KW8M Eco-POWER METER (1A/5ACT input type)
44
Data item
(MEWTOCOL)
Name
Unit
Kind of date
Range: Hexadecimal
(Range: Decimal)
MODBUS
Function
code
0096H<LSB>
(DT00150)
0097H<MSB>
(DT00151)
Load ON-time
0.1h
Unsigned 32bit
0H to F423FH (0 to 999999)
03H/
06H/10H
0098H<LSB>
(DT00152)
0099H<MSB>
(DT00153)
Load OFF-time
0.1h
Unsigned 32bit
0H to F423FH (0 to 999999)
03H/
06H/10H
009AH<LSB>
(DT00154)
009BH<MSB>
(DT00155)
Pulse count value
-
Unsigned 32bit
0H to 5F5E0FFH (0 to 99999999)
03H/
06H/10H
009EH<LSB>
(DT00158)
009FH<MSB>
(DT00159)
Preset value
-
Unsigned 32bit
0H to 5F5E0FFH (0 to 99999999)
03H/
06H/10H
00A0H<LSB>
(DT00160)
00A1H<MSB>
(DT00161)
Prescale value
-
Unsigned 32bit
0H to 186A0H (0 to 100000)
03H/
06H/10H
00A2H
(DT00162)
Max.
counting speed
Hz
Unsigned 16bit
1EH (30), 7D0H (2000)
03H/
06H/10H
00A3H
(DT00163)
Auto-off time
min
Unsigned 16bit
0H to 63H (0 to 99)
03H/
06H/10H
00AAH<LSB>
(DT00170)
00ABH<MSB>
(DT00171)
Voltage L1V (R)
0.1V
Unsigned 32bit
0H to 1869FH (0 to 99999)
03H
00ACH<LSB>
(DT00172)
00ADH<MSB>
(DT00173)
Voltage L2 (S/T)
0.1V
Unsigned 32bit
0H to 1869FH (0 to 99999)
03H
00AEH<LSB>
(DT00174)
00AFH<MSB>
(DT00175)
Voltage L3V (S/T)
0.1V
Unsigned 32bit
0H to 1869FH (0 to 99999)
03H
00B0H<LSB>
(DT00176)
00B1H<MSB>
(DT00177)
Instantaneous
active power
0.01kW
Unsigned 32bit
0H to 5F5E0FFH (0 to 99999999)
03H
00B2H<LSB>
(DT00178)
00B3H<MSB>
(DT00179)
Instantaneous
reactive power
0.01kvar
Signed 32bit
FF676981H to 5F5E0FFH
(-9999999 to 99999999)
03H
00B4H<LSB>
(DT00180)
00B5H<MSB>
(DT00181)
Instantaneous
apparent power
0.01kVA Unsigned 32bit
0H to 5F5E0FFH (0 to 99999999)
03H
<LSB>: Least significant byte
<MSB>: Most significant byte
note 1) 03H: Read 06H/10H: Write
2) Data register except specified is “0”.
3) If each setting value is wrote by communication, it memories to internal EEP-ROM at the same
time. Therefore, change setting frequently makes EEP-ROM’s life short. Avoid to usage like this.
4) Write a data within the range when you write it.