Technical Terminology & Cautions for Use

AECTB36E   201811-T

TECHNICAL NOTES ON ELECTRICAL CHARACTERISTICS

CAUTIONS IN A CIRCUIT

1) The snap-action switch is designed for AC operations. While it
has small contact gaps and no arc absorber, it may be used for
low-capacity DC operations.
Please refer to the rating of each products
2) For applications with very small switching voltage or current,
choose the low-level load type (Au contact).

3) When selecting a contact type of a snap-action switch to be
used for low-level load switching, the following should be noted. 
Silver contacts’ surfaces are prone to be oxidized and form a
sulfide film. The switch operates with no problems at the

beginning of use. However, as the contact surfaces develop films 
with time, the film may not be broken by the switching operation, 
causing a conduction failure. Therefore, please choose the Au 
contact type for switching a load of 0.1 A or below.
4) Application to Electronic Circuits
• The snap-action switch contacts can sustain bounce or chatter
when closed. Bounce or chatter can cause noise or pulse count
errors when the snap action switch is used in electronic circuits.
• If contact bounce or chatter poses problems in the vicinity of
the OP and RP, use a suitable absorption network, such as a C/
R network.
5) Check the surge current, normal current and surge duration.
6) Contact resistance given in performance specifications is
measured with a voltage drop method using 6 to 8 V DC, 1 A
(except for low-level load type). Contact resistance across COM
and NC terminals is measured in the free position, while contact
resistance across COM and NO terminals is measured in the
total travel position.
7) To prevent contact welding failure, be sure to use a serial
resistance for each capacitive load.
8) If snap-action switch operation is synchronized with the AC
supply phase, this may cause: shortened electrical life, contact
fusion failure, contact transfer, or other reliability problems.

Small current and voltage application range (Au contact)

500

100

50

5

2

1

4

8

12

16

20

24

10

DC voltage (VDC)

Current (mA)

1) Contact protection is recommended when snap-action
switches are used in an inductive load circuit.

2) Do not connect the
contacts on individual
switches to different
type or different poles of
the power supply.
Examples of power
supply connections
(connection to different
poles)

Example of wrong 
power supply 
connection (connection 
to different poles of 
power supply)
This may lead to mixed 
DC and AC.

3) Avoid circuits which
apply voltage between
contacts. (This may lead
to mixed deposition.)

Circuit diagram

Cautions for use

Contact for snap-action switch

(1) r = more than 10 

Ω

(2) In an AC circuit

Impedance of R is to be slightly smaller 
than impedance of r and c.

Contact for snap-action switch

Can be used for both AC and DC.
Impedance of r is nearly equal to 
impedance of R.
C: 0.1 

μ

F

Contact for snap-action switch

(1) For DC circuits only.

Contact for snap-action switch

Can be used for both AC and DC.

r

c

R

r

c

R

R

diode

ZNR
Varistor

Induction load

PL

Wrong

Solenoid load

Lamp load

PL

Right

Solenoid load

Lamp load

Load connected to same pole

L

Load

L

Load

AC

DC

Wrong

Wrong

L

100V

200V

ー 8 ー

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Содержание AV6 Series

Страница 1: ...Copying machine Printer Also for all types of equipment required for maintenance and inspections 2 SPST NO LEVER POSITION 1 Standard 2 Backward CURRENT CAPACITY reference APPLICABLE CONNECTOR Easy assembling as this switch is connector integrated Applicable connector XA connector produced by JST Mfg Co Ltd Contact SXA 001T P0 6 Housing XAP 02V 1 Connector Applicable range 100mA 1mA 0 30V 5V DC AV ...

Страница 2: ...ts 1 500 Vrms for 1 min Between each terminal and ground 1 500 Vrms for 1 min Contact resistance initial 100mΩ max by voltage drop 0 1A 6 to 8 VDC Value includes the resistance between the connector and the lead AWG28 length 50 mm Viblation resistance malfunction vibration resistance 10 to 55 Hz at single amplitude of 0 75mm Contact opening max 1msec Shock resistance malfunction shock resistance A...

