- 23-
6. Maintenance
6.1 Maintenance and Cleaning for User
It is good practice to inspect your heat pump regularly. Maintenance should be carried out at least
annually to maintain a good lifespan of your heat pump.
1. Regularly clean the Y type filters every 6 months to ensure that the system is clean and to
avoid blockage to the system.
2. Units should be kept clean (no leaves or dirt) and no obstructions should be placed in front of
or behind the unit. Good ventilation and regular cleaning (3-6 months) of the evaporator will
help maintain efficiency.
3. Ensure the unit has power in the winter whether the unit is used or not.
6.2 Maintenance for Specialist
1. Check the power unit and electrical system.
2. Check the water system, safety valves and exhaust devices are working properly so as not
to pump air into the system causing reduced circulation.
3. Check water pump is functioning properly. Make sure the water pipeline and pipe fittings are
not leaking.
4. Clear evaporator of any debris.
5. Check the various components of the unit work properly. Inspect the pipe joints and valves
branch have inflated oil, to ensure no leakage of the refrigerant unit.
6. Chemically flush the plate heat exchanger after every 3 years.
7. Check refrigerant gas content if necessary.
8. Check delta (water in/out) making it meets the guidelines of delta 3 to 7.
Содержание AH9
Страница 1: ...1 DC INVERTER MONOBLOCK AIR TO WATER HEAT PUMP AND CHILLER User Manual REV WR 2017V8...
Страница 9: ...9 Wiring Diagram 3 Phase 3 4 1 Installation Drawing...
Страница 21: ...21 5 1 Internal View 5 2 System Drawing AH9 11 16 17S 25S...
Страница 22: ...22 5 3 Dimensions Model 9 W 1090 D 420 H 780 A 440 B 810 16 17S 1280mm for 16 17S 1462mm for 25S...