10.6 Over Limit Input
Operations depend on the status of over limit input (+) and over limit input (-) as follows.
■
Operation at over limit input (Home search is valid)
Condition
Direction
Limit status
Operation
When home return
operation is executed
Forward
Over limit input (+): ON
Executable
Over limit input (-): ON
Executable
Reverse
Over limit input (+): ON
Executable
Over limit input (-): ON
Executable
During home return
operation
Forward
Over limit input (+): ON
Automatic reverse
operation
Reverse
Over limit input (-): ON
Automatic reverse
operation
■
Operation at over limit input (Home search is invalid)
Condition
Direction
Limit status
Operation
When home return
operation is executed
Forward
Over limit input (+): ON
Not executable, Error
occurs.
Over limit input (-): ON
Executable
Reverse
Over limit input (+): ON
Executable
Over limit input (-): ON
Not executable, Error
occurs.
During home return
operation
Forward
Over limit input (+): ON
Stop, Error occurs.
Reverse
Over limit input (-): ON
Stop, Error occurs.
■
Input valid logic of over limit input
● When the over limit switches (+) (-) are not connected to the pulse output unit, change the
over limit input valid logic of the Pulse_4Axes parameter to "NO contact". The default is "NC
contact", and an over limit error occurs.
■
Precautions on over limit switch
● An over limit input valid for JOG operation, home return and pulser operation is the one
logically found in the direction of the movement. Even if an over limit switch (-) is input for a
movement in (+) direction or an over limit switch (+) is input for a movement in (-) direction,
the operation will not stop.
● Make sure that an over limit switch (+) is set in the direction of the elapsed value increment
and an over limit switch (-) in the direction of the elapsed value decrement.
● When a switch is not set in the correct direction, the followings might be a cause. Check your
settings and correct them.
1) An over limit switch, (+) or (-), is not set in a correct direction.
2) CW / CCW output method is set reverse for the connection of the pulse output unit and
the motor driver.
3) A sign input logic is set reverse for the connection of the pulse output unit and the motor
driver.
10.6 Over Limit Input
WUME-GM1PG-01
10-17
Содержание AGM1PG04L
Страница 2: ... MEMO 2 WUME GM1PG 01 ...
Страница 11: ...1 Before Using This Product 1 1 Safety Precautions 1 2 1 2 Handling Precautions 1 3 WUME GM1PG 01 1 1 ...
Страница 14: ... MEMO 1 4 WUME GM1PG 01 ...
Страница 22: ... MEMO 2 8 WUME GM1PG 01 ...
Страница 42: ... MEMO 3 20 WUME GM1PG 01 ...
Страница 52: ...4 5 Increment and Absolute 4 10 WUME GM1PG 01 ...
Страница 70: ...AccDec 10000 END_CASE 6 1 Sample Program 6 6 WUME GM1PG 01 ...
Страница 82: ... MEMO 7 10 WUME GM1PG 01 ...
Страница 90: ... MEMO 8 8 WUME GM1PG 01 ...
Страница 94: ...AccDec 10000 END_CASE 9 1 Sample Program 9 4 WUME GM1PG 01 ...
Страница 108: ...Current stops when the home or near home position is detected 10 4 Home and Near Home Input Logic 10 12 WUME GM1PG 01 ...
Страница 116: ... MEMO 10 20 WUME GM1PG 01 ...
Страница 124: ... MEMO 11 8 WUME GM1PG 01 ...
Страница 142: ... MEMO 14 4 WUME GM1PG 01 ...
Страница 158: ...16 3 Dimensions 16 3 1 Pulse Output Unit Unit mm 16 3 Dimensions 16 8 WUME GM1PG 01 ...
Страница 162: ... MEMO App 4 WUME GM1PG 01 ...
Страница 163: ...Record of Changes Date Manual No Record of changes August 2021 WUME GM1PG 01 1st edition WUME GM1PG 01 ...
Страница 164: ... MEMO WUME GM1PG 01 ...
Страница 165: ... MEMO WUME GM1PG 01 ...
Страница 166: ...Panasonic Corporation 2021 August 2021 WUME GM1PG 01 ...