■
Voltage input range: 0 to +10 V
Input range: 0 to +10 V
Analog input
value
(V)
Digital conversion
value
(K)
+10
+32,000
+8
+25,600
+6
+19,200
+4
+12,800
+2
+6,400
0
0
When exceeding the rated range
Analog input
value
Converted value
+10 V or more
+32,000
0 V or less
0
■
Voltage input range: 0 to +5 V
Input range: 0 to +5 V
Analog input
value
(V)
Digital conversion
value
(K)
+5
+32,000
+4
+25,600
+3
+19,200
+2
+12,800
+1
+6,400
0
0
When exceeding the rated range
Analog input
value
Converted value
+5 V or more
+32,000
0 V or less
0
4.1 Input Conversion Characteristics
WUME-FPXHAIO-01
4-3
Содержание AFPXHEAD4
Страница 2: ...MEMO 2 WUME FPXHAIO 01...
Страница 5: ...Indicates operation procedures WUME FPXHAIO 01 v...
Страница 6: ...MEMO vi WUME FPXHAIO 01...
Страница 26: ...MEMO 2 10 WUME FPXHAIO 01...
Страница 42: ...3 4 Analog Input Functions 3 16 WUME FPXHAIO 01...
Страница 46: ...3 5 Analog Output Functions 3 20 WUME FPXHAIO 01...
Страница 56: ...MEMO 4 10 WUME FPXHAIO 01...
Страница 62: ...MEMO 5 6 WUME FPXHAIO 01...
Страница 72: ...MEMO 7 6 WUME FPXHAIO 01...
Страница 75: ...MEMO WUME FPXHAIO 01...