3.5.2 Analog Output Range Setting
When a set value is entered in the "Output range setting area" using the user program, the
analog output range is set in the unit
● When H1 to H7 is entered in the "Output range setting area", the analog output is started.
● If a change is made to the program after the mode is changed to the PROG. mode, cycle the
power.
■
Sample program
If an expansion is made to the 1st unit, set as follows using the user program to set the -10 to
+10 V range to CH0 and CH1 and the +4 to +20 mA range to CH2 and CH3.
R0
F0 MV
H7744
WY36
■
Output range setting value
H1: 0 to +10 V
H2: 0 to +5 V
H3: 0 to +20 mA
H4: -10 to +10 V
H5: -5 to +5 V
H6: +1 to +5 V
H7: +4 to +20 mA
H0, H8 to F: Do not use the analog input.
■
I/O allocation
Channel
Expansion location
1st unit
2nd unit
3rd unit
4th unit
5th unit
6th unit
7th unit
8th unit
CH0 to CH3
WY36
WY46
WY56
WY66
WY76
WY86
WY96
WY106
■
I/O contents
The range setting data for each channel data is allocated from the lower level in the order of
CH0, CH1, CH2, and CH3.
3.5 Analog Output Functions
3-18
WUME-FPXHAIO-01
Содержание AFPXHEAD4
Страница 2: ...MEMO 2 WUME FPXHAIO 01...
Страница 5: ...Indicates operation procedures WUME FPXHAIO 01 v...
Страница 6: ...MEMO vi WUME FPXHAIO 01...
Страница 26: ...MEMO 2 10 WUME FPXHAIO 01...
Страница 42: ...3 4 Analog Input Functions 3 16 WUME FPXHAIO 01...
Страница 46: ...3 5 Analog Output Functions 3 20 WUME FPXHAIO 01...
Страница 56: ...MEMO 4 10 WUME FPXHAIO 01...
Страница 62: ...MEMO 5 6 WUME FPXHAIO 01...
Страница 72: ...MEMO 7 6 WUME FPXHAIO 01...
Страница 75: ...MEMO WUME FPXHAIO 01...