- 10 -
OPERATIONAL PRINCIPLE
WHEN SUPPLYING HOT WATER
1) By opening the Hot Water Top (1), the water fl ows through the Water Flow Sensor (3) to the Heat
Heat Exchanger (19).
2) The frequency signal is given from the Water Flow Sensor (3) and when the PC Board (27) senses the signal
that reached a certain frequency, the Fan (24) starts to turn round.
3) After the Fan (24) turned round and pre-purged, the Gas Inlet Solenoid Valve (9), Solenoid Valve 1 (10) and
Solenoid Valve 2 (11) open at the same time. Then, the Proportional Gas Control Valve (13) becomes an
ignition motion and allows the gas to fl ow to the Main Burner (15) (and Sensing Burner for PH-28RIFS,
PH-28CIFS, PH-28RDVS and PH-28CDVS only).
4) At the same time, the Igniter (16) continuously makes sparks and ignites the Main Burner (15).
After ignited, when the Flame Rod (18) senses the fl ame and make sure the combustion, the Proportional
Gas Control Valve (13) fi nishes the ignition motion.
5) After fi nished the ignition motion, the proportional gas control is started. When there is a temperature
difference between the hot water temperature that is sensed by the Hot Water Outlet Thermistor (6) and the
set temperaturer on the Remote Control, the PC Board (27) judges it and open or close the Solenoid
Valve 1 (10), Solenoid Valve 2 (11) and Solenoid Valve 3 (12), and also the Proportional Gas Control Valve
(13) continuously adjusts the gas volume in order to maintain the outlet temperature from the Heat
Exchanger (19).
The Water Flow Servo (7) also adjusts the proper amount of water fl ow to supply a stable hot water
temperature at all times.
6) According to the adjustment of the gas volume by the Proportional Gas Control Valve (13), a signal from the
PC Board (27) is also sent to the Fan Motor (25) in order to maintain the relation between the gas volume
and air volume at all times.
7) (For PH-28RIFS, PH-28CIFS, PH-28RDVS and PH-28CDVS only) When the air intake or venting is
blocked, or the oxygen of the air intake is not suffi cient, the output of the Thermocouple that is located at the
Sensing Burner would be changed. The PC Board (27) senses this change and controls the Fan (24),
Proportional Gas Control Valve (13), etc. in order to prevent the imperfect combustion. Further, if such
condition is proceeded, it shuts off the Gas Inlet Solenoid Valve (9), Solenoid Valve 1 (10),
Solenoid Valve 2 (11), Solenoid Valve 3 (12) and Proportional Gas Control Valve (13) in order to stop the
operation.
8) When the Hot Water Tap (1) is closed, the frequency signal from the Water Flow Sensor (3) is stopped and
the Gas Inlet Solenoid Valve (9), Solenoid Valve 1 (10), Solenois Valve 2 (11), Solenoid Valve 3 (12) and
Proportional Gas Control Valve (13) turn off and becomes a post-purge motion.
9) When the time of the post-purge is up, the Fan (24) stops.
Содержание PH-28CDVSN
Страница 16: ...Operational Flow Chart Maintenance Information 16...
Страница 18: ...18...
Страница 19: ...MAINTENANCE INFORMATION SHOWN IN LED DISPLAY OF REMOTE CONTROL ABOVE 19...
Страница 44: ...44...
Страница 53: ...Schematic Disassembly PH 28RIFS 53...
Страница 54: ...Schematic Disassembly PH 28ROF 54...
Страница 55: ...Schematic Disassembly PH 28RIFS PH 28ROF 734 55...
Страница 58: ...Schematic Disassembly PH 28CIFS 58...
Страница 59: ...Schematic Disassembly PH 28COF 59...
Страница 60: ...Schematic Disassembly PH 28CIFS PH 28COF 734 60...
Страница 63: ...Schematic Disassembly PH 28RDVS 63...
Страница 64: ...Schematic Disassembly PH 28CDVS 64...
Страница 65: ...Schematic Disassembly PH 28RDVS PH 28CDVS 65...