- 18- 

P02 

AC temp differentia   

2~15

℃,

minus differentia 

2

 

 

P03 

Coil copper pipe temp to active defrost 

-20~5

 

0

 

 

P04 

water source side anti freeze temp 

(for Geo heat pump)

 

-20~5

 

2

 

 

P06 

  Coil copper pipe temp to stop defrost   

10~35

 

30

 

 

P07 

defrost time (defrost action lasting max time, will stop defrost    if   
longer than this value) 

15~99 minutes 

15 

 

P08 

defrost interval time ( time between 2defrosts, less than this value, it 
will not defrost) 

15~99 minutes 

35 

 

P09 

ambient temp to activate hot water e-heater 

-20~20

 

0

 

 

P10 

ambient temp to activate AC e-heater 

-20~20

 

0

 

 

P11 

DHW frequency limitation percentage on max frequency.   
(If heat pump max is 90HZ, p11=9, DHW only run 81hz) 

2~10

    (equal to the highest   

frequency 20~100%) 

10 

 

P12 

compressor discharge air protection temp (higher than the setting, it will 
protect) 

100~127

 

115

 

 

P13 

defrost interval multiple times control   
(if P08=35minutes, P13=2, interval between defrost will be 
35*2=70Minutes) 

0

no defrost

1~4

defrost interval   

time multiple rate   

 

P14 

functional parameter ( to control seasonal valve and solar valve, 
UK may not use it) 

0

G3 is seasonal switching valve

 

1

G3is solar valve 

 

 

P19 

running with fixed    frequency 

(for factory testing only)

 

10~100 HZ     

50HZ 

 

P20 

running frequency setting

( for factory only)

 

0

manual frequency

   

1

auto running frequency 

 

P21 

EEV manually initial open degree (heating) /2 

50~240 (Only valid when P23=3) 

175 

   

P22 

EEV manually initial open degree (cooling)/2 

50~240(Only valid when P23=3) 

175 

   

P23 

EEV control mode 

0—no

1—checking

2—manual

 

3—auto   

for factory only

 

 

P24 

EEV Temp differential to stop the valve (heating)   

-5~10

 

  for factory only

 

0

 

 

P25 

EEV temp differential to stop the valve (cooling) 

-5~10

   

for factory only

 

0

 

 

P26 

water pump working mode 

0(no  stop)

1

stop  when  reach  temp

)、

2

running 1 minute every 15minutes

 

 

P27 

  second heat source validation 

0

no

1

yes

 

 

P28 

  starting air temp for second heat source 

-30~15

(On when lower than this) 

-15

 

 

P29 

room target setting temp 

10-28

 

21

 

(

H

P30 

buffer tank highest temp 

35-55

 

45

 

(

G

P31 

buffer tank lowest temp 

15-30

 

25

 

(

L

P32 

  water temp adjust range 

1-5

 

2

 

(

F

P33 

water temp adjust interval   

20-255min 

120min  (

I

P34 

longest counting period 

6-48H 

24H 

(

J

P35 

target water temp modification value 

-2

-5

 

2

 

(

E

P36 

ambient temp correction factor X100 

10-200 

75 

(

C

P37 

starting ambient temp for calculation 

-7-15

 

7

 

(

B

P38 

temp differential to reduce frequency 

4-15

 

7

 

T

 

P39 

target of low frequency(when reach the setting of P38, it will 
reduce to the P39/100 of the highest 

15-90 

15 

U

 

P40 

monitoring interval (to adjust frequency) 

1-15min 

2min 

V

 

P41 

temp interval (increase or decrease base on this setting. Every P40 
minutes when reach P41 C/2, will change frequency) 

1-4

 

1

 

W

 

P42 

increase frequency adjustmentX100 

2-50(%) 

15 

S

 

P43 

decrease frequency adjustment X100 

2-50 (%) 

15 

Y

 

P44 

target temp tolerance 

1-3

 

2

 

Z

 

P45 

AC AU curve offset value (our weather compensation curve AU) 

-15~15

 

0

 

 

P46 

AC AU curve max temp value    (our AU) 

30~50

 

45

 

 

P47 

night mode validation (night mode: DHW increase 3C, 
  AC temp reduce 2C) 

0

off

1

on

 

 

P48 

night mode starting point 

0-23

time

 

22 

 

P49 

night mode ending point 

0-23

time

 

 

 
Remarks: 

1.

 

The Parameter P21~P25 are different for different modles, it can 
only be set during the production. You have to keep it during your 

Содержание AH9

Страница 1: ...1 DC INVERTER MONOBLOCK AIR TO WATER HEAT PUMP AND CHILLER User Manual REV WR 2017V8...

