BWT™ System Installation Guide
21
Chapter 3. Acoustic Isolation Installation (FIPA Buffers)
Chapter 3. Acoustic Isolation Installation (FIPA Buffers)
3.1
Introduction
The FIPA Buffer is used for gas applications at lower pressures. This buffer has a flanged isolation section that reduces
acoustic short circuits. The buffer also has a flanged process connection and is typically available in two lengths:
• 2 in.
6 in. for low temperature ranges from -150 to 315
o
C (-270 to 600
o
F)
• 6 in.
6 in. for high temperature ranges from -150 to 600
o
C (-270 to 1,100
o
F)
Follow the instructions in this chapter to properly install the buffers and transducers.
3.2 Identifying and Checking the Components
Panametrics supplies the parts required for your installation. Before you begin, check the lists below to make sure you
have all of the needed components. Refer to
Figure 7 on page 22 and Figure 8 on page 22 to help you identify each
component.
Note:
The list below is for a
one-path
installation.
• Acoustic Isolation FIPA Buffers
- fully assembled
• 2 BWT1 transducers
• 2 Kamprofile gaskets
IMPORTANT:
Kamprofile gaskets must be used for two reasons: they ensure a leak tight seal and they provide
necessary acoustic isolation.
• 2 Junction boxes
• Preamplifiers - required for gas flow applications (may be mounted in transducer junction box)
• 3M epoxy or equivalent for permanent bond
(not shown in photo)
• Required studs, nuts and washers
(not shown in photo)
• 10 ft (3 m) coaxial cable with BNC connectors
(not shown in photo)
• Additional preamplifier to electronics cable (required for gas flow applications)
(not shown in photo)
You will need to supply the following additional items:
• Copperslip (SS316), Molykote grease P47 (CS) or equivalent anti-seizing compound
• Adjustable torque wrench with 15
-
148 ft-lb range (20
-
200 N-m) with socket drive
• Standard and deep sockets
• Adjustable wrench (12 in. long or equivalent)
• Steel wool
• Calipers
• Tape measure
CAUTION!
It is critical that you follow the instructions presented in this document. If you do not,
Panametrics cannot ensure the proper operation of your equipment.
Содержание BWT System
Страница 1: ...panametrics com Flow 916 058 F July 2021 BWT System Installation Guide ...
Страница 2: ......
Страница 4: ...ii no content intended for this page ...
Страница 8: ...Contents BWT System Installation Guide ...
Страница 16: ...Chapter 1 General Information 8 BWT System Installation Guide no content intended for this page ...
Страница 52: ...Chapter 5 Specifications 44 BWT System Installation Guide no content intended for this page ...
Страница 54: ...46 BWT System Installation Guide no content intended for this page ...
Страница 57: ......