KW8M Eco-POWER METER (1A/5ACT input type)
47
8.2.2 Pulse input
Input mode
Addition (Fixed)
Max. counting speed
2kHz /30Hz (Select with setting mode)
Pulse input
Min. input signal width:
0.25ms (When 2kHz selected) /16.7ms (When 30Hz selected)
ON:OFF ratio = 1 : 1
Input signal
Contact / No contact (open collector)
・
Impedance when shorted: Max. 1k
Ω
・
Residual voltage when shorted: Max. 2V
・
Impedance when open: Min. 100k
Ω
Output mode
HOLD (Over count)
Decimal point
Set to 3rd decimal places
Pre-scale setting
Range
0.001 to 100.000 (Selectable with setting mode)
8.3 Pulse output (Transistor output) Specifications
Number of output point
1 point
Insulation method
Optical coupler
Output type
Open collector
Output capacity
100mA 30V DC
Pulse width
approx. 100ms
ON state voltage drop
1.5V or less
OFF state leakage current
100
μ
A or less
Pulse output unit
0.001/0.01/0.1/1/10/100kWh/Alarm(AL-P)/
Current alarm(
AL-C) /Stand-by alarm (AL-S) /Counter(Cnt)
(Selectable with setting mode)
* We recommend the setting of minimum unit for pulse output for measurement shown as below.
Output pulse: 4-pulse or less per 1sec.
How to calculate
(Unit for pulse output
:
PL-P)
>
(Max. measurement power [kW]
)/
(3600[s]
×
4 [pulse/s])
Caution
(1) Improper unit setting may cause miss counting.
(2) If the OFF time is too short, there is a possibility of counting errors.