Страница 3: ...7 6 3 85 7 2 5 9 5 0 08 29 2 2 4 0 05 0 1 2 4 0 05 0 1 7 7 Pin plunger type PT 0 6 Max Pin plunger type OP 8 4 0 3 10 0 Pretravel PT Max 0 6mm Movement Differential MD Max 0 1mm Overtravel OT Min 0 4mm Operating Position OP Distance from mounting hole 8 4 0 3mm CAD Data Hinge lever External dimensions 12 9 4 0 7 2 5 OP 10 0 0 08 PT 2 6 Max 2 5 0 1 5 7 9 5 0 08 29 2 2 4 0 05 0 1 2 4 0 05 0 1 7 7 10...

Страница 4: ...ever position Standard Pretravel PT Max 2 6mm Movement Differential MD Max 0 8mm Overtravel OT Min 1 2mm Operating Position OP Distance from mounting hole 12 2 0 8mm Pretravel PT Max 1 4mm Movement Differential MD Max 0 6mm Overtravel OT Min 0 7mm Operating Position OP Distance from mounting hole 11 3 0 6mm Pretravel PT Max 2 6mm Movement Differential MD Max 0 8mm Overtravel OT Min 1 2mm Operating...

Страница 5: ...than the specified connector or solder the terminals directly 2 Make sure leads are arranged so that no constant force is applied to them when the connectors are mated 3 Keep the connector straight when inserting it If it is inserted at an angle it may snag near the entrance or it may be inserted too forcefully 4 Problems thought to be caused by the XA connector which is specified as conforming to...

Страница 6: ...d The life test is performed at a switching frequency of 20 times minute and operating speed of 100 mm second at the regular cam Contact form This refers to the components determining the type of application which make up the electrical input output circuits in the contact Insulation resistance Resistance between non continuous terminals each terminal and other exposed metal parts and between each...

Страница 7: ...orce be maintained to ensure high reliability For a normally closed NC circuit the driving mechanism should be set so that the actuator is normally in the free position For a normally open NO circuit the actuator should be pressed to 70 to 100 of the specified stroke to absorb possible errors If the stroke is set too close to the operating point OP this may cause unstable contact and in the worst ...

Страница 8: ...ct resistance across COM and NO terminals is measured in the total travel position 7 To prevent contact welding failure be sure to use a serial resistance for each capacitive load 8 If snap action switch operation is synchronized with the AC supply phase this may cause shortened electrical life contact fusion failure contact transfer or other reliability problems Small current and voltage applicat...

Страница 9: ... the section CAUTIONS FOR USE for each product Avoid using in a silicon atmosphere Avoid using organic silicon rubber adhesives sealing compounds oil grease and wires in a silicon atmosphere Please consult us when using under the following conditions 1 Environments where hydrogen sulfide or other corrosive gases are present 2 Environments where gasoline thinner or other flammable explosive gases a...

Страница 10: ...ods of time Storage for extended periods of time including transportation periods at high temperatures or high humidity levels or in atmospheres with organic gases or sulfide gases may cause a sulfide film or oxide film to form on the surfaces of the contacts and or it may interfere with the functions Check out the atmosphere in which the units are to be stored and transported In terms of the pack...

Страница 11: ...ing unit Simulated roller lever Large Medium Small Possible Tip of hinge lever is bent into a semi circle enabling use as a simple roller type Leaf lever Large Large Small Excellent Play in lever is used to assure maximum stroke Construction provides for space where lever is attached for outstanding resistance to freezing Hinge roller lever Large Medium Small Possible This is a hinge lever with a ...

Страница 12: ...rrow com Downloaded from Arrow com Downloaded from Arrow com Downloaded from Arrow com Downloaded from Arrow com Downloaded from Arrow com Downloaded from Arrow com Downloaded from Arrow com Downloaded from Arrow com Downloaded from Arrow com Downloaded from Arrow com ...

Отзывы: