 1 CWC5002 270 36 INTAKE GRILLE C...

Страница 69: ...17 ExplodedView 69 CU A28BKP5 CS A28BKP5 CU A28BKP5 ...

Страница 70: ... 150 18 3 WAYS VALVE GAS 1 CWC4034 170 19 4 WAYS VALVE ASS Y 1 CWC4034 740 20 V COIL COMPLETE 1 CWC4019 400 21 STRAINER 1 CWC4042 340 22 TUBE ASS Y CAPILLARY TUBE CHECK VALVE 1 CWC5932 090 23 CONTROL BOARD ASS Y 1 CWC4712 690 24 CAPACITOR FAN MOTOR 1 CWC4069 960 25 CAPACITOR COMPRESSOR 1 CWC4069 780 26 HOLDER CAPACITOR 1 CWC4828 750 27 TERMINAL BOARD ASS Y 1 CWC4706 590 29 SENSOR COMPLETE 1 CWC390...

Страница 71: ...4092 070 SW1 SW2 PUSH SWITCH C4001 200 FUSE FUSE XBA2C31TR0 X1 RESONATOR F4090 010T BZ BUZZER SOUND GENERATOR C4091 030 All parts are supplied from TAMACO Taiwan Electronic Controller CWC3919 670 CU A28BKP5 SYMBOL DESCRIPTION NAME PART NO IC1 INTEGRATED CIRCUIT C4083 950A IC2 INTEGRATED CIRCUIT C4083 720 IC3 INTEGRATED CIRCUIT C4083 730 IC4 INTEGRATED CIRCUIT C4083 450 Q1 TRANSISTOR C4086 060T Q2 ...

Страница 72: ...20 Electronic Circuit Diagram CS A28BKP5 CU A28BKP5 SCHEMATIC DIAGRAM 1 3 72 CS A28BKP5 CU A28BKP5 ...

Страница 73: ...SCHEMATIC DIAGRAM 2 3 73 CS A28BKP5 CU A28BKP5 ...

Страница 74: ...SCHEMATIC DIAGRAM 3 3 74 CS A28BKP5 CU A28BKP5 ...

Страница 75: ...75 CS A28BKP5 CU A28BKP5 ...

Страница 76: ...Forced Operation 60 sec 0 sec Time Save Control 7 min 42 sec Anti Freezing Control 4 min 0 sec Mode Judgement 20 sec 0 sec Soft Dry Off 6 min 36 sec On 10 min 60 sec SOFT DRY 10 min operation Deodorizing Control 40 sec 4 sec Comp ON Cooling 70 sec 7 sec Comp ON 20 sec 2 sec Comp OFF 180 sec 18 sec Comp OFF Soft Dry 40 sec 4 sec Comp ON 360 sec 36 sec Comp OFF After Deice Ended 30 sec 3 sec Comp OF...

Страница 77: ...20 1 REMOTE CONTROL 77 Printed in Taiwan CS A28BKP5 CU A28BKP5 ...

Отзывы: