KW8M Eco-POWER METER (1A/5ACT input type)
30
・
Current measurement parts
Eco-POWER METER measures the current as below.
Display
System
L1 L2 L3
Single-phase two-wire
L1(R) current
(Skip)
(Skip)
Single-phase three-wire
L1(R) current
L2 (T) current
(Skip)
Three-phase three-wire
L1(R) current
L2 (T) current
L3 (S) current
Three-phase four-wire
L1(R) current
L2 (S) current
L3 (T) current
6.1.4 Voltage
・
It displays the voltage value of the load.
・
Press <SHIFT/
▽
> to change voltage between P1 and P0, P2 and P0, P3 and P0.
*Before start measuring, select phase and wire system according to the measured load.
When 1P3W or 3P3W is selected, it doesn’t measure 1P2W system correctly. When 3P4W system is
selected, it doesn’t measure 1P2W, 1P3W, 3P3W system correctly.
Select phase and wire system according to the measured system. (Refer to the explanation of setting
mode.)
[V]
Lighting
・
When input voltage is under 5% of rating, it displays “0.0” and doesn’t measure.
(“Under 5%” means the value getting from this calculation
“rated voltage 200(400) x 0.05 x VT ratio”.)
・
When input voltage exceeds 150%F.S. at each range,
「
- - - -
」
will be displayed.
・
Voltage measurement parts
Eco-POWER METER measures the voltage as below.
Display
System
L1 V
L2 V
L3 V
Single-phase
two-wire
Between P1 and P0 (R)
voltage(line-voltage)
(Skip) (Skip)
Single-phase
three-wire
R voltage
(phase-voltage)
S voltage
(phase-voltage)
(Skip)
Three-phase
three-wire
Between P1 and P0 (R)
voltage (line-voltage)
Between P2 and P0 (T)
voltage (line-voltage)
Between P1 and P2 (S)
voltage (line-voltage)
Three-phase
four-wire
R voltage
(phase-voltage)
S voltage
(phase-voltage)
T voltage
(phase-voltage)