Страница 2: ...ed during installation for heat pump air conditioning side to ensure proper water flow 2 Water filter MUST be installed before water go into PLATE HEAT EXCHANGER The water filter need to be cleaned at...

Страница 3: ...s 0 factory setting the auxiliary heater switches on to ensure the heat pump unit works normally The unit is also capable of cooling in the summer The heat pump controller is an intelligent wired syst...

Страница 4: ...is led off to a water drain or a suitable soak away The distance between the unit and the exterior wall must be at least 350 mm The free space above must be at least one meter The unit must not be pl...

Страница 5: ...all installation options When connecting with the AH9 11 16 the total water volume in the heat pump pipe system and buffer tank must be at least 10 liters per KW of output A Space Heating Cooling DHW...

Страница 6: ...Cooling DHW Solar Application 1 Solar Application 2 1 Heat Pump 3 DHW sensor 4 Water filter 5 Ball valve 6 Air discharge valve Tap Water Inlet DHW with solar heating C4 Solar hot water system antifree...

Страница 7: ...pe Connection 28mm pipe is recommended The pipe work must be flushed before the heat pump is connected so that any contaminants do not damage the components parts The heating cooling water inlet and o...

Страница 8: ...with the power supply there is still a risk of damage due to freezing During the installation Anti freeze Ethylene Glycol is strongly recommended If the air temp is ever lower than 0c it must use enou...

Страница 9: ...9 Wiring Diagram 3 Phase 3 4 1 Installation Drawing...

Страница 10: ...ver 30 minutes withdraw AC antifreeze When anti freezing if water temperature reduced to 1 C or lower machine will stop and error code Pd display 3 5 COMMISSIONING 3 5 1 Preparations Before commission...

Страница 11: ...ed from the hot water and venting may be necessary If bubbling sounds can be heard from the heat pump the circulation pump or radiators the entire system will require further venting When the system i...

Страница 12: ...ompressor the auxiliary electric heater E2 will start together with E1 When the heat pump is running AC heating A When the heat pump runs AC heating normally the auxiliary electric heater E2 turns on...

Страница 13: ...H water pump or fan motor 13 DHW 14 Sterilization 15 auto mode 16 room heating 17 cooling 18 service icon 19 lock icon 20 Temp 21 Indicating temp location 22 temp unit 23 Defrost icon 24 anti freeze 2...

Страница 14: ...ization will fail to work In on or standby mode first press key M and for 3 seconds second press key M 15 icon appears then press the or to set sterilization temperature press key to confirm the numbe...

Страница 15: ...y select the setting period press to confirm Hour number flash as below 2 Press up and down key to select number of hour press to confirm After confirmation minute number flash press up and down key t...

Страница 16: ...eed 4 4 6 Auto mode icon Automatically select heating or cooling mode After you select AUTO mode when ambient temp 15C it run AC cooling mode When ambient temp 25C it run AC cooling mode When ambient...

Страница 17: ...ssor abnormal stop Red and flash compressor stops abnormally F4 outdoor module radiator sensor error Flash 5 time Temp sensor open circuit or short circuit F5 outdoor current sensor error Flash 8 time...

Страница 18: ...y only 0 P24 EEV Temp differential to stop the valve heating 5 10 for factory only 0 P25 EEV temp differential to stop the valve cooling 5 10 for factory only 0 P26 water pump working mode 0 no stop 1...

Страница 19: ...h a beep parameter reset indoor PCB need to power off and on again to make the change valid parameter reset to default 4 functional parameter P14 When parameter valve 1 when unit working with AC heati...

Страница 20: ...2 four way valve 1 on 0 off 23 bypass valve 1 on 0 off 24 1 electrical valve 1 on 0 off 25 2 electrical valve 1 on 0 off 26 3 electrical valve 1 on 0 off 27 1 electrical heater 1 1 on 0 off 28 2 elect...

Страница 21: ...21 5 1 Internal View 5 2 System Drawing AH9 11 16 17S 25S...

Страница 22: ...22 5 3 Dimensions Model 9 W 1090 D 420 H 780 A 440 B 810 16 17S 1280mm for 16 17S 1462mm for 25S...

Страница 23: ...has power in the winter whether the unit is used or not 6 2 Maintenance for Specialist 1 Check the power unit and electrical system 2 Check the water system safety valves and exhaust devices are work...

Страница 24: ...he same time you could set the water temperature lower This will basically charge your home during the day so in the evening the home is warm and the heat pump simply maintains the heat This is not co...

Отзывы: