2.3 Wiring to the Connector
2.3.1 Suitable Parts and Tools
A spring connection type is used for the terminal block of the analog I/O section. Perform wire
connection properly by referring to the compatible products listed in the following tables.
Compatible wires (stranded wire)
Size
Nominal cross-sectional area
AWG24 to AWG16
0.2 mm
2
to 1.5 mm
2
Rod terminals with compatible insulation sleeve
Manufacturer
Cross-sectional
area
Size
Model number
Phoenix Contact Co., Ltd.
0.25 mm
2
AWG24
AI 0,25-6 YE
0.50 mm
2
AWG20
AI 0,5-6 WH
0.75 mm
2
AWG18
AI 0,75-6 GY
1.00 mm
2
AWG18
AI 1-6 RD
Crimping tool dedicated to rod terminals
Manufacturer
Model number
Product No.
Phoenix Contact Co., Ltd.
CRIMPFOX UD 6
1204436
2.3.2 Wire Connection Method
Perform wire connection of the terminal block according to the following procedure.
1.
Strip the sheath from the electric wire.
10
mm
2.
While pressing the tab on the terminal block using a flat-blade screwdriver, insert the wire
all the way until it stops. Confirm that the electric wire is fixed in place when the screwdriver
is released.
2.3 Wiring to the Connector
2-8
WUME-FPXHAIO-01
Содержание AFPXHEAD4
Страница 2: ...MEMO 2 WUME FPXHAIO 01...
Страница 5: ...Indicates operation procedures WUME FPXHAIO 01 v...
Страница 6: ...MEMO vi WUME FPXHAIO 01...
Страница 26: ...MEMO 2 10 WUME FPXHAIO 01...
Страница 42: ...3 4 Analog Input Functions 3 16 WUME FPXHAIO 01...
Страница 46: ...3 5 Analog Output Functions 3 20 WUME FPXHAIO 01...
Страница 56: ...MEMO 4 10 WUME FPXHAIO 01...
Страница 62: ...MEMO 5 6 WUME FPXHAIO 01...
Страница 72: ...MEMO 7 6 WUME FPXHAIO 01...
Страница 75: ...MEMO WUME FPXHAIO 01...