Operation
Higher
Standard
Lower
Mode
(+2°C)
(±0°C)
(-2°C)
Cooling
27°C
25°C
23°C
Soft Dry
24°C
22°C
20°C
Heating
23°C
21°C
19°C
b) Overload Deicing Time Diagram
8.4. Automatic Mode Operation
1. When the Automatic Mode Operation is selected, the indoor fan operates at SLo fan speed for 20 seconds to sense intake air
temperature and determine the 1st operation mode.
Standard for Determining Operation Mode 1st Judgement
2. Operation mode will be determine again after 1 hour of operation, if the room temperature reaches to set temperature and
compressor off time is over 7 minutes 30 seconds continuously.
Indoor intake air is less than 16°C, Heating mode will immediate operate. (only in the first time judgement)
The present operation mode will be continued, if the room temperature does not reach to set temperature (Compressor
keeps running) eventhough after 1 hour from automatic operation mode started.
For 2nd judgement onwards, indoor fan will operate for 20 seconds to sense the intake air temperature for determining
operation mode.
Standard for Determining Operation Mode 2nd Judgement onwards
Present
Judgement
Next Mode
Mode
Cooling
Soft Dry
Heating
O
O
Cooling
23°C
Cooling
(Judgement:
Not Applicable
(Judgement:
Heating
23°C & Above)
Below 23°C)
O
O
Soft Dry
20°C
Soft Dry
Not Applicable
(Judgement:
(Judgement:
Heating
20°C & Above)
Below 20°C)
O
O
Heating
Cooling
(Judgement:
Not Applicable
(Judgement:
25°C
Heating
25°C & Above)
Below 25°C)
Automatic Set Temperature Refer 3. as below.
3. Automatic Set Temperature
For each operation, set temperature will automatically set as shown below.
However it can be selected 2°C higher or 2°C lower from standard set temperature by pressing the “Room Temperature Setting
button”.
19
CS-A28
BKP5/CU-A28BKP5
Содержание CS-A28BKP5
Страница 8: ...4 Dimensions 8 CS A28BKP5 CU A28BKP5 CS A28BKP5 CU A28BKP5 ...
Страница 10: ...6 Block Diagram 10 CS A28BKP5 CU A28BKP5 CS A28BKP5 CU A28BKP5 ...
Страница 11: ...7 Wiring Diagram 11 CS A28BKP5 CU A28BKP5 CS A28BKP5 CU A28BKP5 ...
Страница 15: ...Soft Dry Operation Time Diagram 15 CS A28BKP5 CU A28BKP5 ...
Страница 46: ... This can be used for left rear piping and left bottom piping also 46 CS A28BKP5 CU A28BKP5 ...
Страница 64: ...14 Technical Data 64 CS A28BKP5 CS A28BKP5 CU A28BKP5 ...
Страница 65: ...65 CS A28BKP5 CU A28BKP5 CS A28BKP5 CU A28BKP5 ...
Страница 66: ...66 CS A28BKP5 CU A28BKP5 CS A28BKP5 CU A28BKP5 ...
Страница 67: ...15 Exploded View 67 CS A28BKP5 CS A28BKP5 CU A28BKP5 ...
Страница 69: ...17 ExplodedView 69 CU A28BKP5 CS A28BKP5 CU A28BKP5 ...
Страница 72: ...20 Electronic Circuit Diagram CS A28BKP5 CU A28BKP5 SCHEMATIC DIAGRAM 1 3 72 CS A28BKP5 CU A28BKP5 ...
Страница 73: ...SCHEMATIC DIAGRAM 2 3 73 CS A28BKP5 CU A28BKP5 ...
Страница 74: ...SCHEMATIC DIAGRAM 3 3 74 CS A28BKP5 CU A28BKP5 ...
Страница 75: ...75 CS A28BKP5 CU A28BKP5 ...
Страница 77: ...20 1 REMOTE CONTROL 77 Printed in Taiwan CS A28BKP5 CU A28BKP5 ...