ROBATA 72/54 CONCRETE FIRE | Installation & Owner’s Manual

TROUBLESHOOTING cont’d

WARNING:

Turn off appliance and let cool before 

servicing.  Only a qualified service person 

should service and repair this appliance.

OBSERVED PROBLEM

POSSIBLE CAUSE

REMEDY

When power is turned on, nothing 

happens

1.  No power to unit

1.  Check connections between 

controls, power adapter and 

power source

2.  Check power at source

3.  Verify that power adapter is 

functioning correctly

4.  If you are using a third-party 

remote control unit, verify that 

this unit is functioning correctly

When power is turned on, there is a 

spark at pilot but no ignition

1.  Gas supply turned off or manual 

shutoff valve closed

2.  Air in gas lines when installed

3.  Pilot is clogged

4.  Pilot valve lead is loose/

disconnected

1.  Turn off gas supply or open 

manual shutoff valve

2.  Purge air from the supply line

3.  Clean pilot (see Cleaning and 

Maintenance, page 12) or replace 

pilot assembly

4.  Check/reconnect lead

Burner does not light after pilot is lit

1.  Burner orifice is clogged

2.  Inlet gas pressure is too low                  

3.  Flame sensor or Main Valve lead 

loose/disconnected

4.  Ignition Control Board failure

1.  Clean burner orifice

2.  Contact local gas or propane 

supplier

3.  Reconnect / replace lead 

4.  Replace Board

Delayed burner ignition

1.  Lighting port is blocked

1.  Remove burner media/debris 

from Lighting Port

Burner flame is too low or too high

1.  Incorrect gas supply or pressure

2.  Blocked burner orifice or burner 

ports

3.  Improper burner orifice size

1.  Check for proper gas supply 

pressure

2.  Free burner orifice and burner 

ports of any burrs, paint, or other 

blockage

3.  Verify proper burner orifice sizing 

(see page 6)

Содержание Robata 54 Concrete

Страница 1: ...gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance An LP cyllinder not connected for use shall not be stored in the vicinity of this or any other appliance C...

Страница 2: ...1 NFPA 54 or the International Fuel Gas Code 3 Keep the appliance area clear and free from combustible materials gasoline and other flammable vapors and liquids 4 Do not burn solid fuel in this appli...

Страница 3: ...TRAY GAS ELECTRICAL SUPPLY BODY ROBATA 72 ROBATA 54 1 UNPACK Account for all parts p 15 16 2 FRAGILE Handle with care 3 LEVEL Place on a solid level surface 4 AIR VENTS Do not block ventilation gaps p...

Страница 4: ...OBATA 72 54 CONCRETE FIRE Installation Owner s Manual DIMENSIONS ROBATA 54 22 559 24 610 8 203 54 1372 20 3 4 527 12 1 2 318 22 559 12 1 2 318 SIDE END BOTTOM VENTILATION GAP DO NOT OBSTRUCT BASE OPEN...

Страница 5: ...ROBATA 72 54 CONCRETE FIRE Installation Owner s Manual DIMENSIONS ROBATA 72 SIDE END BOTTOM BASE OPENINGS VENTILATION GAPS DO NOT OBSTRUCT 12 1 2 318 16 3 4 425 24 610 72 1829 22 559 8 203 11 1 4 286...

Страница 6: ...h 57 000 BTU h 80 000 BTU h 77 000 BTU h Inlet Pressure Min 4 5 W C 11 0 W C 4 5 W C 11 0 W C Inlet Pressure Max 10 5 W C 13 0 W C 10 5 W C 13 0 W C Orifice Size 26 43 18 37 Burner Ports 35 35 47 47...

Страница 7: ...rock or tempered glass pebble on top of burner media See page 8 Decorative media should be brought level with the top of the pilot cover An uneven or excessively thick layer of topping can result in...

Страница 8: ...tallation Owner s Manual BURNER MEDIA DECORATIVE TOPPING METAL LID OPTIONAL DECORATIVE TOPPING MEDIA VARIOUS FILL TOPPING TRAY COVER BURNER MEDIA KEEP BELOW LID LINE BURNER MEDIA CRUSHED GLASS NG LAVA...

Страница 9: ...en flame to check for a leak Apply a mixture of liquid soap and water to all joints Bubbles forming on joints while the gas is running indicate a leak Correct all leaks at immediately Test Pressures i...

Страница 10: ...ed service technician to inspect the appliance and to replace any part of the control system and any gas control that has been under water Improper installation adjustment alteration service or mainte...

Страница 11: ...the ON position 7 Plug the supplied 24 VAC AC adapter into a 110V power outlet 8 Connect the AC adapter to the AC input plug at the unit 9 Place Burner Assembly in Housing 10 To ignite burner turn on...

Страница 12: ...s 13 14 BURNER ELEMENT AND PILOT Keep the burner and pilot area clean by vacuuming or brushing at least twice a year Make sure the burner porting and burner air openings are free of obstructions at al...

Страница 13: ...PORT In the case of consistently windy conditions a protective glass barrier may be necessary 2 Ensure gas line is thoroughly bled 3 Ensure ventilation holes gaps are not obstructed Unit is smoking s...

Страница 14: ...ed 4 Pilot valve lead is loose disconnected 1 Turn off gas supply or open manual shutoff valve 2 Purge air from the supply line 3 Clean pilot see Cleaning and Maintenance page 12 or replace pilot asse...

Страница 15: ...me 2a Air Shutter 3 Orifice FIT ORI 26 or 18 FIT ORI 37 or 43 4 Media Tray LIN 36 or 48 ASSY A same 5 Burner Tray LIN 36 or 48 ASSY B same 6 Control Box Brackets LIN 36 or 48 ASSY C same 7 Pilot Assem...

Страница 16: ...R E BOX same 2 Dual Solenoid Valve E VAL BASO w LP reg spring 3 3 8 x1 1 2 Nipple 4 3 8 Bulkhead Union 5 3 8 Union 6 Pilot Assembly PIL E 410 PIL E 410LP 7 Shrink fit Cord Grip 8 Ignition Control Boar...

Страница 17: ...ED PARTS LIST Wiring Diagram 1 2 3 4 5 10 6 7 11 8 9 MAIN GND VALVE PILOT GND BURNER GND 24V SENSE SPARK AC POWER ADAPTER INPUT AC 120V 60 Hz 8A OUTPUT 24 VAC 750 mA CHASSIS GROUND PILOT PIL E 410 OR...

Страница 18: ...rranty will also be void if the appliance is not operated and maintained according to the operating instructions supplied with the appliance and does not extend to 1 fire pit burner assembly damaged b...

Отзывы: